Catalogs > Industrial Controls Catalog > Motor Control, IEC > Control and Load Switches > Bulletin 194L Control and Load Switches
Bulletin 194L Control and Load Switches
| Introduction | Standards Compliance and Certifications | Product Overview | Product Selection |
| Accessories | Switching Diagrams | Specifications | Approximate Dimensions |
Electrical Ratings
| Performance Data | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | |||||||||||
| IEC Applications | |||||||||||||||||
| Rated voltage Ue ¬ | IEC-947 | [V] | 690 | 690 | 690 | 690 | 690 | 690 | |||||||||
| Isolating conditions acc. to VDE fulfilled up to rated impulse voltage Uimp | [kV] |
6 |
6 |
6 |
6 |
8 |
8 |
||||||||||
| Thermal rated current Ith¬ | 40 °C | IEC-947 | [A] | 16 | 20 | 25 | 30 | 32 | 45 | ||||||||
| Thermal rated current Ithe | 60 °C | IEC-947 | [A] | 12 | 16 | 20 | 25 | 32 | 45 | ||||||||
| Rated current Ie¬ | IEC-947 | 690V | [A] | 12 | 16 | 20 | 25 | 32 | 40 | ||||||||
| AC-1/ AC-21A |
Non-inductive or slightly inductive loads/ switching of resistive loads with slight overload |
||||||||||||||||
| AC-1 | Non-inductive or slightly inductive loads | SEV | 660V | [A] | 12 | 16 | 20 | 25 | 32 | 40 | |||||||
| AC22A | Switching of mixed resistive and inductive loads with slight overload | IEC-947 | 220…500V 690V |
[A] [A] |
12 12 |
16 16 |
20 20 |
25 25 |
32 32 |
40 40 |
|||||||
| AC-15 | Switching of inductive drives, motors, valves, and electromagnets. | IEC-947 | 220…240V 380…415V 500V |
[A] [A] [A] |
5 3 2 |
6 4 2.5 |
7 5 3 |
8 6 4 |
— | — | |||||||
| DC switching capacity Rated current Ie |
Contacts in series |
||||||||||||||||
| Rated Voltage [V] | 1 | 2 | 3 | 4 | 5 | 6 | 8 | ||||||||||
| 24 | 48 | 72 | 96 | 120 | 144 | 192 | [A] | 12 | 16 | 20 | 22 | — | — | ||||
| 48 | 96 | 144 | 192 | 240 | 288 | 384 | [A] | 10 | 12 | 16 | 18 | — | — | ||||
| 60 | 120 | 180 | 240 | 300 | 360 | 450 | [A] | 8 | 10 | 12 | 14 | 32 | 40 | ||||
| DC-21A | For resistive loads, T £ 1ms | 110 | 220 | 330 | 440 | 550 | 660 | — | [A] | 2 | 2.5 | 4 | 5 | — | — | ||
| 220 | 440 | 660 | — | — | — | — | [A] | 0.5 | 0.6 | 0.7 | 0.8 | — | — | ||||
| Ue max = 600V | 440 | — | — | — | — | — | — | [A] | 0.4 | 0.4 | 0.5 | 0.5 | — | — | |||
| Rated making/breaking capacity (= 1.5 x Ie) | |||||||||||||||||
| 25.2 | 50.4 | 75.6 | 100.8 | 126 | 151.2 | 201.6 | [A] | 18 | 24 | 30 | 33 | — | — | ||||
| 1.05 x Rated voltage [V] | 50.4 | 100.8 | 151.2 | 201.6 | 252 | 302.4 | 403.2 | [A] | 15 | 21 | 24 | 27 | — | — | |||
| For resistive loads, T Ith 1ms | 63 | 126 | 189 | 252 | 315 | 378 | 504 | [A] | 12 | 18 | 18 | 21 | 48 | 60 | |||
| 115.5 | 231 | 346.5 | 462 | 577.5 | — | — | [A] | 3 | 4.5 | 6 | 7.5 | — | — | ||||
| Ue max = 600V | 231 | 462 | — | — | — | — | — | [A] | 0.75 | 1.12 | 1.05 | 1.2 | — | — | |||
| 462 | — | — | — | — | — | — | [A] | 0.52 | 0.78 | 0.47 | 0.75 | — | — | ||||
| Rated current Ie | |||||||||||||||||
| Rated voltage [V] | 24 | 48 | 72 | 96 | 120 | 144 | 192 | [A] | 8 | 10 | 12 | 14 | 16 | 16 | |||
| 30 | 60 | 90 | 120 | 150 | 180 | 240 | [A] | 4.5 | 5.5 | 7 | 8 | — | — | ||||
| For inductive loads T = 50 ms | 48 | 96 | 144 | 192 | 240 | 288 | 384 | [A] | 1.5 | 2 | 2.5 | 3 | 8 | 8 | |||
| Rated voltage [V] | 60 | 120 | 180 | 240 | 300 | 360 | 450 | [A] | 1 | 1.2 | 1.5 | 1.8 | 4.8 | 4.8 | |||
| 110 | 220 | 330 | 440 | 550 | 660 | — | [A] | 0.4 | 0.5 | 0.6 | 0.7 | 2 | 2 | ||||
| 220 | — | — | — | — | — | — | [A] | — | — | — | — | 0.6 | 0.6 | ||||
| Rated making/breaking capacity (= 1.1 x Ie) | |||||||||||||||||
| 1.1 x Rated voltage [V] | 26.4 | 52.8 | 79.2 | 105.6 | 132 | 158.4 | 184.8 | [A] | 8.8 | 11 | 13.2 | 1.54 | — | 17.6 | |||
| 33 | 66 | 99 | 132 | 165 | 198 | 231 | [A] | 4.95 | 6.05 | 7.7 | 8.8 | — | — | ||||
| For inductive loads T = 50 ms | 52.8 | 105.6 | 158.4 | 211.2 | 264 | 316.8 | 369.6 | [A] | 1.65 | 2.2 | 2.75 | 3.3 | 8.8 | 8.8 |
|||
| Ue max = 600V | 66 | 132 | 198 | 264 | 330 | 396 | 462 | [A] | 1.1 | 1.32 | 1.65 | 1.98 | 5.28 | 5.28 |
|||
| 121 | 242 | 363 | 484 | 605 | — | — | [A] | 4.95 | 6.05 | 7.7 | 8.8 | 2.2 | 2.2 | ||||
| Power Lost | [W] | 0.3 | 0.5 | 0.6 | 0.9 | 0.8 | 1.4 | ||||||||||
| Rated power | |||||||||||||||||
| Pe | Contacts in series | ||||||||||||||||
| Rated voltage [V] DC-23A, DC-3, DC-5 For inductive loads, T £1 ms |
24 | 1 | [kW] | 0.12 | 0.15 | 0.20 | 0.25 | 0.30 | 0.30 | ||||||||
| 24 | 2 | [kW] | 0.20 | 0.25 | 0.30 | 0.37 | — | — | |||||||||
| 48 | 2 | [kW] | 0.25 | 0.30 | 0.37 | 0.50 | 0.50 | 0.50 | |||||||||
| 48 | 3 | [kW] | 0.30 | 0.37 | 0.50 | 0.75 | — | — | |||||||||
| 60 | 2 | [kW] | 0.25 | 0.30 | 0.37 | 0.50 | 1.00 | 1.00 | |||||||||
| 60 | 4 | [kW] | 0.37 | 0.50 | 0.75 | 1.00 | — | — | |||||||||
| 110 | 4 | [kW] | 0.50 | 0.75 | 1.00 | 1.20 | — | — | |||||||||
| 110 | 6 | [kW] | 1.00 | 1.20 | 1.40 | 1.60 | — | — | |||||||||
| 220 | 4 | [kW] | 0.37 | 0.50 | 0.75 | 1.00 | — | — | |||||||||
| 220 | 6 | [kW] | 1.00 | 1.20 | 1.40 | 1.50 | — | — | |||||||||
| ¬ See standards compliance listed on page IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
|||||||||||||||||
| T 32 and 40 A data for one contact in series. | |||||||||||||||||
| Performance Data, Continued | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | ||||||
| IEC Applications, Continued | ||||||||||||
| Rated making/breaking capacity (= 4 x Ie) | Contacts in series | |||||||||||
| Rated Voltage [V] | 25.2 25.2 50.4 50.4 63 63 115.5 115.5 231 231 |
1 2 2 3 2 4 4 6 4 6 |
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] |
20.0 33.3 21.0 25.0 16.6 24.6 18.1 36.4 6.7 18.1 |
25.0 41.6 25.0 30.8 20.0 33.3 27.2 43.6 9.1 21.8 |
33.3 50.0 30.8 42.0 24.6 50.0 36.4 51.0 13.6 25.2 |
41.6 61.6 41.6 62.4 33.2 66.4 44.0 58.2 18.2 27.2 |
50.0 — 41.6 — 66.6 — — — — — |
50.0 — 41.6 — 66.6 — — — — — |
|||
| DC-23A, DC-3, DC-5 | ||||||||||||
| For inductive loads, T £ 7.5 ms | ||||||||||||
| Rated breaking capacity | at 220V 0.45 [cos j] at 380V 0.45 [cos j] at 660V 0.45[cos j] |
[A] [A] [A] |
72 72 53 |
96 96 72 |
128 128 86 |
176 176 112 |
296 280 196 |
296 336 196 |
||||
| Rated power Pe¬ | IEC-947 | |||||||||||
| AC-2 | Slip-ring motors: starting, reversing and electric braking; star/delta starting |
3 Æ 3-pole |
240V 380V 415V 440V 500V 660V |
[kW] [kW] [kW] [kW] [kW] [kW] |
3 5.5 5.5 5.5 7.5 7.5 |
4 7.5 7.5 7.5 10 10 |
5.5 9 9 9 11 11 |
5.5 13 13 13 15 15 |
— — — — — — |
— — — — — — |
||
| AC-3 | Squirrel-cage motors: starting and stopping of running motors |
IEC-947 | ||||||||||
| 3 Æ 3-pole |
220…240V 380…440V 500V 660V |
[kW] [kW] [kW] [kW] |
2.2 4 5.5 5.5 |
3 5.5 7.5 7.5 |
4.5 7.5 10 8 |
5.5 11 13 11 |
7.5 15 — 18.5 |
7.5 18.5 — 18.5 |
||||
| 1 Æ 2-pole |
110V 220…240V 380…440V |
[kW] [kW] [kW] |
0.75 1.3 2.2 |
1.1 2.2 3.7 |
1.2 2.5 4.5 |
1.6 3.2 5.5 |
— 4 8 |
— 4 16 |
||||
| AC-4 | Squirrel-cage motors: starting, reversing, electric braking, inching |
IEC-947 | ||||||||||
| 3 Æ 3-pole |
220…240V 380…415V 440…550V |
[kW] [kW] [kW] |
0.75 1.5 1.5 |
1.5 2.2 2.2 |
3 3.7 3.7 |
4 5.5 5.5 |
5.5 7.5 7.5 |
5.5 7.5 11 |
||||
| 1 Æ 2-pole |
110V 240V 380V 440V |
[kW] [kW] [kW] [kW] |
0.18 0.37 0.75 0.75 |
0.37 0.75 1.1 1.1 |
0.55 1.5 1.8 1.8 |
0.75 2.2 3 3 |
— — — — |
— — — — |
||||
| ¬ See standards compliance listed on page IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
||||||||||||
| Performance Data, Continued | 12 A | 16 A | 20 A | 25 A | 32 A | 40 A | |||||
| IEC Applications, Continued | |||||||||||
| AC-23A | Occasional switching of motors and other highly inductive loads (criterion for selecting main switches) |
IEC-947 3Æ 3-pole |
220…240V 380…440V 500V 660V |
[kW] [kW] [kW] [kW] |
2.2 4 5.5 5.5 |
3 5.5 7.5 7.5 |
4.5 7.5 10 8 |
5.5 11 13 11 |
11 18.5 — 22 |
11 22 — 22 |
|
| 1Æ 2-pole |
110V 220…240V 380…440V |
[kW] [kW] [kW] |
0.75 1.3 2.2 |
1.1 2.2 3.7 |
1.2 2.5 4.5 |
1.6 3.2 5.5 |
— 5.5 11 |
— 5.5 11 |
|||
| Short-circuit ratings | |||||||||||
| Rated short-time current (1s) Strongest series fuse, not in enclosure Conditional rated short-circuit |
(gL characteristic) | [kArms] [A] [kA] |
0.48 20¬ 6 |
0.48 20¬ 6 |
0.6 20¬ 5 |
0.75 25¬ 5 |
0.8 35 5 |
0.8 40 5 |
|||
| Switch Rate | electrical | [ops/h] | 120 | 120 | 120 | 120 | 120 | 120 | |||
| CSA and UL Applications | |||||||||||
| Rated Voltage Ue | [V AC] | 600 | 600 | 600 | 600 | 600 | 600 | ||||
| Ampere Rating |
Pilot Duty General Use |
Contact class Non-inductive or slightly inductive loadT |
[A] | A600 12 |
A600 16 |
— 20 |
— 25 |
— 32 |
— 40 |
||
| Rated power Pe | UL (CSA) | (FLA) | (FLA) | (FLA) | (FLA) | ||||||
| Standard motor DOL rating (similar to AC-3) |
3Æ 3-pole |
120V 240V 480V 600V |
[Hp] [Hp] [Hp] [Hp] |
1 (7.2) 2 (6.8) 5 (7.6) 5 (6.1) |
1.5 (12) 3 (9.6) 7.5 (11) 7.5 (9) |
2 (13.6) 4 (12.4) 8 (11.6) 10 (11) |
3 (19.2) 6 (18) 12 (17) 15 (17) |
5 (30.4) 7.5 (22) 20 (27) 20 (22) |
5 (30.4) 10 (28) 25 (34) 25 (27) |
||
| 1Æ 2-pole |
120V 240V 480V 600V |
[Hp] [Hp] [Hp] [Hp] |
0.5 (9.8) 1 (8.0) 2 (6.0) 3 (6.8) |
.75 (13.8) 1.5 (10.0) 3 (8.5) 3 (6.8) |
1 (16) 2 (12) 4 (11.2) 5 (11.2) |
1.5 (20) 3 (17) 6 (17) 7.5 (16) |
2 (24) 5 (28) 7.5 (21) 10 (20) |
2 (24) 5 (28) 10 (26) 15 (27) |
|||
| Heavy motor load, reversing Rating (similar to AC-4) Max. back-up fuse |
3Æ 3-pole (gG characteristic) |
120V 240V |
[Hp] [Hp] [A] |
— — 35 |
— — 55 |
— — 60 |
— — 80 |
||||
| Short Circuit Ratings |
Maximum Short Circuit Prospective Fault Current Maximum Fuse Size |
[kA] [A] |
5 35 |
5 55 |
5 60 |
5 80 |
|||||
| Switching Rate | electrical | [ops/h] | 120 | 120 | 120 | 120 | 120 | 120 | |||
Mechanical Data
| Performance Data | 12/16 A | 20/25 A | 32/40 A | ||
| Protection class acc. to IEC 529 | Handles Switch Bodies |
IP66 IP20 |
IP66 IP20 |
IP66 IP20 |
|
| Mechanical Endurance | [mil.ops] | 1 | 1 | 1 | |
| Switching rate | mechanical | [ops/h] | 1200 | 1200 | 1200 |
| Maximum Wire Gauges | |||||
| rigid wire fine strands |
AWG [mm2] AWG [mm2] |
(2)18…12 (2)1…2.5 (2)18…12 (2)1…2.5 |
(2)16…10 (2)1.5…6 (2)16…10 (2)1.5…4 |
(2)12…8 (2)4…10 (2)14…10 (2)2.5…6 |
|
Environmental Data
| Performance Data | 12/16/20/25 A | 32/40 A | |
| Ambient temperature | |||
| Operation | 25…+60 °C (13…+140 °F) |
25…+60 °C (13…+140 °F) |
|
| Storage | 40…+80 °C (40…+176 °F) |
40…+80 °C (40…+176 °F) |
|
| ¬ Does not apply to switches in enclosure. | |||
| T Suitable for switching off-load (AC-20) above 660V, but only up to 660V for switches with screws at the rear. | |||
| See standards compliance listed on page IEC 60947-3 Low-voltage switchgear and control gear part 3 UL 508 CSA: C22.2 No. 14. |
|||