Current, Phase, Thermistor, and Motor Rotation Monitoring Relays

Catalogs > Industrial Controls Catalog > Supplemental Motor Protection > Current, Phase, Thermistor, and Motor Rotation Monitoring Relays > Line Voltage and Current Monitor Relays

Line Voltage and Current Monitor Relays

Introduction Standards Compliance and Certifications Product Selection Specifications Approximate Dimensions
Specifications

Line Voltage Monitor

Line Voltage 380V, 415V, 440V, +10%, –20%, 3-phase, 50 Hz, ± 1%;
120V, 208V, 240V, 480V, 600V, +10%, –20%, 3-phase, 60 Hz, ±1%
Use device only at nameplate rating.
Temperature Range –20…+60 °C (–4…+140 °F)
  

Output Contact Range

Volts AC Make Break Volts DC Make/Break
170…600
48…170
1…48
4800 VA
28.2 A
28.2 A
480 VA
480 VA
10 A
1…28
10 A
Continuous Carrying Current: 10 A
  

Line Current Monitor

Supply Voltage 120V, 208V, 240V, 480V, 600V, +10%, –20%, single-phase, 60 Hz
Use only at voltages listed on relay nameplate. Power requirement is 4.4 VA.
Input Current
        Normal operating range
        Maximum continuous current
        Maximum inrush current
        Input impedance
3-phase, 60 Hz, ±1%
0…5 A
10 A
35 A for 5 s
0.005 W for each phase
Temperature Range –20…+60 °C (–4…+140 °F)
  

Output Contact Ratings

Volts AC Make Break Volts DC Make/Break
125…250, 1…125 2200 VA, 17.6 A 220 VA, 1.76 A 1…30 3 A
Continuous Carrying Current: 5 A AC or DC
  

Typical Wiring Diagrams

See Applicable Codes and Laws

Click to enlarge - 813S-2_2-1


Line Voltage Monitor — Provides pre-start and running protection against abnormal voltage conditions on line side of voltage monitor only.

Click to enlarge - 813S-2_2-2


Line Current Monitor — Protects on line and load side of current transformers (CT) when used in single motor branch circuit. Current unbalance protection is effective during motor running period only. Phase failure and reversal protection is provided during both starting and running periods.