Family Overview

Bulletin 194 Line Overview

  Click to enlarge - 194E_A40_switch_4c Click to enlarge - 194E_E160_switch_4c Click to enlarge - 194L-HC4I-175_L Click to enlarge - 194L_switch_4c Click to enlarge - 194R_J30_1753
  Bulletin 194E Bulletin 194L Bulletin 194R Next Generation
Product Type Inductive load-rated load switch Inductive load-rated control/load switch Fused and non-fused rotary disconnects
Current Range 16…315 A 12…40 A 30 A, 60 A
Main Applications
  • UL, CSA ratings "suitable as at-motor disconnect"
  • UL, CSA ratings "suitable as at-motor disconnect"
  • UL 98 ratings "suitable as service entrance disconnecting means"

  • UL 508, CSA ratings "suitable as at-motor disconnect"
  • Functionality
  • 3- or 6-pole switch configurations for OFF-ON or changeover applications (16…100 A switches)

  • 3- or 4-pole switch configurations for OFF-ON or changeover applications (125…315 A switches)
  • 1- to 6-pole multifunction switch control configurations for OFF-ON, changeover, Star-Delta (Wye-Delta), reversing, ammeter, voltmeter, and step switch applications

  • Also available in custom control configurations up to 16 circuits for any unique control switching application.
  • 3- or 4-pole fusible or non-fusible disconenct for standard OFF-ON or emergency stop in a main panel disconnect application

  • 4th pole available as modular accessory

  • Test mode switch position
  • Mounting Styles Front/door or base/DIN Rail mounting Front/door or base/DIN Rail mounting Base/DIN Rail mounting
    Handles
  • Handle colors in grey/black and red/yellow and padlockable versions

  • Legend plates available in 0-I international markings and text styles
  • Uniformly styled handles: selector knob, disk style, rectangular style, and key-operated versions (Type 1/12/3R, IP66)

  • Handle colors in grey/black and red/yellow and padlockable versions

  • Legend plates available in 0-I international markings and text styles
  • Available in rotary styles, UL Type 1/3R/4/4X/12, IP66, standard, or test mode versions

  • Handle colors in black and red/yellow and padlockable versions

  • 30 A/60 A legend markers (optional) — uses Cat. No. 1492-MS6X12 markers
  • Open Switch or Enclosed
  • Open switch (large frame Bul. 194E — open style only)

  • Enclosed: IP66 thermoplastic enclosure or UL/CSA rated enclosure
  • Open switch
  • Open switch

  • Enclosed: UL/CSA rated enclosure
  • UL/CSA Electrical Ratings:      
    Rated Voltage Ue 600V AC 600V AC 600V AC
    Rated Current Ie 16…315 A @ 600V 12…40 A @ 600V 30 A, 60 A @ 600V
    Rated Power Pe [FLA] Varies w/ 1- or 3-phase switch, voltage Varies w/ 1- or 3-phase switch, voltage Varies w/ 1- or 3-phase switch, voltage
    Short-Circuit Ratings 5 kA 5 kA 200 kA
    Switching Rate [ops/h] 120 120 180
    Mechanical Life [ops]
  • 0.2 million (16…100 A switches)

  • 0.1 million (125 A and 160 A switches)

  • 0.075 million (250 A and 315 A switches)
  • 1 million
  • 10 000
  • IEC Rated Current Ie      
    AC-1 16…315 A @ 600V 12…40 A @ 600V 20…63 A @ 690V
    AC-21A 16…315 A @ 600V 12…40 A @ 600V Varies w/ 1- or 3-phase switch, voltage
    AC-22A 16…315 A @ 600V 12…40 A @ 600V Varies w/ 1- or 3-phase switch, voltage
    Ambient Operational Temp. -25…+60 °C (-13…+140 °F) -25…+60 °C (-13…+140 °F) -20…+60 °C (-4…+140 °F)
    Ambient Enclosed Temp. -20…+60 °C (-4…+140 °F) -20…+60 °C (-4…+140 °F) -20…+60 °C (-4…+140 °F)
    Ambient Storage Temp. -40…+80 °C (-40…+176 °F) -40…+80 °C (-40…+176 °F) -40…+65 °C (-40…+149 °F)
    Protection class per IEC 529
  • Switch bodies: IP2
  • Switch bodies: IP2
  • Switch bodies: IP2

  • Fuse carriers: IP30
  • Optional Accessories
  • IP66 handles

  • Multi-length shafts and shaft extension kits

  • Terminal covers
  • IP66 handles

  • Multi-length shafts and shaft extension kits

  • Terminal covers
  • IP66 handles

  • Multi-length shafts

  • Auxiliary contacts

  • Terminal covers

  • NFPA 79 internal handle
  • Standards/Certifications
  • UL 508

  • CSA C22.2, No. 14

  • IEC 60947-3 Low Voltage Switchgear and Controlgear part 3

  • CE
  • UL 508

  • CSA C22.2, No. 14

  • IEC 60947-3 Low Voltage Switchgear and Controlgear part 3

  • CE
  • UL 98, UL 508

  • CSA C22.2, No. 14

  • IEC 60947-3 Low Voltage Switchgear and Controlgear part 3

  • CE
  •