Dedicated Function Motor Protection Relays
|
MachineAlert Relays
The MachineAlert Relays family of dedicated function electronic motor protection relays offers state-of-the-art supplementary protective functions that are easily added and applied to motor control circuits. MachineAlert Relays are an economical choice for protecting equipment investments and minimizing production downtime. To meet specific application requirements, a full range of products allows selective addition of protective enhancing functions for both motors and equipment.
- Current monitors
- Phase monitors
- Thermistor monitors
- Rotation monitors
Product Overview
Description
Electronic Design
- Microprocessor technology provides highly accurate and repeatable protection
- Built-in LCD and keypad afford a precise, digital setting
- Wide adjustment ranges allow for application flexibility
- Password protection hinders unauthorized programming access
- Compact 22.5 mm and 45 mm packaging
- Global application with CE and cULus approvals
Enhanced Protection
- Current monitors that provide the added benefits of under- and overcurrent detection
- Phase monitors that guard against the damaging effects of phase loss, under- and overvoltage, phase imbalance, and phase reversal
- Thermistor monitors that protect equipment from overtemperature conditions
- Motor rotation monitors that signal motor rotational status
Easy to Use
- Compact size saves valuable panel space
- LCD/keypad programming takes the guesswork out of device setup
- DIN Rail mounting makes installation a snap
- Terminals provide IP20 finger safety protection and are clearly marked
- LCD display provides relay status indication
| Features | Typical Applications | ||
Current Monitors |
|||
Phase Monitors |
|||
Thermistor Monitors |
|||
Motor Rotation Monitors |
|||
Product Family Overview
| Features⋆ | Bulletin 809S Current Monitors |
Bulletin 813S Phase Monitors |
Bulletin 817 Thermistor Monitors |
Bulletin 819 Motor Rotation Monitors |
|||
| E1 | E2 | E2 | E1 | E2 | E1 | E2 | |
| Under- and overcurrent protection | S | S | — | — | — | — | — |
| Under- and overvoltage protection | S | — | S | — | — | — | — |
| Phase imbalance and phase loss protection | — | — | voltage based |
— | — | — | — |
| Phase sequence protection | — | — | S | — | — | — | — |
| Overtemperature protection | — | — | — | S | S | — | — |
| Speed detection via frequency input | — | — | — | — | — | S | |
| Speed detection evaluation of motor feedback voltage | — | — | — | — | — | S | S |
| Operating Range | 0.5…5 A 1.0…24.9V 10…249V |
2.0…15.0 A | 500V AC or 690V AC |
— | — | IEC 400V AC CSA/UL 300V AC |
IEC 690V AC CSA/UL 600V AC |
| Case size (mm) | 22.5 | 45 | 45 | 22.5 | 22.5 | 22.5 | 45 |
| LCD / keypad | S | S | S | — | — | S | S |
| LED Status Indicator | — | — | — | S | S | — | — |
| Automatic reset | S | S | S | S | O | S | S |
| Manual reset | — | — | — | — | O | — | — |
| Remote reset | — | — | — | — | O | — | — |
| Changeover contacts (SPDT) | 1 | 1 | 1 | — | — | — | 1 |
| N.O. contacts | — | 1 | 1 | 2 | 2 (independent) |
2 (independent) |
1 |
| No setting required | — | — | — | S | S | — | — |
| Programmable trip level, reset level and time delay settings | S | S | S | — | — | S | S |
| Trip cause identification | — | — | S | S | S | — | — |
| Measuring Circuit Monitoring (open, short) | — | — | — | S | S | S | S |
| ⋆ S= Standard O= Option |
|||||||
Standards Compliance and Certifications
Standards Compliance—Bulletins 809S/813S/819
EN 60255-5, EN50263
CSA C22.2, No.14
UL 508
CE
cULus Listed
Standards Compliance—Bulletin 817
IEC 255-8, IEC 292-1
IEC 255-4, IEC 69
SEV, SEN 36 1503
CSA C22.2, No. 14
UL 508
Certifications—Bulletins 809S/813S/819
cULus Listed (File E14840, Guide NKCR, NKCR7)
Certifications—Bulletin 817
cURus Recognized (File 33916, Guide NKCR2, NKCR8)
SEV
NEMKO
FI
Product Selection
| Motor Protection Relay Type | Description | Cat. No. |
| Bulletin 809S Current Monitors | 0.5…5 A AC/DC (1-phase), 2.0…24.9V or 20…249V AC/DC 50/60 Hz | 809S-E1Ä |
| 2.0…15 A AC/DC (1-phase) | 809S-E2ĵ | |
| Bulletin 813S Phase Monitors | Monitoring Range 150…500V AC | 813S-E2Bĵ |
| Monitoring Range 250…690V AC | 813S-E2Cĵ | |
| Bulletin 817 Thermistor Monitors | Automatic Reset | 817-E1⋆ |
| Automatic, manual or remote reset, status storage | 817-E2⋆ | |
| Bulletin 819 Motor Speed Monitors | Max. Monitored Voltage 400V AC max. (IEC), 300V AC max. (CSA/UL), or Frequency Monitoring for signals of any curve form in the range 16…100Vp-p | 819-E1Ä |
| Max. Monitored Voltage 690V AC max. (IEC), 600V AC max. (CSA/UL) | 819-E2Ä | |
| Package Quantity = 1 | ||
| ⋆ Rated supply voltage of 24…240V AC/DC. | ||
Ä Supply Voltage Suffix Code
The Cat. No. as listed is incomplete. Select a Supply Voltage Suffix Code from the table below to complete the Cat. No.
Example: Cat. No. 809S-E1Ä becomes 809S-E1D.
| Voltage Rating | 24V DC | 115V AC | 230V AC |
| ZJ | D | A | |
µ Frequency Code
The Cat. No. as listed is incomplete. Select a Frequency Code from the table below to complete the Cat. No.
Example: Cat. No. 813S-E2BDµ becomes 813S-E2BD60.
| Frequency Rating | 50 Hz | 60 Hz |
| 50 | 60 | |
Current Transformers
Use only with Cat No. 809S-E1.
| Trip Current Range Continuous AC Amperes (5 A Secondary Winding) |
Maximum Current [A] | Cat. No. | |
| Continuous | Inrush | ||
| 4.2…50 | 75 | 350 | 809S-CT1 |
| 17…200 | 300 | 1400 | 809S-CT2 |
| 42…500 | 750 | 3500 | 809S-CT3 |
| 100…1200 | 1800 | 8400 | 809S-CT4 |
Specifications
| Programmable Settings | |
| Setting | Recommended Adjustment Range |
| 809S-E1 | |
| Actuation Value, Current | 0.5…5.0 A |
| Release Value, Current | 0.5…5.0 A |
| Actuation Value, Voltage | 1.0…24.9V/10…249V |
| Release Value, Voltage | 1.0…24.9V/10…249V |
| Delay | 0.0…24.9 s |
| 809S-E2 | |
| Actuation Value, Imbalance | 5…35% |
| Release Value, Imbalance | 5…35% |
| Delay, Relay Energize | 0.0…24.9 s |
| Delay, Relay De-energize | 0.0…24.9 s |
| 813S-E2 | |
| Overvoltage Level (E2B/E2C) | 150…500V AC/250…700V AC |
| Undervoltage Level (E2B/E2C) | 150…500V AC/250…700V AC |
| % Imbalance Level | 5…19% |
| Delay, Relay Energize | 0.0…24.9 s |
| Delay, Relay De-energize | 0.0…24.9 s |
| 819-E1 | |
| Actuation Value, Voltage | 1.0…24.9V AC |
| Release Value, Voltage | 1.0…24.9V AC |
| Actuation Value, Frequency | 10…249 Hz |
| Release Value, Frequency | 10…249 Hz |
| Delay | 0.0…24.9 s |
| 819-E2 | |
| Actuation Value, Voltage | 1.0…24.9V AC |
| Release Value, Voltage | 1.0…24.9V AC |
| Delay, Relay Energize | 0.0…24.9 s |
| Delay, Relay De-energize | 0.0…24.9 s |
| Bulletin 817 PTC Sensor Characteristics | ||||
| Type of control unit | Mark A | |||
| Sensor Characteristic | per IEC 34-11-2 | |||
| Maximum number of sensors | 6 | |||
| Maximum cold resistance of PTC sensor chain | 1500 W | |||
| Trip resistance | 3600 W (±300 W) | |||
| Reset resistance | 1580 W (±60 W) | |||
| Short circuit trip resistance | <20 W (5 W, +0 W) | |||
| Short circuit reset resistance | 24 W (0 W, +6 W) | |||
| Open circuit resistance | >18000 W | |||
| Bulletin 817 Power/Trip Idendification | ||||
| Power on | Green | |||
| Trip Overtemperature | Red | |||
| Trip open circuit (Sensor) | Red 2 Hz | |||
| Trip short circuit (sensor) | Red flashes | |||
| Bulletin 817 Measuring and Reset Lines | ||||
| Measuring Line | Up to 200 parallel or twisted; >200 m shielded, shield connected with T1 |
|||
| Minimum Cross Section (mm2) | 0.5 | |||
| Maximum Line length (m) | 200 | |||
| Remote reset | Max 600 m; Up to 200 parallel or twisted; >200 m shielded, shield connected with r1 |
|||
| Bulletin 817 Relay Configuration | ||
| 817-E1 | 817-E2 | |
|
|
|
| Normal |
|
|
| Tripped |
|
|
| Power Off |
|
|
Dedicated Function Relays, 809S-E1 to 813S-E2
| Dedicated Function Relays | ||||
| 809S-E1 | 809S-E2 | 813S-E2 | ||
| ELECTRICAL | ||||
| Main | ||||
| Rated Insulation Voltage (Ui) | 250V AC | 690V AC | 690V AC | |
| Rated Operating Voltage (Ue) | IEC: 250V AC CSA/UL: 250V AC |
IEC: 690V AC CSA/UL: 600V AC |
IEC: 690V AC CSA/UL: 600V AC |
|
| Measurement Range | 0.5...5 A AC/DC 1…24.9V 10...249V AC/DC |
1...15 A AC/DC | E2B: 500V E2C: 690V |
|
| Accuracy | ±5% | ±5% | ±5% | |
| Number of Phases | 1 | 1 | 3 | |
| Supply | ||||
| Rated Supply Voltage (Us) | 24V DC 115V AC, 230V AC |
24V DC 115V AC, 230V AC |
24V DC 115V AC, 230V AC |
|
| Operating Range | AC: 0.8…1.1 Us DC: 0.85…1.1 Us |
AC: 0.8…1.1 Us DC: 0.85…1.1 Us |
AC: 0.8…1.1 Us DC: 0.85…1.1 Us |
|
| Maximum Power Consumption | 1 VA | 2 VA | 2 VA | |
| Output Relay | ||||
| Type of Contacts | (1) Form C | (1) Form A (1) Form C |
(1) Form A (1) Form C |
|
| Rated Operating Current | 5 A @ 250V AC 4 A @ 24V DC |
5 A @ 250V AC 4 A @ 24V DC |
5 A @ 250V AC 4 A @ 24V DC |
|
| Utilization Category | AC1, DC1 | AC1, DC1 | AC1, DC1 | |
| MECHANICAL | ||||
| Environmental | ||||
| Ambient Temperature | (storage) | 20…+80 °C | 20…+80 °C | 20…+80 °C |
| (operating) | 5…+60 °C | 5…+60 °C | 5…+60 °C | |
| Humidity | 5…95% non-condensing |
5…95% non-condensing |
5…95% non-condensing |
|
| Maximum Altitude | 2000 m | 2000 m | 2000 m | |
| Pollution Environment | Pollution Degree 2 | Pollution Degree 2 | Pollution Degree 2 | |
| Degree of Protection | IP20 | IP20 | IP20 | |
| Terminal Cross-Sections | ||||
| Terminal Screws | M3 | M3 | M3 | |
| Conductor Size | 0.2…2.5 mm2 26…14 AWG |
0.2…2.5 mm2 22…12 AWG |
0.2…2.5 mm2 22…12 AWG |
|
Dedicated Function Relays, 817-E1 to 819-E2
| Dedicated Function Relays | |||||
| 817-E1 | 817-E2 | 819-E1 | 819-E2 | ||
| ELECTRICAL | |||||
| Main | |||||
| Rated Insulation Voltage (Ui) | 250V AC | 250V AC | 400V AC | 690V AC | |
| Rated Operating Voltage (Ue) | IEC: 250V AC CSA/UL: 250V AC |
IEC: 250V AC CSA/UL: 250V AC |
IEC: 400V AC CSA/UL: 300V AC |
IEC: 690V AC CSA/UL: 600V AC |
|
| Measurement Range | — | — | Freq: 10…249 Hz (16…100Vp-p) Back-EMF: 1.0…24.9V |
Back-EMF: 1.0…24.9V | |
| Accuracy | — | — | ±5% | ±5% | |
| Number of Phases | — | — | 1 | 1 | |
| Supply | |||||
| Rated Supply Voltage (Us) | 24…240V AC/DC | 24…240V AC/DC | 24V DC, 115V AC, 230V AC | 24V DC, 115V AC, 230V AC | |
| Operating Range | 0.8…1.1 Us | 0.8…1.1 Us | AC: 0.8…1.1 Us DC: 0.85…1.1 Us |
AC: 0.8…1.1 Us DC: 0.85…1.1 Us |
|
| Maximum Power Consumption | 1.5 VA | 1.5 VA | 1 VA | 2 VA | |
| Output Relay | |||||
| Type of Contacts | (2) Form A dependent |
(2) Form A independent |
(2) Form A independent |
(1) Form A (1) Form C |
|
| Rated Operating Current | 3 A @ 120V AC 1.5 A @ 240V AC |
3 A @ 120V AC 1.5 A @ 240V AC |
5 A @ 250V AC 4 A @ 24V DC |
5 A @ 250V AC 4 A @ 24V DC |
|
| Utilization Category | AC15, DC13 | AC15, DC13 | AC1, DC1 | AC1, DC1 | |
| MECHANICAL | |||||
| Environmental | |||||
| Ambient Temperature | (storage) | 40…+80 °C | 40…+80 °C | 20…+80 °C | 20…+80 °C |
| (operating) | 25…+60 °C | 25…+60 °C | 5…+60 °C | 5…+60 °C | |
| Humidity | 5…95% non-condensing |
5…95% non-condensing |
5…95% non-condensing |
5…95% non-condensing |
|
| Maximum Altitude | 2000 m | 2000 m | 2000 m | 2000 m | |
| Pollution Environment | Pollution Degree 2 | Pollution Degree 2 | Pollution Degree 2 | Pollution Degree 2 | |
| Degree of Protection | IP20 | IP20 | IP20 | IP20 | |
| Terminal Cross-Sections | |||||
| Terminal Screws | M3 | M3 | |||
| Conductor Size | 0.5…2.5 mm2 20…12 AWG |
0.5…2.5 mm2 20…12 AWG |
0.2…2.5 mm2 26…14 AWG |
0.2…2.5 mm2 22…12 AWG |
|
Function and Wiring Diagrams
809S-E1 Wiring Diagram
|
809S-E1 Function Diagram
|
|
819-E1 Wiring Diagram
|
819-E1 Function Diagram
|
|
|
809S-E2 Wiring Diagram
|
809S-E2 Function Diagram
|
|
819-E2 Wiring Diagram
|
819-E2 Function Diagram
|
|
|
813S-E2 Wiring Diagram
|
813S-E2 Function Diagram
|
Approximate Dimensions
Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.
809S-E1, 819-E1
|
809S-E2, 813S-E2, 819-E2
|
Dimensions shown are in millimeters (inches) Dimensions are not intended for manufacturing purposes.
817-E1, 817-E2
|
809S-CT1, 809S-CT2, 809S-CT3, 809S-CT4
Use only with Cat. Nos. 809S-E1 and 809S-E2
|
| Cat. No. | A Min. |
B | C | D | E | F |
| 809S-CT1 | 32 (1-1/4) |
102 (4) |
117 (4-5/8) |
95.5 (3-3/4) |
32 (1-1/4) |
6.4 (1/4) |
| 809S-CT2 | ||||||
| 809S-CT3 | 57 (2-1/4) |
149 (5-7/8) |
181 (7-1/8) |
127 (5) |
38 (1-1/2) |
7.1 (9/32) |
| 809S-CT4 | 95.5 (3-3/4) |
171 (6-3/4) |
198 (7-25/32) |
165 (6-1/2) |
41.5 (1-5/8) |
7.1 (9/32) |