Catalogs > Industrial Controls Catalog > Supplemental Motor Protection > Current, Phase, Thermistor, and Motor Rotation Monitoring Relays > Line Voltage and Current Monitor Relays
Line Voltage and Current Monitor Relays
| Introduction | Standards Compliance and Certifications | Product Selection | Specifications | Approximate Dimensions |
Line Voltage Monitor
| Line Voltage | 380V, 415V, 440V, +10%, 20%, 3-phase, 50 Hz, ± 1%; 120V, 208V, 240V, 480V, 600V, +10%, 20%, 3-phase, 60 Hz, ±1% Use device only at nameplate rating. |
| Temperature Range | 20…+60 °C (4…+140 °F) |
Output Contact Range
| Volts AC | Make | Break | Volts DC | Make/Break |
| 170…600 48…170 1…48 |
4800 VA 28.2 A 28.2 A |
480 VA 480 VA 10 A |
1…28 |
10 A |
| Continuous Carrying Current: 10 A | ||||
Line Current Monitor
| Supply Voltage | 120V, 208V, 240V, 480V, 600V, +10%, 20%, single-phase, 60 Hz Use only at voltages listed on relay nameplate. Power requirement is 4.4 VA. |
| Input Current Normal operating range Maximum continuous current Maximum inrush current Input impedance |
3-phase, 60 Hz, ±1% 0…5 A 10 A 35 A for 5 s 0.005 W for each phase |
| Temperature Range | 20…+60 °C (4…+140 °F) |
Output Contact Ratings
| Volts AC | Make | Break | Volts DC | Make/Break |
| 125…250, 1…125 | 2200 VA, 17.6 A | 220 VA, 1.76 A | 1…30 | 3 A |
| Continuous Carrying Current: 5 A AC or DC | ||||
Typical Wiring Diagrams
See Applicable Codes and Laws
|
Line Voltage Monitor — Provides pre-start and running protection against abnormal voltage conditions on line side of voltage monitor only.
|
Line Current Monitor — Protects on line and load side of current transformers (CT) when used in single motor branch circuit. Current unbalance protection is effective during motor running period only. Phase failure and reversal protection is provided during both starting and running periods.