Bulletin 284 ArmorStart Distributed Motor Controller
| Product Overview |
|
Bulletin 284 ArmorStart Distributed Motor Controller
- On-Machine starting solution
- Variable frequency AC drive using PowerFlex® technology
- Horsepower range 0.5…5 Hp (0.4…3.3 kW)
- Robust IP67/NEMA Type 4 and NEMA Type 4X enclosure rating
- Modular plug and play design
- Quick disconnect connections for I/O, communications, motor, three-phase, and control power
- Four inputs and two outputs (expandable with ArmorPoint)
- LED status indication
- DeviceNet communications
- DeviceLogix component technology
- Peer-to-peer communications (ZIP)
- Connectivity to ArmorPoint distributed I/O products
- ControlNet and EtherNet communication via ArmorPoint
- Factory installed options:
- EMI filter
- Control brake contactor
- Dynamic brake connector
- Source brake contactor
- Output contactor
- Shielded motor cable
- 0…10V analog input
- Safety monitor
- Hand/Off/Auto (HOA) keypad configuration
- EMI filter
Standards Compliance and Certifications
Standards Compliance
UL 508C
CSA C22.2, No. 14
EN/IEC 60947-1, EN 50178, EN 61800-3
CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC
Certifications
cULus (File No. E207834, Guide NMMS, NMMS7)
Description
The Bulletin 284 ArmorStart Distributed Motor Controller is an integrated, pre-engineered starter for variable frequency AC drive applications. The ArmorStart offers a robust IP67/NEMA Type 4 enclosure design, which is suitable for water wash-down environments. The ArmorStart products are also offered with NEMA Type 4X rating, suitable for environment wash down with caustic chemicals used in the food and beverage industry. The wash-down rating is 1000 psi for the NEMA Type 4X rated devices. The modular plug-and-play design offers simplicity in wiring the installation. The quick disconnects for the I/O, communication, and motor connection reduce the wiring time and eliminate wiring errors. The ArmorStart offers, as standard, four DC inputs and two relay outputs to be used with sensors and actuators respectively, for monitoring and controlling the application process. The ArmorStarts LED status indication and built-in diagnostics capabilities allows ease of maintenance and troubleshooting. The optional Hand/Off/Auto (HOA) keypad allows for local start/stop control at the ArmorStart Distributed Motor Controller.
The Bulletin 284 ArmorStart Distributed Motor Controller offers short circuit protection per UL 508C and IEC 60947-1. The ArmorStart is rated for local-disconnect service by incorporating the Bulletin 140 Motor Protector as the local-disconnect, eliminating the need for additional components. The ArmorStart Distributed Motor Controllers are suitable for group motor installations.
Mode of Operation
Volts per Hertz (Sensorless Vector Performance)
This method provides excellent speed regulation and high levels of torque across the entire speed range of the drive, and improved speed regulation even as loading increases. Basic control yields the most cost effective performance when sensorless vector control is not required.
|
Additional Features
- Four Preset Speeds
- Flying Start
- Auto Restart
Sensorless Vector Control (SVC)
Sensorless vector control provides exceptional speed regulation and very high levels of torque across the entire speed range of the drive.
|
Additional Features
- Eight Preset Speeds
- Process Control Loop (PID)
- Skip Frequency
- Step Logic Functionality
- Flying Start
- Timer/Counter Functions
- Auto Restart
-
Description of Features
Overload Protection
The Bulletin 284 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStarts overload protection is programmable via the communication network providing the user with flexibility. The overload trip class allows for class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
Gland Plate Entrance
The ArmorStart product offers two different methods for connecting incoming three-phase and control power to the device. One method offered is the traditional conduit entrance which provides a 3/4 and 1 in. conduit hole opening for wiring three-phase and control power. The second method offers connectivity to the ArmorConnect power media. Factory installed receptacles are provided for connectivity to both three-phase and control power media.
Motor Cable
With every Bulletin 284 ArmorStart Distributed Motor Controller, a 3meter unshielded 4-conductor cordset is provided with each unit as standard. If the optional EMI filter is selected, a 3meter shielded 4-conductor cordset is provided with each unit as standard.
LED Status Indication
The LED Status Indication provides four status LEDs and a Reset button. The LEDs provide status indication for the following:
- POWER LED
The LED is illuminated solid green when control power is present and with the proper polarity
- RUN LED
This LED is illuminated solid green when a start command and control power are present
- NETWORK LED
This bicolor (red/green) LEDs indicates the status of the communication link
- FAULT LED
Indicates Controller Fault (trip) condition
- The Reset Button as a local trip reset.
Inputs
The inputs are single keyed (two inputs per connector), which are sourced from DeviceNet power (24V DC), with LED status indication.
Outputs
Two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power, which can be either, 24V DC, 120V AC, or 240V AC with LED status indication.
Fault Diagnostics
Fault diagnostics capabilities built into the Bulletin 284 ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.
- Short Circuit
- Overtemperature
- Overload
- Output Fuse Protection
- Phase Short
- DeviceNet Power Loss
- Ground Fault
- Internal Communication Fault
- Stall
- DC Bus Fault
- Control Power Loss
- EEPROM Fault
- Control Power Fuse Protection
- Hardware Fault
- I/O Fault
- Restart Retries
- Overcurrent
- Miscellaneous Fault
- Brake Fuse Protection
- Overtemperature
- Output Fuse Protection
- DeviceNet Power Loss
- Internal Communication Fault
- DC Bus Fault
- EEPROM Fault
- Hardware Fault
- Restart Retries
- Miscellaneous Fault
Network and Expandable I/O Capabilities
The Bulletin 284D ArmorStart Distributed Motor Controller delivers enhanced control to access parameter settings and provides fault diagnostics, and remote start/stop control. DeviceNet is the communication protocol, provided with the ArmorStart including DeviceLogix.
The Bulletin 284A ArmorStart Distributed Motor Controller allows connectivity to the ArmorPoint backplane. The ArmorPoint I/O system can communicate using DeviceNet, ControlNet, or EtherNet communication protocols. In addition to the different network protocols, the ArmorPoint Distributed I/O products allow the I/O capability to be expanded beyond the standard two outputs. The two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power of 24V DC, 120V AC, or 240V AC. LED status indication is also provided, as standard with ArmorPoint. When using the ArmorPoint, a maximum of two ArmorPoint Distributed Motor Controllers can be connected to the ArmorPoint Distributed I/O product.
Factory Installed Options
HOA Selector Keypad with Jog Function
The HOA Selector Keypad with Jog Function allows for local start/stop control with capabilities to JOG and to Forward/Reverse motor direction.
EMI Filter
The EMI Filter option is required if the Bulletin 284 ArmorStart Distributed Motor requires to be CE compliant. If the EMI Filter is selected, a 3meter shielded 4conductor cordset is provided as standard. This option is only available with sensorless vector control.
Dynamic Brake Connector
A 3-meter, 3-pin cable for connection to a dynamic brake module is provided as standard when this option is selected. See Accessories on Dynamic Brake Modules ª for available dynamic brake modules.
Control Brake Contactor
An internal contactor is used to switch the electromechanical motor brake On/Off. The motor brake is powered from the control voltage circuit. A customer accessible 3.0 A fuse is provided to protect the brake cable. One 3-meter 3-pin cable for connection to the motor brake is provided as standard when this option is selected.
Source Brake Contactor
An internal contactor is used to switch the electromechanical motor brake on/off. The motor brake is powered from the main power circuit. A customer accessible 3.0 A fuse is provided to protect the brake cable. A 3-meter, 3-pin cable for connection to the motor, is provided as standard when this option is selected.
Output Contactor
An internal contactor will be sourced from control voltage to isolate the load side of the Bulletin 284 ArmorStart Distributed Motor Controller. When control power is applied the output contactor is closed and when control power is removed the output contactor opens. There is no switching element such as a relay in the system. If control power is lost then the output contactor will open since its coil power is lost. A sequenced stop involving the output contact cannot be performed.
Shielded Motor Cable
A 3-meter shielded 4-conductor cordset is provided instead of the 3-meter unshielded 4-conductor cordset. If the EMI Filter is selected, a 3-meter shielded 4-conductor cordset is provided as standard.
Safety Monitor
The Safety Monitor Option allows for independent monitoring of the output status of the device. The function is implemented using a normally closed contact which complies with IEC 60947-5-1 for mechanically linked contacts. Two terminal blocks are provided as the inputs which maybe used with an external safety circuit. The external safety circuit monitors the status of the output contactor.
0…10V Analog Input
The Bulletin 284 Distributed Motor Controller with Sensorless Vector Control provides a 0…10V analog input. The 0…10V Analog Input, 15 A, factory-installed option provides a 0…10V external frequency command from the 0…10V or +/-10V analog input or remote potentiometer. A 5-pin micro receptacle is provided for connectivity for customer connection. A shielded 5-conductor cordset or patch cord is recommended.
Cat. No. Explanation
| 284 | D | | F | H | D2P3 | D | | 10 | | CR | | Option 1 | | Option 2 | | Option 3 | ||||
| a | b | c | d | e | f | g | h | i | j | k |
| a | |
| Bulletin Number | |
| Code | Description |
| 284 | VFD Starter |
| b | |
| Communications | |
| Code | Description |
| D | DeviceNet™ |
| A | ArmorPoint |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | |
| Torque Performance Mode | |
| Code | Description |
| H | Volts per Hertz (Sensorless Vector Performance) |
| e | |||
| Output Current | |||
| 200…240V | 380…480V | ||
| Code | Description | Code | Description |
| B2P3 | 2.3 A, 0.4 kW, 0.5 Hp | D1P4 | 1.4 A, 0.4 kW, 0.5 Hp |
| B4P5 | 4.5 A, 0.75 kW, 1.0 Hp | D2P3 | 2.3 A, 0.75 kW, 1.0 Hp |
| B7P6 | 7.6 A, 1.5 kW, 2.0 Hp | D4P0 | 4.0 A, 1.5 kW, 2.0 Hp |
| — | — | D6P0 | 6.0 A, 2.2 kW, 3.0 Hp |
| — | — | D7P6 | 7.6 A, 3.3 kW, 5.0 Hp |
| f | |
| Control Voltage | |
| Code | Description |
| Z | 24V DC |
| D | 120V AC |
| B | 240V AC |
| g | |
| Short Circuit Protection (Motor Circuit Protector) |
|
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| h | ||||
| Control and 3-Phase Power Connections / Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | N | Conduit Entrance | Conduit Entrance | 3 m, shielded cordset male 90° |
| CR | W ¬ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | N | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, shielded cordset male 90° |
| RR | W ¬ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| i | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad with Jog Function |
| j | ||
| Option 2 | ||
| Code | Description | |
| CB | blank | Control Brake Contactor |
| CB | W ¬ | No cable |
| DB | blank | DB Brake Connector |
| SB | blank | Source Brake Contactor |
| SB | W ¬ | No cable |
| k | |
| Option 3 | |
| Code | Description |
| OC | Output Contactor |
| SM T | Safety Monitor |
¬ See Accessories on Cables for extended motor and brake cable lengths.
T The output contactor is included with the Safety Monitor option.
Product Selection
| Build a Catalog Number |
IP67/NEMA Type 4 with conduit entrance, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200...240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FHB2P3Z-10-CR | 284D-FHB2P3D-10-CR | 284D-FHB2P3B-10-CR |
| 0.75 | 1 | 4.5 | 284D-FHB4P5Z-10-CR | 284D-FHB4P5D-10-CR | 284D-FHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-FHB7P6Z-25-CR | 284D-FHB7P6D-25-CR | 284D-FHB7P6B-25-CR | |
| 380...480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FHD1P4Z-10-CR | 284D-FHD1P4D-10-CR | 284D-FHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-FHD2P3Z-10-CR | 284D-FHD2P3D-10-CR | 284D-FHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-FHD4P0Z-10-CR | 284D-FHD4P0D-10-CR | 284D-FHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-FHD6P0Z-25-CR | 284D-FHD6P0D-25-CR | 284D-FHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-FHD7P6Z-25-CR | 284D-FHD7P6D-25-CR | 284D-FHD7P6B-25-CR | |
IP67/NEMA Type 4 with conduit entrance, ArmorPoint communications, and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FHB2P3Z-10-CR | 284A-FHB2P3D-10-CR | 284A-FHB2P3B-10-CR |
| 0.75 | 1 | 5 | 284A-FHB4P5Z-10-CR | 284A-FHB4P5D-10-CR | 284A-FHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284A-FHB7P6Z-25-CR | 284A-FHB7P6D-25-CR | 284A-FHB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FHD1P4Z-10-CR | 284A-FHD1P4D-10-CR | 284A-FHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284A-FHD2P3Z-10-CR | 284A-FHD2P3D-10-CR | 284A-FHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284A-FHD4P0Z-10-CR | 284A-FHD4P0D-10-CR | 284A-FHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284A-FHD6P0Z-25-CR | 284A-FHD6P0D-25-CR | 284A-FHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284A-FHD7P6Z-25-CR | 284A-FHD7P6D-25-CR | 284A-FHD7P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FHB2P3Z-10-RR | 284D-FHB2P3D-10-RR | 284D-FHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284D-FHB4P5Z-10-RR | 284D-FHB4P5D-10-RR | 284D-FHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-FHB7P6Z-25-RR | 284D-FHB7P6D-25-RR | 284D-FHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FHD1P4Z-10-RR | 284D-FHD1P4D-10-RR | 284D-FHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-FHD2P3Z-10-RR | 284D-FHD2P3D-10-RR | 284D-FHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-FHD4P0Z-10-RR | 284D-FHD4P0D-10-RR | 284D-FHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-FHD6P0Z-25-RR | 284D-FHD6P0D-25-RR | 284D-FHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-FHD7P6Z-25-RR | 284D-FHD7P6D-25-RR | 284D-FHD7P6B-25-RR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, ArmorPoint communications, and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FHB2P3Z-10-RR | 284A-FHB2P3D-10-RR | 284A-FHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284A-FHB4P5Z-10-RR | 284A-FHB4P5D-10-RR | 284A-FHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284A-FHB7P6Z-25-RR | 284A-FHB7P6D-25-RR | 284A-FHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FHD1P4Z-10-RR | 284A-FHD1P4D-10-RR | 284A-FHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284A-FHD2P3Z-10-RR | 284A-FHD2P3D-10-RR | 284A-FHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284A-FHD4P0Z-10-RR | 284A-FHD4P0D-10-RR | 284A-FHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284A-FHD6P0Z-25-RR | 284A-FHD6P0D-25-RR | 284A-FHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284A-FHD7P6Z-25-RR | 284A-FHD7P6D-25-RR | 284A-FHD7P6B-25-RR | |
NEMA Type 4X with conduit entrance, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SHB2P3Z-10-CR | 284D-SHB2P3D-10-CR | 284D-SHB2P3B-10-CR |
| 0.75 | 1 | 4.5 | 284D-SHB4P5Z-10-CR | 284D-SHB4P5D-10-CR | 284D-SHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-SHB7P6Z-25-CR | 284D-SHB7P6D-25-CR | 284D-SHB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SHD1P4Z-10-CR | 284D-SHD1P4D-10-CR | 284D-SHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-SHD2P3Z-10-CR | 284D-SHD2P3D-10-CR | 284D-SHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-SHD4P0Z-10-CR | 284D-SHD4P0D-10-CR | 284D-SHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-SHD6P0Z-25-CR | 284D-SHD6P0D-25-CR | 284D-SHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-SHD7P6Z-25-CR | 284D-SHD7P6D-25-CR | 284D-SHD7P6B-25-CR | |
NEMA Type 4X with quick disconnects for ArmorConnect power media, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SHB2P3Z-10-RR | 284D-SHB2P3D-10-RR | 284D-SHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284D-SHB4P5Z-10-RR | 284D-SHB4P5D-10-RR | 284D-SHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-SHB7P6Z-25-RR | 284D-SHB7P6D-25-RR | 284D-SHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SHD1P4Z-10-RR | 284D-SHD1P4D-10-RR | 284D-SHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-SHD2P3Z-10-RR | 284D-SHD2P3D-10-RR | 284D-SHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-SHD4P0Z-10-RR | 284D-SHD4P0D-10-RR | 284D-SHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-SHD6P0Z-25-RR | 284D-SHD6P0D-25-RR | 284D-SHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-SHD7P6Z-25-RR | 284D-SHD7P6D-25-RR | 284D-SHD7P6B-25-RR | |
Cat. No. Explanation
| 284 | D | | F | V | D2P3 | D | | 10 | | CR | | Option 1 | | Option 2 | | Option 3 |
| a | b | c | d | e | f | g | h | i | j | k |
| a | |
| Bulletin Number | |
| Code | Description |
| 284 | UFD Starter |
| b | |
| Communications | |
| Code | Description |
| D | DeviceNet™ |
| A | ArmorPoint |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | |
| Torque Performance Mode | |
| Code | Description |
| V | Sensorless Vector Control and Volts per Hertz |
| e | |||||
| Output Current | |||||
| 200…240V | 380…480V | 500…600V | |||
| Code | Description | Code | Description | Code | Description |
| B2P3 | 2.3 A, 0.4 kW, 0.5 Hp | D1P4 | 1.4 A, 0.4 kW, 0.5 Hp | E1P7 | 1.7 A, 0.75 kW, 1.0 Hp |
| B5P0 | 5.0 A, 0.75 kW, 1.0 Hp | D2P3 | 2.3 A, 0.75 kW, 1.0 Hp | E3P0 | 3.0 A, 1.5 kW, 2.0 Hp |
| B7P6 | 7.6 A, 1.5 kW, 2.0 Hp | D4P0 | 4.0 A, 1.5 kW, 2.0 Hp | E4P2 | 4.2 A, 2.2 kW, 3.0 Hp |
| — | — | D6P0 | 6.0 A, 2.2 kW, 3.0 Hp | E6P6 | 6.6 A, 4.0 kW, 5.0 Hp |
| — | — | D7P6 | 7.6 A, 3.3 kW, 5.0 Hp | — | — |
| f | |
| Control Voltage | |
| Code | Description |
| Z | 24V DC |
| D | 120V AC |
| B | 240V AC |
| g | |
| Short Circuit Protection (Motor Circuit Protector) | |
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| h | ||||
| Control and 3-Phase Power Connections / Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | N | Conduit Entrance | Conduit Entrance | 3 m, shielded cordset male 90° |
| CR | W ¬ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | N | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, shielded cordset male 90° |
| RR | W ¬ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| i | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad with Jog Function |
| j | ||
| Option 2 | ||
| Code | Description | |
| CB | blank | Control Brake Contactor |
| CB | W ¬ | No cable |
| DB | blank | DB Brake Connector |
| SB | blank | Source Brake Contactor |
| SB | W ¬ | No cable |
| k | |
| Option 3 | |
| Code | Description |
| EMI | EMI Filter |
| OC | Output Contactor |
¬ See Accessories on Cables for extended motor and brake cable lengths.
T The output contactor is included with the Safety Monitor option.
Product Selection
| Build a Catalog Number |
IP67/NEMA Type 4 with conduit entrance, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200...240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FVB2P3Z-10-CR | 284D-FVB2P3D-10-CR | 284D-FVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284D-FVB5P0Z-10-CR | 284D-FVB5P0D-10-CR | 284D-FVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-FVB7P6Z-25-CR | 284D-FVB7P6D-25-CR | 284D-FVB7P6B-25-CR | |
| 380...480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FVD1P4Z-10-CR | 284D-FVD1P4D-10-CR | 284D-FVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-FVD2P3Z-10-CR | 284D-FVD2P3D-10-CR | 284D-FVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-FVD4P0Z-10-CR | 284D-FVD4P0D-10-CR | 284D-FVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-FVD6P0Z-25-CR | 284D-FVD6P0D-25-CR | 284D-FVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-FVD7P6Z-25-CR | 284D-FVD7P6D-25-CR | 284D-FVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-FVE1P7Z-10-CR | 284D-FVE1P7D-10-CR | 284D-FVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284D-FVE3P0Z-10-CR | 284D-FVE3P0D-10-CR | 284D-FVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284D-FVE4P2Z-10-CR | 284D-FVE4P2D-10-CR | 284D-FVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284D-FVE6P6Z-25-CR | 284D-FVE6P6D-25-CR | 284D-FVE6P6B-25-CR | |
IP67/NEMA Type 4 with conduit entrance, ArmorPoint communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FVB2P3Z-10-CR | 284A-FVB2P3D-10-CR | 284A-FVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284A-FVB5P0Z-10-CR | 284A-FVB5P0D-10-CR | 284A-FVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284A-FVB7P6Z-25-CR | 284A-FVB7P6D-25-CR | 284A-FVB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FVD1P4Z-10-CR | 284A-FVD1P4D-10-CR | 284A-FVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284A-FVD2P3Z-10-CR | 284A-FVD2P3D-10-CR | 284A-FVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284A-FVD4P0Z-10-CR | 284A-FVD4P0D-10-CR | 284A-FVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284A-FVD6P0Z-25-CR | 284A-FVD6P0D-25-CR | 284A-FVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284A-FVD7P6Z-25-CR | 284A-FVD7P6D-25-CR | 284A-FVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284A-FVE1P7Z-10-CR | 284A-FVE1P7D-10-CR | 284A-FVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284A-FVE3P0Z-10-CR | 284A-FVE3P0D-10-CR | 284A-FVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284A-FVE4P2Z-10-CR | 284A-FVE4P2D-10-CR | 284A-FVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284A-FVE6P6Z-25-CR | 284A-FVE6P6D-25-CR | 284A-FVE6P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FVB2P3Z-10-RR | 284D-FVB2P3D-10-RR | 284D-FVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284D-FVB5P0Z-10-RR | 284D-FVB5P0D-10-RR | 284D-FVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-FVB7P6Z-25-RR | 284D-FVB7P6D-25-RR | 284D-FVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FVD1P4Z-10-RR | 284D-FVD1P4D-10-RR | 284D-FVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-FVD2P3Z-10-RR | 284D-FVD2P3D-10-RR | 284D-FVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-FVD4P0Z-10-RR | 284D-FVD4P0D-10-RR | 284D-FVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-FVD6P0Z-25-RR | 284D-FVD6P0D-25-RR | 284D-FVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-FVD7P6Z-25-RR | 284D-FVD7P6D-25-RR | 284D-FVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-FVE1P7Z-10-RR | 284D-FVE1P7D-10-RR | 284D-FVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284D-FVE3P0Z-10-RR | 284D-FVE3P0D-10-RR | 284D-FVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284D-FVE4P2Z-10-RR | 284D-FVE4P2D-10-RR | 284D-FVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284D-FVE6P6Z-25-RR | 284D-FVE6P6D-25-RR | 284D-FVE6P6B-25-RR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, ArmorPoint communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FVB2P3Z-10-RR | 284A-FVB2P3D-10-RR | 284A-FVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284A-FVB5P0Z-10-RR | 284A-FVB5P0D-10-RR | 284A-FVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284A-FVB7P6Z-25-RR | 284A-FVB7P6D-25-RR | 284A-FVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FVD1P4Z-10-RR | 284A-FVD1P4D-10-RR | 284A-FVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284A-FVD2P3Z-10-RR | 284A-FVD2P3D-10-RR | 284A-FVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284A-FVD4P0Z-10-RR | 284A-FVD4P0D-10-RR | 284A-FVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284A-FVD6P0Z-25-RR | 284A-FVD6P0D-25-RR | 284A-FVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284A-FVD7P6Z-25-RR | 284A-FVD7P6D-25-RR | 284A-FVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284A-FVE1P7Z-10-RR | 284A-FVE1P7D-10-RR | 284A-FVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284A-FVE3P0Z-10-RR | 284A-FVE3P0D-10-RR | 284A-FVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284A-FVE4P2Z-10-RR | 284A-FVE4P2D-10-RR | 284A-FVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284A-FVE6P6Z-25-RR | 284A-FVE6P6D-25-RR | 284A-FVE6P6B-25-RR | |
NEMA Type 4X with conduit entrance, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SVB2P3Z-10-CR | 284D-SVB2P3D-10-CR | 284D-SVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284D-SVB5P0Z-10-CR | 284D-SVB5P0D-10-CR | 284D-SVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-SVB7P6Z-25-CR | 284D-SVB7P6D-25-CR | 284D-SVB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SVD1P4Z-10-CR | 284D-SVD1P4D-10-CR | 284D-SVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-SVD2P3Z-10-CR | 284D-SVD2P3D-10-CR | 284D-SVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-SVD4P0Z-10-CR | 284D-SVD4P0D-10-CR | 284D-SVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-SVD6P0Z-25-CR | 284D-SVD6P0D-25-CR | 284D-SVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-SVD7P6Z-25-CR | 284D-SVD7P6D-25-CR | 284D-SVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-SVE1P7Z-10-CR | 284D-SVE1P7D-10-CR | 284D-SVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284D-SVE3P0Z-10-CR | 284D-SVE3P0D-10-CR | 284D-SVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284D-SVE4P2Z-10-CR | 284D-SVE4P2D-10-CR | 284D-SVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284D-SVE6P6Z-25-CR | 284D-SVE6P6D-25-CR | 284D-SVE6P6B-25-CR | |
NEMA Type 4X with quick disconnects for ArmorConnect power media, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SVB2P3Z-10-RR | 284D-SVB2P3D-10-RR | 284D-SVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284D-SVB5P0Z-10-RR | 284D-SVB5P0D-10-RR | 284D-SVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-SVB7P6Z-25-RR | 284D-SVB7P6D-25-RR | 284D-SVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SVD1P4Z-10-RR | 284D-SVD1P4D-10-RR | 284D-SVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-SVD2P3Z-10-RR | 284D-SVD2P3D-10-RR | 284D-SVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-SVD4P0Z-10-RR | 284D-SVD4P0D-10-RR | 284D-SVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-SVD6P0Z-25-RR | 284D-SVD6P0D-25-RR | 284D-SVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-SVD7P6Z-25-RR | 284D-SVD7P6D-25-RR | 284D-SVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-SVE1P7Z-10-RR | 284D-SVE1P7D-10-RR | 284D-SVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284D-SVE3P0Z-10-RR | 284D-SVE3P0D-10-RR | 284D-SVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284D-SVE4P2Z-10-RR | 284D-SVE4P2D-10-RR | 284D-SVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284D-SVE6P6Z-25-RR | 284D-SVE6P6D-25-RR | 284D-SVE6P6B-25-RR | |
Options Factory Installed
Accessories
Sealing Caps
| Description | For Use With | Cat. No. |
| Plastic Sealing Cap (M12)¬ | Input I/O Connection | 1485A-M12 |
| AC Micro Aluminum Sealing Cap - External¬ | Output I/O Connection | 889A-RMCAP |
| Stainless Steel Sealing Cap (M12)T | Input I/O Connection | 1485AS-C3 |
| Stainless Steel Sealing Cap (M12)T | Output I/O Connection | 889AS-RMCAP |
| ¬ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections. | ||
| T To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections. | ||
Cables
| Description | Cable Rating | Length [m (ft)] | Cat. No. |
| Extended Motor Cable Cordsets | |||
| 90° M22 Motor Cordset | IP67/NEMA Type 4 | 6 (19.6) | 280-MTR22-M6 |
| 14 (45.9) | 280-MTR22-M14 | ||
| 90° M22 Motor Cordset | IP69K | 6 (19.6) | 280S-MTR22-M6 |
| 14 (45.9) | 280S-MTR22-M14 | ||
| Motor Cable Patchcords | |||
| 90° Male/Straight Female M22 | IP67/NEMA Type 4 | 1 (3.3) | 280-MTR22-M1D |
| 3 (9.8) | 280-MTR22-M3D | ||
| 90° Male/Straight Female M22 | IP69K | 1 (3.3) | 280S-MTR22-M1D |
| 3 (9.8) | 280S-MTR22-M3D | ||
| Shielded Motor Cable Cordsets | |||
| 90° M22 Motor Cordset | IP67/NEMA Type 4 | 6 (19.6) | 284-MTRS22-M6 |
| 90° M22 Motor Cordset | IP67/NEMA Type 4 | 14 (45.9) | 284-MTRS22-M14 |
| 90° M22 Motor Cordset | IP69K | 6 (19.6) | 284S-MTRS22-M6 |
| 90° M22 Motor Cordset | IP69K | 14 (45.9) | 284S-MTRS22-M14 |
| Shielded Motor Cable Patchcords | |||
| 90° Male/Straight Female M22 | IP67/NEMA Type 4 | 1 (3.3) | 284-MTRS22-M1D |
| 90° Male/Straight Female M22 | IP67/NEMA Type 4 | 3 (9.8) | 284-MTRS22-M3D |
| 90° Male/Straight Female M22 | IP69K | 1 (3.3) | 284S-MTRS22-M1D |
| 90° Male/Straight Female M22 | IP69K | 3 (9.8) | 284S-MTRS22-M3D |
| Extended Brake Cable Cordsets | |||
| 90° M25 Source Brake Cable | IP67/NEMA Type 4 | 6 (19.6) | 285-BRC25-M6 |
| 90° M25 Source Brake Cable | IP67/NEMA Type 4 | 14 (45.9) | 285-BRC25-M14 |
| 90° M25 Source Brake Cable | IP69K | 6 (19.6) | 285S-BRC25-M6 |
| 90° M25 Source Brake Cable | IP69K | 14 (45.9) | 285S-BRC25-M14 |
ArmorPoint® Media §
| Description | Length [m (ft)] | Cat. No. |
| ArmorPoint Bus Extension Cable including Terminating Resistor | 1 (3.3) | 280A-EXT1 |
| Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol | 1 (3.3) | 280A-EXTCABLE |
| § ArmorPoint media is only available with an IP67/NEMA Type 4 rating. | ||
DeviceNet Media §
Sensor Media z
Dynamic Brake Modules ª
| Drive Ratings | Cat. No. § | |||
| Input Voltage | kW | Hp | Min. Resistance [W] | |
| 240V, 50/60 Hz, 3-Phase | 0.4 | 0.5 | 48 | AK-R2-091P500 |
| 0.75 | 1.0 | 48 | AK-R2-091P500 | |
| 1.5 | 2.0 | 48 | AK-R2-091P500 | |
| 2.2 | 3.0 | 32 | AK-R2-047P500 | |
| 3.7 | 5.0 | 32 | AK-R2-047P500 | |
| 480V, 50/60 Hz, 3-Phase | 0.4 | 0.5 | 97 | AK-R2-360P500 |
| 0.75 | 1.0 | 97 | AK-R2-360P500 | |
| 1.5 | 2.0 | 97 | AK-R2-360P500 | |
| 2.2 | 3.0 | 77 | AK-R2-120P1K2 | |
| 4.0 | 5.0 | 77 | AK-R2-120P1K2 | |
| § The resistors listed in this table are rated for 5% duty cycle. | ||||
| ª Dynamic brake modules have an IP00 rating. | ||||
Peer-to-Peer Communications
|
The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP) which allows one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.
ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)
|
When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Bulletin 280A-EXT1. The 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.
Note:Access to DeviceLogix programming is available with RSNetworx for DeviceNet.
|
If an additional ArmorStart Distributed Motor Controller is to be connected, the Bulletin 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.
I/O Expansion with DeviceNet
If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Bulletin 1738-ADNX ArmorPoint Distributed I/O product.
|
Bulletin 1738 ArmorPoint Distributed I/O Products
Digital Output Products
Digital Input Products
Analog Products
Power Supply Products
| Description | Cat. No. | |
|
|
ArmorPoint I/O Field Potential Distributor Module | 1738-FPD |
| 24V DC Expansion Power Supply | 1738-EP24DC | |
AC and Relay Products
Specialty Products
Adapter Products
Specifications
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…500V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| 120V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | ||||||
| Short Circuit Protection | SCPD performance Type 1 | Current Rating | Voltage | 480Y/277V | 480/480V | 600Y/347V | 600V |
| 10 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 25 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NEC Group Motor | — | |||||
| Power Requirements | ||||||||||
| Units | No Options | Brake or Output Contactor | w/ Brake and Output Contactor | |||||||
| Control Voltage | Volts | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC |
| Total Control VA (Pick Up) | VA (W) | (11 W) | 16 | 24 | (13 W) | 38 | 46 | (16 W) | 60 | 68 |
| Total Control VA (Hold In) | VA (W) | (11 W) | 16 | 24 | (13 W) | 20 | 28 | (16 W) | 24 | 32 |
| External Devices powered by Control Voltage | ||||||||||
| Outputs (2) (1 A max. each) |
Amps | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Total Control VA (Pick Up) with max outputs | VA (W) | (59 W) | 256 | 504 | (61 W) | 278 | 548 | (64 W) | 300 | 548 |
| Total Control VA (Hold In) with max outputs | VA (W) | (59 W) | 256 | 504 | (61 W) | 261 | 512 | (64 W) | 264 | 512 |
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings (Sourced from Control Circuit) | Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 1000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X | IP69K | ||
| Approximate Shipping Weight | 13.6 kg (30 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Wire Size | Primary/Secondary terminal: (16 …10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | (18…10 AWG) | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Other Rating | EMC Emission Levels | ||
| Conducted Radio Frequency Emissions | Class A | ||
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | |||
| Electrostatic Discharge | 4 kV contact and 8 kV Air | ||
| Radio Frequency Electromagnetic Field | 10V/m | ||
| Fast Transient | 2 kV | ||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Overload Characteristics | |||
| Trip Class | 10 | ||
| Overload Protection | I2t overload protection - 150% for 60 s, 200% for 30 s | ||
| Number of Poles | 3 | ||
| DeviceNet Specifications | |||
| DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | ||
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| 364 mA @ 11V DC - 4.0 W | |||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | |||
| Baud Rates | 125, 250, 500 kbps | ||
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| 200 m (656 ft) @ 250 kbps | |||
| 100 m (328 ft) @ 500 kbps | |||
| Certifications | cULus (File No. E207834) UL 508C EN/IEC 60947-1, EN 50178, EN 61800-3 CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC |
||
External Connections for Input Connector
|
External Connections for Output Connector
|
External Connections for DeviceNet Connector
|
External Connections for Motor Connector
|
External Connections for Brake Contactor Connector
|
External Connections for Dynamic Brake Connection
|
External Connections for ArmorPoint Interface (IN)
|
External Connections for ArmorPoint Interface (OUT)
|
External Connections for 0…10V Analog Input
|
Overload Curves
|
Approximate Dimensions
Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, IP67/NEMA Type 4 with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, IP67/NEMA Type 4 with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, IP67/NEMA Type 4 with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, IP67/NEMA Type 4 with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, NEMA Type 4X with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, NEMA Type 4X with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, NEMA Type 4X with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, NEMA Type 4X with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dynamic Brake Modules
Dimensions are in millimeters (inches) and weights are in kilograms (pounds). Dimensions are not intended to be used for manufacturing purposes.
|
| Frame | Cat. No. | Weight [kg (lb)] |
| A | AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 | 1.1 (2.5) |
| B | AK-R2-030P1K2, AK-R2-120P1K2 | 2.7 (6) |