Bulletin 194E, 16…100 A
|
Bulletin 194E IEC Load Switches
- Suitable as At-Motor Disconnect Switch (UL508)
- 16, 25, 32, 40, 63, 80, 100 A Inductive Load-Rated Switches
- IP66/ UL Type 1/3/3R/12 Operating Handles
- IP2LX Finger-Safe Terminals
- 3- and 6-Pole Versions; Add-on Accessory Poles to Make 4-, 5-, 7- and 8-Pole Units
- Front/Door or DIN/Base Mounting Configurations
- Available in OFF-ON and Changeover Configurations
- 3- and 6-Pole Enclosed Switches
- Optional Thermoplastic Enclosures
- Positive-Guided Actuation
- Padlockable Handles Available (up to 3 padlocks)
Standards Compliance and Certifications
Standards Compliance
IEC 60947-1
IEC 60947-3 Low-voltage
switchgear and control gear
part 3
UL 508
CSA: C22.2 No. 14
Certifications
UL Listed (File No. E14841, Guide NLRV)
CSA Certified (LR 13908)
IEC and BS
CE
RINA — Italian Naval Registry
CCC
Description
Bulletin 194E load switches are designed for use as local motor isolation or other load switch applications. Available with 3- and 6-pole versions with add-on additional poles, grounding and neutral terminals and auxiliary contacts, the Bulletin 194E shares the same operating handles as the Bulletin 194L Control and Load Switches.
Bulletin 194E switches are offered in two mounting styles, Front/Door and Base/DIN configurations for a variety of installations. Switch body styles for Bulletin 194E base-mounted switches include standard interlock shaft; Bulletin 194E front-mounted switches include standard shaft. Two-position OFF-ON switch is used to connect or disconnect a variety of inductive loads, including solenoids, valves, magnetic starters, relays, and motors. Handles featuring marked legend plates are available in Selector-Knob, Disk-Style, Rectangular-Style and Key-Operated versions. Selector-Knob versions are available in three sizes. Most handles are available in colors of grey/black or red/yellow and have padlockable versions.
Cat. No. Explanation
194E 16…100 A Small-Frame Switches (Handles listed on Bulletin 194E/194L Handles (for use with Bulletin 194E Switches))
| 194E | | A | 32 | | 1753 |
| a | b | c |
| a | b | c | |||||||
| Installation Type | Load Size | Function/Circuit Diagram Ref. # | |||||||
| Code | Description | Code | Description | Code | Function | Description | Circuit Diagram Ref. # | ||
| A | Base/DIN mounting | 16 | 16 A | 1753 | OFF/ON | 3-pole, 2-position (90°) | 1753 | ||
| E | Front/Door mounting | 25 | 25 A | 1756 | OFF/ON | 6-pole, 2-position (90°) | 1756 | ||
| 32 | 32 A | 1783 | OFF/ON | 3-pole, 2-position (90° - inverted) | 1783 | ||||
| 40 | 40 A | 3753 | Changeover | 3-pole, 3-position (90°) | 3753 | ||||
| 63 | 63 A | ||||||||
| 80 | 80 A | ||||||||
| 100 | 100 A | ||||||||
Product Selection
Frequently Ordered⋆ OFF-ON 3-Pole Switch (includes operating shaft) (Handles listed on Bulletin 194E/194L Handles (for use with Bulletin 194E Switches))
Frequently Ordered⋆ OFF-ON 6-Pole Switch (includes operating shaft) (Handles listed on Bulletin 194E/194L Handles (for use with Bulletin 194E Switches))
Bulletin 194E/194L Handles (for use with Bulletin 194E Switches)
Cat. No. Explanation
| 194L | | HE | 6 | N | | 175 | ||
| a | b | c | d |
| a |
| Code |
| HC |
| HE |
| b | |||
| Code | Use with Handle Type |
Handle Legend Plate Size |
Use With 194E Switch Size |
| 4 | A, E, I, L | 48 mm x 48 mm (1-57/64 in. x 1-57/64 in.) |
194E-16…63 A |
| S | 48 mm x 62 mm (1-57/64 in. x 2-7/16 in.) |
194E-25…63 A | |
| 6 | A, E, I, L | 64 mm x 64 mm (2-33/64 in. x 2-33/64 in.) |
194E-25…100 A |
| G, N § | 67 mm x 67 mm (2-41/64 in. x 2-41/64 in.) |
194E-25…100 A | |
| S | 64 mm x 78 mm (2-33/64 in. x 3-5/64 in.) |
194E-25…100 A | |
| 8 | A, I | 88 mm x 88 mm (3-15/32 in. x 3-15/32 in.) |
194E-40…100 A |
| G, N♣ | 90 mm x 90 mm (3-35/64 in. x 3-35/64 in.) |
194E-40…100 A | |
| c | |
| Code | Legend Plate Type |
| A | Square |
| I | Square |
| E | Square/lockable |
| L | Square/lockable |
| G | Disc/lockable (up to 3 locks) |
| N | Disc/lockable (up to 3 locks) |
| S | Large Square with extra legend area |
| d | ||
| Code | Description | Legend Marking |
| 175 | O-I |
|
| 175I | OFF-ON | |
| 350 | 1-0-2 (Reversing) |
|
| 375 | 1-0-2 (90 degrees) (Changeover) |
|
| 178 | O-I |
|
| 178I | OFF-ON | |
⋆ For 22.5 mm mounting hole style handle (code HC), select either handle type A, E, I, or L with 48 x 48 mm legend plate size (code 4) only or handle type G or N with 64 x 64 mm legend plate size (code 6) only.
Order 194E- 16 A Type G and N handles as Cat. No. 194E-HE4N-175 or 194E-HE4G-175
§ Use Type G and N with ON-OFF function only (selection "d", code -175)
♣ Cat. No. 194R-HE front-mounting switch only
Frequently Ordered 194L Handles — OFF-ON Base/Front-Mounted 3- and 6-Pole Switch Handles
(Switch Body listed on Frequently Ordered⋆ OFF-ON 3-Pole Switch (includes operating shaft) (Handles listed on Bulletin 194E/194L Handles (for use with Bulletin 194E Switches)))
| Handle Type | Degree of Protection | Handle Color | Bezel Plate Size | For Use With | Legend Plate Marking | Cat. No. |
| E | IP66 (UL Type 1) (UL Type 3/3R/12) | Black/Grey | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194E-16…63 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 | 194L-HE4E-175 |
| OFF-ON | 194L-HE4E-175I | |||||
| L | Red/Yellow | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194E-16…63 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 | 194L-HE4L-175 | |
| OFF-ON | 194L-HE4L-175I | |||||
| G | IP66 (UL Type 3/3R/12) | Black/Grey | 54 x 54 mm (2-1/8 x 2-1/8 in.) |
194E-16 A | 0-1 OFF-ON |
194E-HE4G-175 |
| 67 x 67 mm (2-41/64 x 2-41/64 in.) |
194E-25…100 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 OFF-ON |
194L-HE6G-175 | |||
| 88 x 88 mm (3-15/32 x 3-15/32 in.) |
194E-40…100 A | 0-1 OFF-ON |
194L-HE8G-175 | |||
| N | Red/Yellow | 54 x 54 mm (2-1/8 x 2-1/8 in.) |
194E-16 A | 0-1 OFF-ON |
194E-HE4N-175 | |
| 67 x 67 mm (2-41/64 x 2-41/64 in.) |
194E-25…100 A 194L-E12…40 A, -1753 194L-A12…40 A, -1753 |
0-1 OFF-ON |
194L-HE6N-175 | |||
| 88 x 88 mm (3-15/32 x 3-15/32 in.) |
194E-40…100 A | 0-1 OFF-ON |
194L-HE8N-175 | |||
| L | IP66 (UL Type 3/3R/12) | Red/Yellow | 48 x 48 mm (1-57/64 x 1-57/64 in.) |
194L-E12…40 A, -1753 | 0-1 | 194L-HC4L-175 |
| OFF-ON | 194L-HC4L-175I | |||||
Bulletin 194E Open and Enclosed Switch Kits
Cat. No. Explanation
| 194E | | Y | 32 | | 1753 | | 6N |
| a | b | c | d |
| a | |
| Code | Installation Type |
| A | Base/DIN mounting, open type switch |
| E | Front/Door mounting, open type switch |
| Y | Enclosed base mounting switch with handle (Uses IP66 ABS thermoplastic enclosure) |
| b | |
| Code | Load Size |
| 16 | 16 A⋆ |
| 25 | 25 A |
| 32 | 32 A |
| 40 | 40 A |
| 63 | 63 A |
| 80 | 80 A |
| 100 | 100 A |
⋆ For 16 A Enclosed Switch: use "16M" (3-pole enclosure has M16/20 knockouts, 6-pole 16 A enclosure has M25/32 knockouts). For 25/32 A Enclosed Switch with M20/25 metric knockouts: use 25M or 32M.
| c | |
| Code | Configuration |
| 1753 | 3-pole OFF/ON (90°) |
| 1756 | 6-pole OFF/ON (90°) |
| d | |
| Code | Handle Style |
| 4N | 194E-HE4N-175 (use with 16 A switch) |
| 4G | 194E-HE4G-175 (use with 16 A switch) |
| 4A | 194L-HE4A-175 (use with 16…100 A switch) |
| 6N | 194L-HE6N-175 (use with 25…100 A switch) |
| 6G | 194L-HE6G-175 (use with 25…100 A switch) |
| 6A | 194L-HE6A-175 (use with 25…100 A switch) |
Frequently Ordered Switch Kits — OFF-ON Front- and Base-Mounted 3-Pole Switch With Cat. No. 194L‑HE6N‑175 Red/Yellow Handle
Base-Mounting Distribution Switches (handles are pre-assembled to switch)
Frequently Ordered Enclosures — 3- and 6-Pole Enclosed Switches
With Cat. No. 194L-HE6N-175 Red/Yellow Operating Handles
Bulletin 194E Enclosed Disconnect Load Switches with 194R Handles (with Defeater, suitable for 3 padlocks)
Cat. No. Explanation ⋆
| 194E | | FA | 32 | E | | P11 | | P11 | | 6 |
| a | b | c | d | d | e |
| a | |
| Code | Enclosure Type |
| FA | UL Type 3/4/12, IP66 painted steel, hinged, for 16…100 A switches |
| GA | UL Type 3/4/12, IP66 painted steel, hinged, in 6 x 6 x 4 in. size, for 16…32 A 3-pole switches § |
| CA | UL Type 4/4X, IP66 stainless steel, hinged, for 16…100 A switches |
| DA | UL Type 4/4X, IP66 stainless steel, hinged, in 6 x 6 x 4 in. size, for 16…32 A 3-pole switches § |
| KA | UL Type 3/4/4X, IP66 non-metallic, for 16…100 A switches |
| AA | UL Type 1, IP54 painted steel, hinged, for 16…100 A switches (Same enclosure as FA without gasketing) |
| b | |
| Code | Load Size |
| 16 | 16 A |
| 20 | 25 A |
| 32 | 32 A |
| 40 | 40 A |
| 63 | 63 A |
| 80 | 80 A |
| 00 | 100 A |
| c | |
| Code | Handle Color (194R-HS _ _) |
| Blank | Grey/black |
| E | Red/yellow |
| d | |
| Code | Left Side + Right Side Modifications⋆ |
| Blank | No Option |
| -P11 | 1 N.O. + 1 N.C. auxiliary contacts |
| -PL11 | 1 N.O. + 1 N.C.L.B. auxiliary contacts |
| -P22 | 2 N.O. + 2 N.C. auxiliary contacts |
| -PD10 | 1 N.O. E.B.∆ |
| -NP | Additional pole |
| -PE | Grounding pole |
| -TN | Neutral pole |
| e | |
| Code | Switch Type |
| Blank | 3-pole switch |
| -6 | 6-pole switch♣ |
⋆ Modifications: Up to two suffix codes may be added to an enclosed disconnect load switch. See Guidelines, Accessory Configuration Guidelines. If only one accessory is chosen, it is mounted on the left side of the switch.
To order the cat. no. 194E-FA40/FA63 or 194E-CA40/CA63 in the larger 80/100A sized enclosure, add an X after the handle color. For example, Cat. No. 194E-FA40E becomes Cat. No. 194E-FA40EX.
§ GA and DA type enclosures: use with 3-pole 16…32 A switches only.
♣ Special order; allow for longer delivery time.
∆ See the Accessory Configuration Guidelines on Accessory Configuration Guidelines.
Frequently Ordered Bulletin 194E Enclosed Switches with Bulletin 194R Handle
| Description | Rated Current (A) | Dimension Reference | Handle Color | Cat. No.⋆ |
| Stainless steel enclosure, IP66/Type 4/4X | 25 | A1 | Black | 194E-CA20 |
| Red/Yellow | 194E-CA20E | |||
| 32 | A1 | Black | 194E-CA32 | |
| Red/Yellow | 194E-CA32E | |||
| 63 | A1 | Black | 194E-CA63 | |
| Red/Yellow | 194E-CA63E | |||
| Painted steel enclosure, IP66/Type 3/4/12 | 25 | A1 | Black | 194E-FA20 |
| Red/Yellow | 194E-FA20E | |||
| 32 | A1 | Black | 194E-FA32 | |
| Red/Yellow | 194E-FA32E | |||
| 40 | A1 | Black | 194E-FA40 | |
| Red/Yellow | 194E-FA40E | |||
| Non-metallic enclosure, IP66/Type 4/4X | 25 | C1 | Black | 194E-KA20 |
| Red/Yellow | 194E-KA20E | |||
| ⋆ Modifications: Up to two suffix codes may be added to an enclosed disconnect load switch. See Guidelines, Accessory Configuration Guidelines. If only one accessory is chosen, it is mounted on the left side of the switch. | ||||
Accessories
IEC Load Switch Accessories
194E-E16…100 A, Front/Door Mounting
|
194E-A16…100 A, Base/DIN Rail Mounting
|
Accessory Configuration Guidelines
Accessory drawings represent modular, snap-on features of Bulletin 194E accessories. They are not suggesting possible accessory configurations. Use the following guidelines for choosing Bul. 194E accessory configurations.
- Up to two accessories may be added to the Bulletin 194E switch body.
- For the Bul. 194E 16, 25, 32, 40, or 63 A switches, the early break auxiliary contact (-PD10) may only be used in the following configurations:
As a single unit on either side of the switch
As a single unit on a side when used with a switch + 4th pole (-NP)
As a single unit on a side when used with a switch + ground terminal (-PE)
As a single unit on a side when used with a switch + neutral terminal (-TN)
No other auxiliary contact may be used in combinations with an early break auxiliary contact (-PD10)
- Other combinations of auxiliary contacts are permissable.
- For the Bul. 194E 80 and 100 A switches, any combination of auxiliary contacts, 4th pole, ground terminal, neutral terminal, and -PD10 is permissable.
| 6-Pole Mechanical Coupling⋆ | For Use With | Cat. No. |
|
194E-16 | 194E-G3821 |
| 194E-25/32 | 194E-G3660 | |
| 194E-40/63 | 194E-G3661 | |
| 194E-80/100 | 194E-G3662 | |
| Description | For Use With | Pkg. Qty. | Cat. No. |
| Additional Earth/Ground and Neutral Terminals — For Thermoplastic Enclosure |
194L-G3663, G3664, G3665, G3666 | 5 | 194E-G3673 |
| 194L-G3572 and G3676 | 5 | 194E-G3653 | |
⋆ User must order (2) Bulletin 194E 3-pole switches separately.
Coupling for changeover switch not available. Changeover switch must be ordered as a factory-assembled device (e.g., 194E-A25-3753).
Operating Shafts
Bulletin 194E Load Switch Cat. No. Shaft Selection for use with 194E and 194L Thermoplastic Enclosures
| Rated Current [A] | 3-Pole Switches (-1753 suffix) | 6-Pole Switches (-1756 suffix) | Changeover Switches (-3753 suffix) | |||
| 194E-E… | 194E-A… | 194E-E… | 194E-A… | 194E-E… | 194E-A… | |
| 16 | plastic shaft (Cat. No. 194L-G3380) | plastic shaft (Cat. No. 194L-G2830) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 25 | plastic shaft (Cat. No. 194L-G3380) | plastic shaft (Cat. No. 194L-G2830) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 32 | plastic shaft (Cat. No. 194L-G3380) | plastic shaft (Cat. No. 194L-G2830) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 40 | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 63 | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194L-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 80 | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
| 100 | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) | metallic shaft (Cat. No. 194E-G3688) | metallic shaft (Cat. No. 194E-G3687) |
Shaft Extension Kits
|
Length | For Use With | Pkg. Qty. | Cat. No. |
| 24 mm (15/16 in.) Per Extension | 194E-A… | 10 | 194L-G2853 | |
| Shaft Extension | ||||
Metal Shaft Extensions — With Padlock Provision in OFF Position
|
Length | For Use With | Pkg. Qty. | Cat. No. |
| 110…235 mm (4-21/64…9-1/4 in.) |
194E-A… | 1 | 194L-G3393 | |
| 230…350 mm (9-3/64…13-51/64 in.) |
194L-G3394 | |||
Metal Shaft Adaptor Kits — For use with 194R Type 4/4X Handles
Other Accessories
194L/194E 22.5 mm Mounting Hole Style Handles (Type B, D) (For Front-Mounted Switches)
Additional Legend Plates/Frames
⋆ Custom-engraved legend plates available. To order, use publication 194L-PP002*. Custom-Engraved legend plates require a 50 pc minimum order and a 6 week lead time.
Shaft for Enclosures
| Enclosure Type | Suitable For | Suitable For | ||||
| 194L (Base-Mounted Switches) |
No. of Contacts | Shaft | Use with 194E Switch |
No. of Poles | Shaft Required | |
| 194L-G3572 | 194L-A12(16) | 1/2 | 194L-G3195 | 194E-A25(32) | 3 and 4 | 194L-G3194 |
| 194L-G3576 | 194L-A12(16) | 3/4 | Standard | |||
| 194L-A20(25) | 1/2 | 194L-G3194 | ||||
| (95 x 150 x 86 mm) | 194L-A20(25) | 3/4 | Standard | |||
| 194L-G3573 | 194L-A12(16) | 5/6 | 194L-G3195 | — | — | — |
| 194L-G3577 | 194L-A12(16) | 7/8 | 194L-G3194 | |||
| 194L-A12(16) | 9/10 | Standard | ||||
| 194L-A20(25) | 5/6 | 194L-G3194 | ||||
| (95 x 150 x 111 mm) | 194L-A20(25) | 7/8 | Standard | |||
| 194E-G3663 | — | — | — | 194E-A40(63) | 3 and 4 | 194L-G3194 |
| 194E-G3664 | 194E-A25(32) | 6 | Standard | |||
| (125 x 180 x 105 mm) | ||||||
| 194E-G3665 | — | — | — | 194E-A80(100) | 3 and 4 | 194E-G3707 |
| 194E-G3666 | 194E-A40(63) | 6 | Standard | |||
| (175 x 230 x 120 mm) | ||||||
Accessory Combinations in Enclosure
| Enclosure Type | Switch | No. of Poles |
Shaft | Aux. Contacts (single or double) |
Additional Pole Block |
On Switch | On Enclosure | ||
| Neutral Terminal Block |
Ground Terminal Block |
Neutral Terminal Block |
Ground Terminal Block |
||||||
| 194L-G3572 (ABS) 194L-G3576 (Noryl) |
194E-A25(32) | 3 | 194L-G3194 | X | X | ||||
| X | X | ||||||||
| X | X | ||||||||
| X | X | ||||||||
| X | X | ||||||||
| X | X | ||||||||
| X | X | ||||||||
| (95 x 150 x 86 mm) | X | X | |||||||
| 194E-G3663 (ABS) 194E-G3664 (Noryl) |
194E-A40(63) | 3 | 194L-G3194 | X | X | X | X | ||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| (125 x 180 x 105 mm) | 194E-A25(32) | 6 | 194E-G3707 | X | X | ||||
| 194E-G3665 (ABS) 194E-G3666 (Noryl) |
194E-A80(100) | 3 | 194E-G3707 | X | X | X | X | ||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| X | X | X | X | ||||||
| (175 x 230 x 120 mm) | 194E-A40(63) | 6 | 194E-G3707 | 1L+1R | X | X | |||
Specifications
Electrical Ratings
| Performance Data | 16 A | 25 A | 32 A | 40 A | 63 A | 80 A | 100 A | Aux. Contacts |
||||
| IEC Applications | ||||||||||||
| Rated operational voltage (Ue): IEC⋆ | [V] | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | |||
| Rated operational voltage (Ue): UL, CSA | [V] | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | |||
| Rated isolation voltage (Ui): IEC/UL, CSA | [V] | 690/600 | 690/600 | 690/600 | 690/600 | 690/600 | 690/600 | 690/600 | 690/600 | |||
| Rated impulse voltage (Uimp): UL, CSA | [kV] | 8 | 8 | 8 | 8 | 8 | 8 | 8 | 8 | |||
| Test voltage, (Ui) 1 minute | [kV] | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | |||
| Lost power per pole | [W] | 0.58 | 1.0 | 1.5 | 1.6 | 2.4 | 3.6 | 5.5 | 0.4 | |||
| Rated frequency | [Hz] | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
| Conventional free air thermal current Ith⋆ | [A] | 25 | 40 | 50 | 63 | 75 | 100 | 120 | 12 | |||
| Conventional enclosed thermal current Ie⋆ | [A] | 20 | 32 | 40 | 50 | 63 | 80 | 100 | 10 | |||
| Rated current Ie⋆ | [A] | 16 | 25 | 32 | 40 | 63 | 80 | 100 | 10 | |||
| AC-1/ |
Non-inductive or only slightly inductive loads |
|||||||||||
| AC-21A |
Switching of resistive loads with slight overload |
|||||||||||
| Rated power Pe | ||||||||||||
| AC-23A |
Occasional switching of 3Æ motors and other highly inductive loads (criterion for selecting main switches) |
230V | [kW] | 5.5 | 7.5 | 7.5 | 15 | 18.5 | 22 | 30 | — | |
| 400V | [kW] | 7.5 | 11 | 15 | 22 | 30 | 37 | 55 | — | |||
| 690V | [kW] | 7.5 | 11 | 15 | 18.5 | 22 | 37 | 45 | — | |||
| AC-3 |
Squirrel-cage motors; starting and stopping of running motors |
230V | [kW] | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | — | |
| 400V | [kW] | 5.5 | 7.5 | 11 | 15 | 18.5 | 30 | 37 | — | |||
| 690V | [kW] | 5.5 | 7.5 | 11 | 15 | 18.5 | 30 | 22 | — | |||
| Short circuit current (co-ordination type 2) Rated conditional short-circuit current Maximum fuse rating of circuit (type g,G) Rated short-time current Icw (1 s) |
400/415V | [kA] | 20 | 20 | 15 | 20 | 15 | 30 | 25 | — | ||
| [A] | 20 | 25 | 35 | 50 | 63 | 80 | 100 | — | ||||
| [A] | 800 | 900 | 900 | 1300 | 1300 | 2500 | 2500 | — | ||||
| Rated breaking capacity AC23A (cosf 0.45) | 230V | [A] | 156 | 296 | 296 | 484 | 484 | 780 | 780 | — | ||
| 400V | [A] | 120 | 256 | 256 | 504 | 504 | 800 | 800 | — | |||
| 690V | [A] | 70 | 136 | 136 | 196 | 196 | 376 | 376 | — | |||
| DC switching capacity | 1 pole | |||||||||||
| Rated current Ie | 24/48V | [A] | 20 | 25 | 32 | 40 | 63 | 80 | 100 | — | ||
| 110V | [A] | 5 | 5 | 6 | 8 | 10 | 16 | 20 | ||||
| 220V | [A] | 1 | 1 | 1 | 1.5 | 15 | 3 | 3 | ||||
| 440V | [A] | 0.5 | 0.5 | 0.5 | 0.6 | 0.6 | 0.7 | 0.7 | ||||
| DC-21A |
For resistive loads, T £ 1 ms Ue max = 660V |
2 poles in series |
96V | [A] | 20 | 25 | 32 | 40 | 63 | 80 | 100 | — |
| 110V | [A] | 20 | 23 | 25 | 32 | 50 | 70 | 80 | ||||
| 220V | [A] | 5 | 5 | 6 | 8 | 10 | 16 | 20 | ||||
| 440V | [A] | 1 | 1 | 1 | 1.5 | 1.5 | 3 | 3 | ||||
| 600V | [A] | 0.6 | 0.6 | 0.6 | 0.8 | 0.8 | 1 | 1 | ||||
| 3 poles in series |
110V | [A] | 20 | 25 | 32 | 40 | 63 | 80 | 100 | — | ||
| 220V | [A] | 13 | 13 | 15 | 20 | 28 | 50 | 63 | ||||
| 440V | [A] | 2.2 | 2.2 | 2.2 | 3.6 | 3.6 | 6.5 | 6.5 | ||||
| 600V | [A] | 1.3 | 1.5 | 1.5 | 2 | 2 | 3 | 3 | ||||
| Rated power Pe | 3 poles in series |
— | ||||||||||
| DC-23A, DC-3, DC-5 | 90V | [kW] | 1 | 1.3 | 1.5 | 2.9 | 4.1 | 5.1 | 7.2 | |||
| For inductive loads, T £ 15 ms |
110V | [kW] | 1 | 1.1 | 1.3 | 2.2 | 3.3 | 5.5 | 7 | |||
| 220V | [kW] | 0.8 | 0.9 | 1.1 | 1.7 | 2 | 3.5 | 4.4 | ||||
| 440V | [kW] | 0.6 | 0.6 | 0.6 | 0.9 | 0.9 | 1.1 | 1.1 | ||||
| 600V | [kW] | 0.4 | 0.4 | 0.4 | 0.5 | 0.5 | 0.9 | 0.9 | ||||
| ⋆ See standards compliance listed on Standards Compliance. | ||||||||||||
Electrical Ratings, Continued
| Performance Data | 16 A | 25 A | 32 A | 40 A | 63 A | 80 A | 100 A | Aux. Contacts |
||
| UL/CSA Applications | ||||||||||
| Continuous current | [A] | 16 | 25 | 32 | 40 | 63 | 80 | 100 | — | |
| Heavy Pilot Duty | [AC] | A600 | A600 | A600 | — | — | — | — | A600 | |
| Standard Duty | [DC] | — | — | — | — | — | — | — | Q600 | |
| Motor rating 60 Hz | 120V, 1P | [FLA] | 16 | 16 | 16 | 24 | 34 | 56 | 80 | — |
| Single-phase (2 poles) | [Hp] | 1 | 1 | 1 | 2 | 3 | 5 | 7.5 | ||
| 240V, 1P | [FLA] | 12 | 12 | 17 | 17 | 28 | 50 | 68 | ||
| [Hp] | 2 | 2 | 3 | 3 | 5 | 10 | 15 | |||
| 480V, 1P | [FLA] | 8.5 | 8.5 | 14 | 21 | 26 | 34 | 68 | ||
| [Hp] | 3 | 3 | 5 | 7.5 | 10 | 15 | 30 | |||
| 600V, 1P | [FLA] | 11.2 | 11.2 | 11.2 | 16 | 20 | 27 | 44 | ||
| [Hp] | 5 | 5 | 5 | 7.5 | 10 | 15 | 25 | |||
| Three-phase | 120V, 3P | [FLA] | 13.6 | 13.6 | 19.2 | 30.4 | 40 | 56 | 84 | — |
| [Hp] | 2 | 2 | 3 | 5 | 7.5 | 10 | 15 | |||
| 240V, 3P | [FLA] | 9.6 | 15.2 | 22 | 28 | 42 | 68 | 80 | ||
| [Hp] | 3 | 5 | 7.5 | 10 | 15 | 25 | 30 | |||
| 480V, 3P | [FLA] | 11 | 14 | 21 | 27 | 34 | 52 | 65 | ||
| [Hp] | 7.5 | 10 | 15 | 20 | 25 | 40 | 50 | |||
| 600V, 3P | [FLA] | 11 | 11 | 17 | 22 | 27 | 52 | 52 | ||
| [Hp] | 10 | 10 | 15 | 20 | 25 | 50 | 50 | |||
Mechanical Data
| Performance Data | 16 A | 25…32 A | 40…63 A | 80…100 A | Aux. Contacts |
||
| Protection class according to IEC 529 | |||||||
| Motor rating 60 Hz | |||||||
| handles | IP66 | IP66 | IP66 | IP66 | IP66 | ||
| switch bodies | IP20 | IP20 | IP20 | IP20 | IP20 | ||
| Mechanical life | [million operations] | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | |
| Max wire gauges | |||||||
| Terminal size per IEC 947-1 | A4 | A6 | A7 | A9 | 2xA2 | ||
| rigid wire | 1/2 conductor | [AWG] [mm2] |
(1)16…10/(2)16…12 (1)1…10/(2)1…4 |
(1)14…8/(2)14…10 (1)1.5…16/(2)1.5…6 |
(1)12…4/(2)12…8 (1)2.5…25/(2)2.5…16 |
(1)10…1/(2)10…4 (1)4…50/(2)4…25 |
18…14 0.75…2.5 |
| fine strands | 1/2 conductor | [AWG] [mm2] |
(1)16…8/(2)16…12 (1)1.5…6/(2)1.5…4 |
(1)14…8/(2)14…10 (1)1.5…10/(2)1…6 |
(1)12…4/(2)12…8 (1)2.5…16/(2)2.5…10 |
(1)10…1/(2)10…6 (1)4…35/(2)4…16 |
18…14 0.5…2.5 |
| Tightening torque | [Nm]/[lbin] | 1.4/12.2 | 1.4/12.2 | 2.8/24.5 | 5.6/50 | 1/8.8 | |
Environmental Data
| Storage | -40…+80 °C (-40…+176 °F) |
| Operation | -25…+60 °C (-13…+140 °F) |
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Front Installation Cat. No. 194E-E…
|
|
| Handles | ||
| Cat. No. | P | Q |
| 194L-HE4A | 28 (1-7/64) |
48 x 48 (1-57/64 x 1-57/64) |
| 194L-HE4I | 28 (1-7/64) |
48 x 48 (1-57/64 x 1-57/64) |
| 194L-HE4S | 28 (1-7/64) |
48 x 62 (1-57/64 x 2-7/16) |
| 194E-HE4N | 34 (1-11/32) |
54 x 54 (2-1/8 x 2-1/8) |
| 194E-HE4G | 34 (1-11/32) |
54 x 54 (2-1/8 x 2-1/8) |
| 194L-HE6A | 28 (1-7/64) |
64 x 64 (2-33/64 x 3-5/64) |
| 194L-HE6I | 28 (1-7/64) |
64 x 64 (2-33/64 x 3-5/64) |
| 194L-HE6S | 28 (1-7/64) |
64 x 78 (2-33/64 x 3-5/64) |
| 194L-HE6N | 34 (1-11/32) |
67 x 67 (2-41/64 x 2-41/64) |
| 194L-HE6G | 34 (1-11/32) |
67 x 67 (2-41/64 x 2-41/64) |
| Switch Body | ||||||
| Use with Cat. No. |
B1⋆ | B2 | F | H | L | G |
| 194E-E16 | 28 (1-7/64) |
N/A | 36 (1-37/64) |
63 (2-31/64) |
51 (2) |
90 (3-35/64) |
| 194E-E25/32 | 36 (1-27/64) |
N/A | 45 (1-25/32) |
64 (2-33/64) |
60 (2-3/8) |
90 (3-1/2) |
| 194E-E40/63 | 48 (1-57/64) |
36 (1-27/64) |
54 (2-1/8) |
72 (2-27/32) |
74 (2-29/32) |
108 (4-1/4) |
| 194E-E80/100 | 48 (1-57/64) |
36 (1-27/64) |
72 (2-27/32) |
90 (3-35/64) |
90 (3-35/64) |
144 (5-11/16) |
| ⋆ Does not apply to 194E-40/63A, 6-Pole Switches. Use B2 dimensions for 6-pole devices. | ||||||
| For 6-pole switches, add 1 in. to the "L" dimension. | ||||||
Cat. No. 194E-E Switch Body with Cat. No. 194L-HC4A Handle for 22.5 mm Hole Mounting Style
|
| Type | L |
| 194E-E16 | 76 (3) |
| 194E-E25/32 | 84.5 (3-21/64) |
| 194E-E40/63 | 98.5 (3-7/8) |
| 194E-E80/100 | 114.5 (4-33/64) |
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Mounting Cat. No. 194E-A…
|
|
| Handles | ||
| Cat. No. | P | Q |
| 194L-HE4A | 28 (1-7/64) | 48 x 48 (1-57/64 x 1-57/64) |
| 194L-HE4I | 28 (1-7/64) | 48 x 48 (1-57/64 x 1-57/64) |
| 194L-HE4S | 28 (1-7/64) | 48 x 62 (1-57/64 x 2-7/16) |
| 194E-HE4N | 34 (1-11/32) | 54 x 54 (2-1/8 x 2-1/8) |
| 194E-HE4G | 34 (1-11/32) | 54 x 54 (2-1/8 x 2-1/8) |
| 194L-HE6A | 28 (1-7/64) | 64 x 64 (2-33/64 x 3-5/64) |
| 194L-HE6I | 28 (1-7/64) | 64 x 64 (2-33/64 x 3-5/64) |
| 194L-HE6S | 28 (1-7/64) | 64 x 78 (2-33/64 x 3-5/64) |
| 194L-HE6N | 34 (1-11/32) | 67 x 67 (2-41/64 x 2-41/64) |
| 194L-HE6G | 34 (1-11/32) | 67 x 67 (2-41/64 x 2-41/64) |
| Cover Requirements | ||||
| For Use With | Y min. | X ³ | Y max. | X ³ |
| 194E-A16 | 5 (13/64) | 142 (5-19/32) | 9.5 (3/8) | 90 (3-35/64) |
| 194E-A25/32 | 5 (13/64) | 142 (5-19/32) | 9.5 (3/8) | 90 (3-35/64) |
| 194E-A40/63 | 2.5 (7/64) | 150 (5-29/32) | 9.5 (3/8) | 90 (3-35/64) |
| 194E-A80/100 | 2.5 (7/64) | 150 (5-29/32) | 9.5 (3/8) | 90 (3-35/64) |
| Switch Body | ||||||||
| Use With Cat. No. |
D3 | E | F1 | F2 | G | H | L | J |
| 194E-A16 | 4.5 (3/16) | 70 (2-49/64) | 45 (1-25/32) | 12.5 (31/64) | 90 (3-35/64) | 63 (2-31/64) | 80 (3-5/32) | 36 (1-27/64) |
| 194E-A25/32 | 4.5 (3/16) | 70 (2-49/64) | 30 (1-3/16) | 15 (19/32) | 90 (3-1/2) | 64 (2-33/64) | 59 (2-5/16) | 45 (1-25/32) |
| 194E-A40/63 | 4.5 (3/16) | 80 (3-5/32) | 37 (1-15/32) | 17 (43/64) | 108 (4-1/4) | 72 (2-27/32) | 73 (2-55/64) | 54 (2-1/8) |
| 194E-A80/100 | 5.6 (7/32) | 95 (3-3/4) | 48.5 (1-29/32) | 23.5 (59/64) | 144 (5-11/16) | 90 (3-35/64) | 89 (3-1/2) | 72 (2-27/32) |
| For 6-pole switches, add 1 in. to the "L" dimension. | ||||||||
Base Mounting Cat. No. 194E-A…
Cat. No. 194E-A… Switch Body with Cat. No. 194L-G2853 Shaft Extension
|
| Switch Body | ||||
| L ⋆ | Cat. No. | |||
| 194E-A 16 | 194E-A 25/32 | 194E-A 40/63 | 194E-A 80/100 | |
| With 1 shaft extension | 79 (3-7/64) |
88 (3-15/32) |
102 (4-1/32) |
118 (4-21/32) |
| With 2 shaft extensions | 103 (4-37/64) |
112 (4-27/64) |
126 (4-31/32) |
142 (5-19/32) |
| With 3 shaft extensions | 127 (5) |
136 (5-23/64) |
150 (5-29/32) |
166 (6-35/64) |
| With 4 shaft extensions | 151 (6-61/64) |
160 (6-5/16) |
174 (6-55/64) |
190 (7-31/64) |
| With 5 shaft extensions | 175 (7-57/64) |
184 (7-1/4) |
198 (7-51/64) |
214 (8-7/16) |
| With 6 shaft extensions | 199 (8-27/32) |
208 (8-13/64) |
222 (8-3/4) |
238 (9-3/8) |
| ⋆ For 6-pole switches, add 1 in. to the "L" dimension. | ||||
| Shaft | Y |
| 194L-G2830 | 2.5…9.5 (7/64…3/8) |
| 194L-G3194 | 9…18 (23/64…23/32) |
| 194L-G3195 | 14…23 (9/16)…(29/32) |
| Handles | |||
| Type | B | Q | P |
| 194L-HE4A | 36 (1-27/64) |
48 x 48 (1-57/64 x 1-57/64) |
28 (1-7/64) |
| 194L-HE4I | 36 (1-27/64) |
48 x 48 (1-57/64 x 1-57/64) |
28 (1-7/64) |
| 194E-HE4G | 28 (1-7/64) |
54 x 54 (2-1/8 x 2-1/8) |
34 (1-11/32) |
| 194E-HE4N | 28 (1-7/64) |
54 x 54 (2-1/8 x 2-1/8) |
34 (1-11/32) |
| 194L-HE6A | 48 (1-57/64) |
64 x 64 (2-33/64 x 2-33/64) |
28 (1-7/64) |
| 194L-HE6I | 48 (1-57/64) |
64 x 64 (2-33/64 x 2-33/64) |
28 (1-7/64) |
| 194L-HE6N | 48 (1-57/64) |
67 x 67 (2-41/64 x 2-41/64) |
34 (1-11/32) |
| 194L-HE6G | 48 (1-57/64) |
67 x 67 (2-41/64 x 2-41/64) |
34 (1-11/32) |
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Installation Cat. No. 194E-A…
Cat. No. 194E-A Switch Body with Metal Shaft Extension
|
| Cat. No. | A |
| 194L-G3393 | 110…235 (4-11/32…9-1/4) |
| 194L-G3394 | 230…350 (9-1/16…13-25/32) |
| Cat. No. | L⋆ |
| 194E-A16 | 51 (2) |
| 194E-A25/32 | 60 (2-3/8) |
| 194E-A40/63 | 74 (2-59/64) |
| 194E-A80/100 | 90 (3-35/64) |
| ⋆ For 6-pole switches, add 1 in. to the "L" dimension. | |
Base and Front Installation
Cat. No. 194E… with Auxiliary Contact Block Installed
| Contacts | M |
| 1 N.O. + 1 N.C. | 9 (23/64) |
| 2 N.O. + 2 N.C. | 18 (23/32) |
|
Cat. No. 194E… with 4-Pole, Ground and Neutral Terminals
| Cat. No. | M |
| 194E-16 | 12.5 (31/64) |
| 194E-25/32 | 14 (9/16) |
| 194E-40/63 | 17.5 (11/16) |
| 194E-80/100 | 22 (7/8) |
|
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Mounting Cat. No. 194E-A…
Thermoplastic Enclosures
|
| Complete Switches | Enclosures | Height A |
Width B |
Knockouts ÆD1 |
Mounting Holes§ | Depth H |
||||
| Cat. No. | Poles | ABS | Noryl | E | F | |||||
| Cat. No. | ||||||||||
| 194E-Y16 | 3 and 4 | ⋆ | ⋆ | 120 (4-23/32) |
70 (2-3/4) |
M16/M20 16/20 mm |
PG11/PG16 18.5/22.5 mm |
50 (1-31/32) |
105 (4-9/64) |
70 (2-49/65) |
| 6 | 194E-G3663 | 194E-G3664 | 180 (7-3/32) |
125 (4-59/64) |
M25/M30 25/30 mm |
PG21/PG29 28.5/37.5 mm |
On Center | 145 (5-23/32) |
105 (4-1/8) |
|
| 194E-Y25/32 | 3 and 4 | 194L-G3572 | 194L-G3576 | 150 (5-29/32) |
95 (3-3/4) |
PG16/PG21 22.5/28.5 mm |
60 (2-3/8) |
115 (4-17/32) |
86 (3-3/8) |
|
| 6 | 194E-G3663 | 194E-G3664 | 180 (7-3/32) |
125 (4-59/64) |
PG21/PG29 28.5/37.5 mm |
On Center | 145 (5-23/32) |
105 (4-1/8) |
||
| 194E-Y40/63 | 3 and 4 | 194E-G3663 | 194E-G3664 | 180 (7-3/32) |
125 (4-59/64) |
PG21/PG29 28.5/37.5 mm |
On Center | 145 (5-23/32) |
105 (4-1/8) |
|
| 6 | 194E-G3665 | 194E-G3666 | 230 (9-1/16) |
175 (6-57/64) |
PG29/PG36 37.5/47.5 mm |
155 (6-3/32) |
195 (7-43/64) |
120 (4-47/64) |
||
| 194E-Y80/100 | 3 and 4 | 194E-G3665 | 194E-G3666 | 230 (9-1/16) |
175 (6-57/64) |
PG29/PG36 37.5/47.5 mm |
155 (6-3/32) |
195 (7-43/64) |
120 (4-47/64) |
|
| ⋆ Empty enclosures not available for purchase. Cat. No. 194E-A16 units have 1 knockout on each end. all others have 2 knockouts on each end. A letter "M" in the catalog number indicates metric knockouts; the unit is otherwise supplied with PG knockouts. § All mounting holes have a 4.2 mm (5/32 in. ) diameter. |
||||||||||
| No. of Extensions | Cat. No. 194E-A 20/32… | Cat. No. 194E-A 40/63… | Cat. No. 194E-A 80/00… |
| With 1 extension | 96 (3-25/32) | 107 (4-7/32) | 114 (4-31/64) |
| With 2 extensions | 120 (4-23/32) | 131 (5-5/32) | 138 (5-7/16) |
| With 3 extensions | 144 (5-43/64) | 155 (6-7/64) | 162 (6-3/8) |
| With 4♣ extensions | 168 (6-39/64) | 179 (7-3/64) | 186 (7-21/64) |
| With 5♣ extensions | 192 (7-9/16) | 203 (8) | 210 (8-17/64) |
| With 6♣ extensions | 216 (8-1/2) | 227 (8-15/16) | 234 (9-7/32) |
| ♣ When more than four modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853). | |||
Dimensions are shown in (millimeters) inches. Dimensions are not intended to be used for manufacturing purposes.
194E Enclosed Switches with 194R Handles
|
|
|
|
|