Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Distributed Starters (Safety Version) > Bulletin 284D
Bulletin 284D
| Introduction | Standards Compliance and Certifications | Cat. No. Explanation | Product Selection | Options Factory Installed |
| Accessories | Safety I/O Module and TÜV Requirements | Specifications | Approximate Dimensions |
Receptacle Connections for DeviceNet Connector
|
Pin 1: Drain (no connection) Pin 2: +VDNET Pin 3: -VDNET Pin 4: CAN_H Pin 5: CAN_L |
Receptacle Connections for Input (M12)
|
Pin 1: +24V (A3 or DNET) Pin 2: Input 0 Pin 3: Common Pin 4: Input 1 Pin 5: NC (no connection) |
Receptacle Connections for Output, DeviceNet or ArmorPoint Version (M12)
|
Pin 1: PE Pin 2: Return Pin 3: Relay out |
Receptacle Connections for Dynamic Brake (M22)
|
Pin 1: GND (green/yellow) Pin 2: BR+ (black) Pin 3: BR- (white) |
ArmorStart Receptacle Pin Outs, Continued
Receptacle Connections for Source or Control Brake
|
Pin 1: L1 (black) Pin 2: GND (green/yellow) Pin 3: L2 (white) |
Receptacle Connections for Motor Connector (M22)
|
Pin 1: T1 (black) Pin 2: T2 (white) Pin 3: T3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
10 A Short Circuit Protection (M22)
|
Pin 1: L1 (black) Pin 2: L2 (white) Pin 3: L3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
25 A Short Circuit Protection (M35)
|
Pin 1: L1 (black) Pin 2: Ground (green/yellow) Pin 3: L3 (red) Pin 4: L2 (white) |
Receptacle Connections for Safety Monitor Outputs to Bulletin 1732DS-* (SM1/SM2) (M12)
|
Pin 1: ArmorStart SM1 (brown) Pin 2: ArmorStart SM2 (white) Pin 3: Not used Pin 4: Not used |
Receptacle Connections for Safety (Bulletin 1732DS) Power (A1/A2) (M12)
|
Pin 1: ArmorStart A1 (brown) Pin 2: ArmorStart P (white) Pin 3: ArmorStart A2 (blue) Pin 4: ArmorStart M (black) |
Bulletin 284D Safety ArmorStart with DeviceNet Communications
|
Motor Overload Trip Curves
Motor overload current parameter provides class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
|
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…500V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | ||||||
| Short Circuit Protection | SCPD Performance Type 1 | Current Rating | Voltage | 480Y/277V | 480/480V | 600Y/347V | 600V |
| 10 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 25 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications | ||||||
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 1000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| Approximate Shipping Weight | 13.6 kg (30 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Wire Size | Primary/Secondary terminal: (16 …10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | (18…10 AWG) | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Disconnect Lock Out | Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed 5/16 in. (8 mm) when closed, or damage will occur to disconnect guard. | ||
| EMC Emission Levels | Conducted Radio Frequency Emissions | 10V rms Communication cables 10V rms (PE) 150 KHz…80 MHz |
|
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | Electrostatic Discharge | 4 kV contact and 8 kV Air | |
| Radio Frequency Electromagnetic Field | 10V/m, 80 KHz…1 GHz 3V/m, 1.4 GHz…2.0 GHz 1V/m, 2.0 GHz…2.7 GHz |
||
| Fast Transient | 2 kV (Power) 2 kV (PE) 1 kV (Communications and control) |
||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Standards Compliance | UL 508C; CSA C22.2, No. 14; EN50178; EN61800-3; EN/IEC 60947-4-2; CE Marked per Low Voltage 2006/95/EC; EMC Directive 2004/108/EC; CCC; ODVA for DeviceNet | ||
| Certifications | cULus (File No. E207834, Guide NMMS, NMMS7) | ||
| UL/NEMA | IEC | ||
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings Sourced from control circuit - A1/A2 |
Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | ||
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| DeviceNet Specifications | DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | |
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| DeviceNet Input Current | 364 mA @ 11V DC - 4.0 W | ||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | Baud Rates | 125, 250, 500 kbps | |
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| Distance Maximum | 200 m (656 ft) @ 250 kbps | ||
| Distance Maximum | 100 m (328 ft) @ 500 kbps | ||
| Drive Characteristics | Sensorless Vector Control |
| Maximum Hp (kW)/Input Voltage | 5 Hp (3.3 kW)/480V AC |
| Overload Capacity | 150% for 60 seconds, 200% for 3 seconds |
| Output Frequency (programmable) | 0…400 Hz |
| Efficiency (typical) | 97.5% |
| Preset Speeds | 8 |
| Carrier Frequency | 2…16 kHz |
| Skip Frequency | ü |
| Process Control Loop | ü (PID) |
| StepLogic Functionality | ü |
| Timer/Counter Functions | ü |
| Drive Ratings — VFD Output Current vs. Input Current | |||||
| Line Voltage | Frequency [Hz] | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | Input Current [A] |
| Sensorless Vector Control | Sensorless Vector Control | ||||
| 380 | 50 | 0.4 | — | 1.4 | 2.15 |
| 0.75 | — | 2.3 | 3.80 | ||
| 1.5 | — | 4.0 | 6.40 | ||
| 2.2 | — | 6.0 | 9.00 | ||
| 3.0 | — | 7.6 | 12.40 | ||
| 460 | 60 | — | 0.5 | 1.4 | 1.85 |
| — | 1 | 2.3 | 3.45 | ||
| — | 2 | 4.0 | 5.57 | ||
| — | 3 | 6.0 | 8.20 | ||
| — | 5 | 7.6 | 12.5 | ||
| Protective Specifications — Sensorless Vector Control | |
| Motor Protection | I2t overload protection — 150% for 60 seconds, 200% for 3 seconds (provides Class 10 protection) |
| Overcurrent | 200% hardware limit, 300% instantaneous fault |
| Overvoltage | 380…460V AC Input — Trip occurs @ 810V DC bus voltage (equivalent to 575V AC incoming line) |
| Undervoltage | 380…480V AC Input — Trip occurs @ 390V DC bus voltage (equivalent to 275V AC incoming line) |
| Faultless Power Ride Through | 100 milliseconds |
| Control Specifications — Sensorless Vector Control | |
| Carrier Frequency | 2…16 kHz drive rating based on 4 kHz |
| Frequency Accuracy Digital Input |
within ±0.05% of set output frequency |
| Speed Regulation (open loop with slip compensation) | ±1% of base speed across a 60:1 speed range |
| Stop Modes | Multiple programmable stop modes including: Ramp, Coast, DC-Brake, Ramp-to-Hold, and S Curve |
| Acceleration/Deceleration | Two independently programmable acceleration and deceleration times: each time may be programmed from 0…600 seconds in 0.1 second increments |
| Intermittent Overload | 150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds |
| Electronic Motor Overload Protection | Class 10 protection with speed sensitive response |
| Sensorless Vector Control (SVC) Minimum DB Resistance | |||
| Drive Rating | Minimum DB Resistance | ||
| Input Voltage | [kW] | [Hp] | [W] |
| 480V, 50/60 Hz, Three-Phase |
0.4 | 0.5 | 97 |
| 0.75 | 1 | 97 | |
| 1.5 | 2 | 97 | |
| 2.2 | 3 | 97 | |
| 4.0 | 5 | 77 | |
| Power Requirements | |||
| Units | No Options | w/ Brake Contactor | |
| Control Voltage | Volts | 24V DC | |
| Total Control VA (Pick Up) | VA (W) | (11 W) | (16 W) |
| Total Control VA (Hold In) | VA (W) | (11 W) | (16 W) |
| External Devices powered by Control Voltage | |||
| Outputs (2) (1 A max. each) |
Amps | 2 | |
| Total Control VA (Pick Up) with max outputs | VA (W) | (59 W) | (64 W) |
| Total Control VA (Hold In) with max outputs | VA (W) | (59 W) | (64 W) |
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings (Sourced from Control Circuit) | Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 1000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X | IP69K | ||
| Approximate Shipping Weight | 13.6 kg (30 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Wire Size | Primary terminal: (16 …10 AWG) Secondary terminal: (18 …10 AWG) |
Primary terminal: 1.3…5.3 mm2 Secondary terminal: 0.8…5.3 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | (18…10 AWG) | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Other Rating | EMC Emission Levels | ||
| Conducted Radio Frequency Emissions | Class A | ||
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | |||
| Electrostatic Discharge | 4 kV contact and 8 kV Air | ||
| Radio Frequency Electromagnetic Field | 10V/m | ||
| Fast Transient | 2 kV | ||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Overload Characteristics | |||
| Trip Class | 10 | ||
| Overload Protection | I2t overload protection - 150% for 60 s, 200% for 30 s | ||
| Number of Poles | 3 | ||
| DeviceNet Specifications | |||
| DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | ||
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| 364 mA @ 11V DC - 4.0 W | |||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | |||
| Baud Rates | 125, 250, 500 kbps | ||
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| 200 m (656 ft) @ 250 kbps | |||
| 100 m (328 ft) @ 500 kbps | |||
| Certifications | cULus (File No. E207834) UL 508C EN/IEC 60947-1, EN 50178, EN 61800-3 CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC |
||