Motor Winding Heaters
| Product Overview |
|
Bulletin 1410 — Motor Winding Heater
Bulletin 1410 Motor Winding Heater is intended for use with 3-phase AC motors to guard against damage caused by condensation build-up on motor windings, which can occur in high-humidity environments during motor off times. This device is not intended to be used to dry out damp motors.
Bulletin 1410 Motor Winding Heater is designed for used with 3-phase AC squirrel-cage motors controlled by automatic full-voltage starters. For applications involving reduced-voltage starters, multi-speed starters, synchronous motors, or the used of power factor correction capacitors, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
- Solid-state design
- Automatic operation
- No adjustments required
Standards Compliance and Certifications
Standards Compliance
CSA C22.2, No. 14
UL 508
Certifications
CSA Certified (LR 1234)
UL Listed (File E56639, Guide NMTR)
Product Selection
Product Selection¬
| Build a Catalog Number |
| 3-Phase Motor Voltage, +10%, -5%, 60 Hz | 3-Phase Hp Rating |
Cat. No. |
| 230 | 15…50 | 1410-EOA47 |
| 460 | 25…100 | 1410-EOB50 |
| 575 | 25…100 | 1410-EOC50 |
| 230 | 50…100 | 1410-FOA50 |
| 460 | 100…200 | 1410-FOB54 |
| 575 | 100…200 | 1410-FOC54 |
| 230 | 100…200 | 1410-GOA54 |
| 460 | 200…400 | 1410-GOB59 |
| 575 | 200…400 | 1410-GOC59 |
| 230 | 200…300 | 1410-HOA57 |
| 460 | 400…600 | 1410-HOB62 |
| 575 | 400…600 | 1410-HOC62 |
| ¬ For applications requiring different horsepower, kilowatt, and voltage ranges from those listed, consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||
Connection Diagram
See Applicable Codes and Laws.
|
Specifications
Specifications
| Output Voltage Regulation | Voltage applied to motor winding will vary ±5% maximum for line voltage variations of +10%, 15%. |
|
| Ambient Temperature Range |
Operating | 0…50 °C (32…122 °F) |
| Storage | 25…+85 °C (13…+184 °F) | |
| Additional SCR Protection | Metal oxide varistor protects against voltage surges. RC snubber circuit limits rate of change of circuit voltage. | |
| True RMS Output Current | Approximately 15% of full load current. | |
| Power Delivered to the Motor | Approximately 1…3 W/Hp. | |
Approximate Dimensions
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes
|
| Cat. No. | A | B | C |
| 1410-EOA47 1410-EOB50 1410-EOC50 |
146.1 (5-3/4) |
88.9 (3-1/2) |
114.3 (4-1/2) |
| 1410-FOA50 1410-FOB54 1410-FOC54 |
204.8 (8-1/16) |
108 (4-1/4) |
177.8 (7) |
| 1410-GOA54 1410-GOB59 1410-GOC59 |
238.1 (9-3/8) |
146.1 (5-3/4) |
206.4 (8-1/8) |
| 1410-HOA57 1410-HOB62 1410-HOC62 |
279.4 (11) |
244.5 (9-5/8) |
207.2 (8-5/32) |