Ground Fault Detection System

Product Overview


Click to enlarge - Supp-5_1-2
Arcing Ground Fault Relay
Cat. No. 1409-DOBD
Click to enlarge - 1409-5_15-2
Arcing Ground Fault Sensor
Cat. No. 1409-N2

Bulletin 1409 — Arcing Ground Fault Detection System


The Bulletin 1409 Arcing Ground Fault Detection Systems are intended for equipment protection only. These systems are not Ground-Fault Circuit-Interrupters for personnel protection as defined in Article 100 of the U.S. National Electric Code.
Bulletin 1409 is available in two designs, Class I and Class II. The Class I systems are intended for use with shunt-trip circuit breakers or medium voltage controllers. These Class I systems do not contain a high-current inhibit circuit.
The Class II Systems are designed for use with motor starters or contactors to interrupt low-level ground faults. They incorporate a high-current inhibit circuit that guards against the controller opening when the fault current exceeds the controller interrupting capacity. Ground fault currents exceeding the interrupting rating of the controllers are designed to be cleared by the short circuit protection device (fuse or circuit breaker).
Both Class I and Class II Systems consist of two parts — a relay and a sensor. The relay contains all the detection, adjustment and output circuitry. The sensor is a special two-winding current transformer. Operation of the ground fault detection system is indicated by the relay toggle.


Standards Compliance and Certifications

Standards Compliance

CSA C22.2, No. 144
UL 1053


Certifications

CSA Certified (LR49901)
UL Listed (File E53935, Guide KDAX)


Product Selection

Build a Catalog Number


Your order must include the cat. no. of the arcing ground fault relays and sensor selected.

Low-level (arcing) ground faults are below the fuse or circuit breaker rating and therefore go undetected until a much larger problem develops. The Allen-Bradley Arcing Ground Fault Detection System is designed to sense these low-level faults and either drop out the motor controller or operate a shunt-trip circuit breaker to clear the fault.

Arcing Ground Fault Relays — Class II with High Current Inhibit Feature

NEMA Starter Size Maximum
Voltage [V AC]
Maximum Horsepower [Hp] Full Load Current [A] High Current Inhibit [A] Cat. No.
Min. Max.
1 200…230 7.5 27 114 144 1409-BOAD
460 10 14 63 79 1409-BOBD
575 10 11 50 62 1409-BOCD
2 200…230 15 45 189 239 1409-COAD
460 25 34 153 193 1409-COBD
575 25 27 122 153 1409-COCD
3 200…230 30 90 360 456 1409-DOAD
460 50 65 293 370 1409-DOBD
575 50 52 234 296 1409-DOCD
4 200…230 50 135 585 741 1409-EOAD
460 100 124 558 706 1409-EOBD
575 100 99 446 564 1409-EOCD
5 200…230 100 270 1116 1413 1409-FOAD
460 200 240 1080 1368 1409-FOBD
575 200 192 864 1094 1409-FOCD
6 200…230 200 540 2160 2736 1409-GOAD
460 400 465 2147 2718 1409-GOBD
575 400 372 1719 2177 1409-GOCD
  

Arcing Ground Fault Sensors

NEMA Starter Size Max. Recommended Cable Size¬  Window Diameter Cat. No.
1…2 2 AWG @ 600V AC 1-9/16 in. 1409-N1
3…4 250 MCM @ 600V AC
4/0 @ 5000V AC
4/0 @ 8000V ACT 
2-1/2 in. 1409-N2
5 500 MCM @ 600V AC
350 MCM @ 5000V AC
350 MCM @ 8000V ACT 
3-1/4 in. 1409-N3
6 2-500 MCM @ 600V AC
500 MCM @ 5000V AC
500 MCM @ 8000V ACT 
4-1/4 in. 1409-N4
  
¬ For a 3-phase system with one cable per phase except as indicated.
T 8000V cable — select sensor to have a window diameter greater than 2.5 times the cable diameter.

Arcing Ground Fault Relays — Class I without High Current Inhibit Feature

Application Max. Line Voltage [V] Cat. No.
Shunt-Trip Circuit Breaker 600 1409-MV
Medium Voltage Controller 7200
  
Note:Interrupting capacity is determined by starter or circuit breaker selection.

Specifications

Response Time 50 ms nominal plus the controller drop-out time
Supply Voltage 120V AC, 60 Hz
Power Input 3 VA
Temperature Range The operating ambient temperature range for the sensor is –40…+85 °C (–40…+184 °F) and for the relay is 0…+65 °C (32…149 °F)
Output Contact Rating Make 30 A; Break 3 A; Continuous carrying current 5 A at 120V
  

Typical Wiring Diagrams

See Applicable Codes and Laws.

Class II with High Current Inhibit Circuit¬ 

Click to enlarge - 1409-5_16-1


Class I without High Current Inhibit Circuit¬ 

Click to enlarge - 1409-5_16-2


¬ Wiring diagrams are shown in the tripped condition.


Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Arcing Ground Fault Relay

Click to enlarge - 1409-5_17-1


Arcing Ground Fault Sensors

Click to enlarge - 1409-5_17-2
Cat. No. 1409-N1: 12.7 (1/2) x 7.1 dia. (9/32)Cat. No. 1409-N2: 12.7 (1/2) x 11.1 dia. (7/16)


Click to enlarge - 1409-5_17-3
Cat. No. 1409-N3Cat. No. 1409-N4


Cat. No. A B C D E F G H J K
1409-N1 92.6
(3-21/32)
88.9
(3-1/2)
104
(4-3/32)
74
(2-15/16)
67.3
(2-21/32)
56.4
(2-7/32)
92.9
(3-21/32)
39.6
(1-9/16)
1409-N2 91.4
(3-19/32)
115.8
(4-9/16)
131.8
(5-3/16)
77
(3-1/32)
88.9
(3-1/2)
88.9
(3-1/2)
120.6
(4-3/4)
63.5
(2-1/2)
69.8
(2-3/4)
54.9
(2-5/32)
1409-N3 73.2
(2-7/8)
144
(5-11/16)
157.2
(6-3/16)
54.9
(2-5/32)
96.8
(3-13/16)
119.4
(4-23/32)
146.1
(5-3/4)
82.6
(3-1/4)
1409-N4 77.2
(3-1/32)
169.9
(6-11/16)
182.6
(7-3/16)
59.5
(2-11/32)
123.7
(4-7/8)
138.2
(5-7/16)
171.5
(6-3/4)
108
(4-1/4)