Bulletin 284 ArmorStart Distributed Motor Controller
| Product Overview |
|
Bulletin 284 ArmorStart Distributed Motor Controller
- On-Machine starting solution
- Variable frequency AC drive using PowerFlex® technology
- Horsepower range 0.5…5 Hp (0.4…3.3 kW)
- Robust IP67/NEMA Type 4 or NEMA Type 4X enclosure rating
- Quick disconnect for I/O, communications, motor, three-phase, and control power connections
- LED status indication
- EtherNet/IP, DeviceNet, and ControlNet communications
- Local logic technology using DeviceLogix
- Peer-to-peer communications (ZIP) (not available with EtherNet/IP communications)
- Connectivity to ArmorPoint distributed I/O products
- Factory installed options:
- EMI filter
- Control brake contactor
- Dynamic brake connector
- Source brake contactor
- Output contactor
- Shielded motor cable
- 0…10V analog input
- Safety monitor
- Hand/Off/Auto (HOA) with jog
- EMI filter
Standards Compliance and Certifications
Standards Compliance
UL 508C
CSA C22.2, No. 14
EN/IEC 60947-4-2, EN 50178, EN 61800-3
CE Marked per Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/EC
CCC
ODVA for EtherNet/IP and DeviceNet
Certifications
cULus (File No. E207834, Guide NMMS, NMMS7)
Mode of Operation
Sensorless Vector Performance (SVP) - V/Hz
This method provides excellent speed regulation and high levels of torque across the entire speed range of the drive, and improved speed regulation even as loading increases. Basic control yields the most cost-effective performance when sensorless vector control is not required.
|
Sensorless Vector Control (SVC)
Sensorless vector control provides exceptional speed regulation and very high levels of torque across the entire speed range of the drive.
|
Additional Features
- Eight Preset Speeds
- Process Control Loop (PID)
- Skip Frequency
- Step Logic Functionality
- Flying Start
- Timer/Counter Functions
Auto Restart
Overload Protection
The Bulletin 284 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStarts overload protection is programmable via the communication network providing the user with flexibility. The overload trip class allows for class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
Fault Diagnostics
Fault diagnostics capabilities built into the Bulletin 284 ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.
- Short Circuit
- Overtemperature
- Overload
- Output Fuse Protection
- Phase Short
- Brake Fuse Protection
- Ground Fault
- Internal Communication Fault
- Stall
- DC Bus Fault
- Control Power Loss
- EEPROM Fault
- Control Power Fuse Protection
- Hardware Fault
- I/O Fault
- Restart Retries
- Overcurrent
- Miscellaneous Fault
- DeviceNet Power Loss
- Overtemperature
- Output Fuse Protection
- DeviceNet Power Loss
- Internal Communication Fault
- DC Bus Fault
- EEPROM Fault
- Hardware Fault
- Restart Retries
- Miscellaneous Fault
Local Logic via DeviceLogix
Provides local control over the devices discrete and network I/O. DeviceLogix consists of function blocks, inputs, outputs, and actual hardware data, including fault and status bits.
Factory-Installed Options
HOA Selector Keypad with Jog Function
The HOA Selector Keypad with Jog Function allows for local start/stop control with capabilities to JOG and to Forward/Reverse motor direction.
EMI Filter
The EMI Filter is required to be CE compliant. When selected, a 3meter shielded 4conductor motor cordset is provided as standard. This is only available with sensorless vector control.
Control Brake Connector
An internal contactor is used to switch an electromechanical motor brake On/Off. The motor brake is powered from the control power circuit. The configuration of the R1 relay controls the function of the brake. A customer accessible 3 A fuse is provided to protect the brake cable. Included is a 3-meter 3-pin cordset for connection to the motor brake as standard.
Source Brake Contactor
An internal contactor is used to switch an electromechanical motor brake On/Off. The motor brake is powered from the line power circuit. The configuration of the R1 relay controls the function of the brake. A customer accessible 3 A fuse is provided to protect the brake cable. Included is a 3-meter 3-pin cordset for connection to the motor brake as standard.
Shielded Motor Cable
A 3-meter shielded 4-conductor cordset is provided instead of the 3-meter unshielded 4-conductor cordset, when the EMI Filter is selected.
IP67 Dynamic Brake Connector
The IP67 Dynamic Brake Resistor design offers simplicity in wiring and installation. The DB1 option must be selected in order to have the quick disconnect connectivity. See accessories for available IP67 Dynamic Brake Resistors.
Output Contactor
An internal contactor is sourced from control voltage to isolate the load side of the VFD. Control voltage or the at-motor disconnect controls the ON/OFF of the output contactor. A sequenced stop involving the output contact cannot be performed.
Safety Monitor
The Safety Monitor Option allows for independent monitoring of the output contactor status. The output contactor is provided as standard with this option. The function is implemented using the normally closed auxiliary contact which complies with
IEC 60947-5-1 for mechanically linked contacts. Two terminal blocks are provided as inputs to an external device, such as a safety circuit.
0…10V Analog Input Connector
This provides 0…10V analog input as an external frequency command from the analog input or remote potentiometer. A 5-pin micro receptacle is provided for connectivity. A shielded 5-conductor cordset or patch cord is recommended.
Catalog Number Explanation
Sensorless Vector Performance (SVP), typical of Powerflex 4 Class Drive
| 284 | D | | F | H | D2P3 | D | | 10 | | CR | | Option 1 | | Option 2 | | Option 3 | ||||
| a | b | c | d | e | f | g | h | i | j | k |
| a | |
| Bulletin Number | |
| Code | Description |
| 284 | VFD Starter |
| b | |
| Communications | |
| Code | Description |
| D | DeviceNet |
| A | ArmorPoint |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | |
| Torque Performance Mode | |
| Code | Description |
| H | Volts per Hertz (Sensorless Vector Performance) |
| e | |||
| Output Current | |||
| 200…240V | 380…480V | ||
| Code | Description | Code | Description |
| B2P3 | 2.3 A, 0.4 kW, 0.5 Hp | D1P4 | 1.4 A, 0.4 kW, 0.5 Hp |
| B4P5 | 4.5 A, 0.75 kW, 1.0 Hp | D2P3 | 2.3 A, 0.75 kW, 1.0 Hp |
| B7P6 | 7.6 A, 1.5 kW, 2.0 Hp | D4P0 | 4.0 A, 1.5 kW, 2.0 Hp |
| — | — | D6P0 | 6.0 A, 2.2 kW, 3.0 Hp |
| — | — | D7P6 | 7.6 A, 3.3 kW, 5.0 Hp |
| f | |
| Control Voltage | |
| Code | Description |
| Z | 24V DC |
| D | 120V AC |
| B | 240V AC |
| g | |
| Short Circuit Protection (Motor Circuit Protector) |
|
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| h | ||||
| Control and 3-Phase Power Connections / Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | N | Conduit Entrance | Conduit Entrance | 3 m, shielded cordset male 90° |
| CR | W ⋆ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | N | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, shielded cordset male 90° |
| RR | W ⋆ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| i | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad with Jog Function |
| j | ||
| Option 2 | ||
| Code | Description | |
| CB | blank | Control Brake Contactor |
| CB | W ⋆ | No cable |
| DB | blank | DB Brake Connector |
| SB | blank | Source Brake Contactor |
| SB | W ⋆ | No cable |
| k | |
| Option 3 | |
| Code | Description |
| OC | Output Contactor |
| SM § | Safety Monitor |
⋆ See Accessories on Motor and Brake Cables for extended motor and brake cable lengths.
The output contactor is included with the Safety Monitor option.
§ Not available with round media option (RR).
Product Selection
| Build a Catalog Number |
DeviceNet Network Communication
IP67/NEMA Type 4 with conduit entrance, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200...240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FHB2P3Z-10-CR | 284D-FHB2P3D-10-CR | 284D-FHB2P3B-10-CR |
| 0.75 | 1 | 4.5 | 284D-FHB4P5Z-10-CR | 284D-FHB4P5D-10-CR | 284D-FHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-FHB7P6Z-25-CR | 284D-FHB7P6D-25-CR | 284D-FHB7P6B-25-CR | |
| 380...480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FHD1P4Z-10-CR | 284D-FHD1P4D-10-CR | 284D-FHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-FHD2P3Z-10-CR | 284D-FHD2P3D-10-CR | 284D-FHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-FHD4P0Z-10-CR | 284D-FHD4P0D-10-CR | 284D-FHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-FHD6P0Z-25-CR | 284D-FHD6P0D-25-CR | 284D-FHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-FHD7P6Z-25-CR | 284D-FHD7P6D-25-CR | 284D-FHD7P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FHB2P3Z-10-RR | 284D-FHB2P3D-10-RR | 284D-FHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284D-FHB4P5Z-10-RR | 284D-FHB4P5D-10-RR | 284D-FHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-FHB7P6Z-25-RR | 284D-FHB7P6D-25-RR | 284D-FHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FHD1P4Z-10-RR | 284D-FHD1P4D-10-RR | 284D-FHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-FHD2P3Z-10-RR | 284D-FHD2P3D-10-RR | 284D-FHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-FHD4P0Z-10-RR | 284D-FHD4P0D-10-RR | 284D-FHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-FHD6P0Z-25-RR | 284D-FHD6P0D-25-RR | 284D-FHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-FHD7P6Z-25-RR | 284D-FHD7P6D-25-RR | 284D-FHD7P6B-25-RR | |
NEMA Type 4X with conduit entrance, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SHB2P3Z-10-CR | 284D-SHB2P3D-10-CR | 284D-SHB2P3B-10-CR |
| 0.75 | 1 | 4.5 | 284D-SHB4P5Z-10-CR | 284D-SHB4P5D-10-CR | 284D-SHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-SHB7P6Z-25-CR | 284D-SHB7P6D-25-CR | 284D-SHB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SHD1P4Z-10-CR | 284D-SHD1P4D-10-CR | 284D-SHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-SHD2P3Z-10-CR | 284D-SHD2P3D-10-CR | 284D-SHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-SHD4P0Z-10-CR | 284D-SHD4P0D-10-CR | 284D-SHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-SHD6P0Z-25-CR | 284D-SHD6P0D-25-CR | 284D-SHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-SHD7P6Z-25-CR | 284D-SHD7P6D-25-CR | 284D-SHD7P6B-25-CR | |
NEMA Type 4X with quick disconnects for ArmorConnect power media, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SHB2P3Z-10-RR | 284D-SHB2P3D-10-RR | 284D-SHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284D-SHB4P5Z-10-RR | 284D-SHB4P5D-10-RR | 284D-SHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-SHB7P6Z-25-RR | 284D-SHB7P6D-25-RR | 284D-SHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SHD1P4Z-10-RR | 284D-SHD1P4D-10-RR | 284D-SHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-SHD2P3Z-10-RR | 284D-SHD2P3D-10-RR | 284D-SHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-SHD4P0Z-10-RR | 284D-SHD4P0D-10-RR | 284D-SHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-SHD6P0Z-25-RR | 284D-SHD6P0D-25-RR | 284D-SHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-SHD7P6Z-25-RR | 284D-SHD7P6D-25-RR | 284D-SHD7P6B-25-RR | |
ArmorPoint Bus Network Communication
IP67/NEMA Type 4 with conduit entrance, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FHB2P3Z-10-CR | 284A-FHB2P3D-10-CR | 284A-FHB2P3B-10-CR |
| 0.75 | 1 | 5 | 284A-FHB4P5Z-10-CR | 284A-FHB4P5D-10-CR | 284A-FHB4P5B-10-CR | |
| 1.5 | 2 | 7.6 | 284A-FHB7P6Z-25-CR | 284A-FHB7P6D-25-CR | 284A-FHB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FHD1P4Z-10-CR | 284A-FHD1P4D-10-CR | 284A-FHD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284A-FHD2P3Z-10-CR | 284A-FHD2P3D-10-CR | 284A-FHD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284A-FHD4P0Z-10-CR | 284A-FHD4P0D-10-CR | 284A-FHD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284A-FHD6P0Z-25-CR | 284A-FHD6P0D-25-CR | 284A-FHD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284A-FHD7P6Z-25-CR | 284A-FHD7P6D-25-CR | 284A-FHD7P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Volts per Hertz (SVP) torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FHB2P3Z-10-RR | 284A-FHB2P3D-10-RR | 284A-FHB2P3B-10-RR |
| 0.75 | 1 | 4.5 | 284A-FHB4P5Z-10-RR | 284A-FHB4P5D-10-RR | 284A-FHB4P5B-10-RR | |
| 1.5 | 2 | 7.6 | 284A-FHB7P6Z-25-RR | 284A-FHB7P6D-25-RR | 284A-FHB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FHD1P4Z-10-RR | 284A-FHD1P4D-10-RR | 284A-FHD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284A-FHD2P3Z-10-RR | 284A-FHD2P3D-10-RR | 284A-FHD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284A-FHD4P0Z-10-RR | 284A-FHD4P0D-10-RR | 284A-FHD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284A-FHD6P0Z-25-RR | 284A-FHD6P0D-25-RR | 284A-FHD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284A-FHD7P6Z-25-RR | 284A-FHD7P6D-25-RR | 284A-FHD7P6B-25-RR | |
Catalog Number Explanation
Sensorless Vector Control (SVC), typical of Powerflex 40 Class Drive
| 284 | D | | F | V | D2P3 | D | | 10 | | CR | | Option 1 | | Option 2 | | Option 3 |
| a | b | c | d | e | f | g | h | i | j | k |
| a | |
| Bulletin Number | |
| Code | Description |
| 284 | VFD Starter |
| b | |
| Communications | |
| Code | Description |
| E | EtherNet/IP |
| D | DeviceNet |
| A | ArmorPoint |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | |
| Torque Performance Mode | |
| Code | Description |
| V | Sensorless Vector Control and Volts per Hertz |
| e | |||||
| Output Current | |||||
| 200…240V | 380…480V | 500…600V | |||
| Code | Description | Code | Description | Code | Description |
| B2P3 | 2.3 A, 0.4 kW, 0.5 Hp | D1P4 | 1.4 A, 0.4 kW, 0.5 Hp | E1P7 | 1.7 A, 0.75 kW, 1.0 Hp |
| B5P0 | 5.0 A, 0.75 kW, 1.0 Hp | D2P3 | 2.3 A, 0.75 kW, 1.0 Hp | E3P0 | 3.0 A, 1.5 kW, 2.0 Hp |
| B7P6 | 7.6 A, 1.5 kW, 2.0 Hp | D4P0 | 4.0 A, 1.5 kW, 2.0 Hp | E4P2 | 4.2 A, 2.2 kW, 3.0 Hp |
| — | — | D6P0 | 6.0 A, 2.2 kW, 3.0 Hp | E6P6 | 6.6 A, 4.0 kW, 5.0 Hp |
| — | — | D7P6 | 7.6 A, 3.3 kW, 5.0 Hp | — | — |
| f | |
| Control Voltage | |
| Code | Description |
| Z | 24V DC |
| D | 120V AC |
| B | 240V AC |
| g | |
| Short Circuit Protection (Motor Circuit Protector) | |
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| h | ||||
| Control and 3-Phase Power Connections / Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | N | Conduit Entrance | Conduit Entrance | 3 m, shielded cordset male 90° |
| CR | W ⋆ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | N | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, shielded cordset male 90° |
| RR | W ⋆ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| i | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad with Jog Function |
| j | ||
| Option 2 | ||
| Code | Description | |
| CB | blank | Control Brake Contactor |
| CB | W ⋆ | No cable |
| DB | blank | DB Brake Connector |
| SB | blank | Source Brake Contactor |
| SB | W ⋆ | No cable |
| k | |
| Option 3 | |
| Code | Description |
| A10 | 0…10V Analog Input |
| EMI | EMI Filter |
| OC | Output Contactor |
| SM § ♣ | Safety Monitor |
⋆ See Accessories on Motor and Brake Cables for extended motor and brake cable lengths.
Not available with EtherNet/IP.
§ Not available with round media option (RR).
♣ The output contactor is included with the Safety Monitor option.
Product Selection
| Build a Catalog Number |
EtherNet/IP Network Communication
IP67/NEMA Type 4 with conduit entrance, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
| Cat. No. | ||||
| 380...480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284E-FVD1P4Z-10-CR |
| 0.75 | 1 | 2.3 | 284E-FVD2P3Z-10-CR | |
| 1.5 | 2 | 4 | 284E-FVD4P0Z-10-CR | |
| 2.2 | 3 | 6 | 284E-FVD6P0Z-25-CR | |
| 3 | 5 | 7.6 | 284E-FVD7P6Z-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 480V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
| Cat. No. | ||||
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284E-FVD1P4Z-10-RR |
| 0.75 | 1 | 2.3 | 284E-FVD2P3Z-10-RR | |
| 1.5 | 2 | 4 | 284E-FVD4P0Z-10-RR | |
| 2.2 | 3 | 6 | 284E-FVD6P0Z-25-RR | |
| 3 | 5 | 7.6 | 284E-FVD7P6Z-25-RR | |
DeviceNet Network Communication
IP67/NEMA Type 4 with conduit entrance, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200...240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FVB2P3Z-10-CR | 284D-FVB2P3D-10-CR | 284D-FVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284D-FVB5P0Z-10-CR | 284D-FVB5P0D-10-CR | 284D-FVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-FVB7P6Z-25-CR | 284D-FVB7P6D-25-CR | 284D-FVB7P6B-25-CR | |
| 380...480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FVD1P4Z-10-CR | 284D-FVD1P4D-10-CR | 284D-FVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-FVD2P3Z-10-CR | 284D-FVD2P3D-10-CR | 284D-FVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-FVD4P0Z-10-CR | 284D-FVD4P0D-10-CR | 284D-FVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-FVD6P0Z-25-CR | 284D-FVD6P0D-25-CR | 284D-FVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-FVD7P6Z-25-CR | 284D-FVD7P6D-25-CR | 284D-FVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-FVE1P7Z-10-CR | 284D-FVE1P7D-10-CR | 284D-FVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284D-FVE3P0Z-10-CR | 284D-FVE3P0D-10-CR | 284D-FVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284D-FVE4P2Z-10-CR | 284D-FVE4P2D-10-CR | 284D-FVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284D-FVE6P6Z-25-CR | 284D-FVE6P6D-25-CR | 284D-FVE6P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-FVB2P3Z-10-RR | 284D-FVB2P3D-10-RR | 284D-FVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284D-FVB5P0Z-10-RR | 284D-FVB5P0D-10-RR | 284D-FVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-FVB7P6Z-25-RR | 284D-FVB7P6D-25-RR | 284D-FVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-FVD1P4Z-10-RR | 284D-FVD1P4D-10-RR | 284D-FVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-FVD2P3Z-10-RR | 284D-FVD2P3D-10-RR | 284D-FVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-FVD4P0Z-10-RR | 284D-FVD4P0D-10-RR | 284D-FVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-FVD6P0Z-25-RR | 284D-FVD6P0D-25-RR | 284D-FVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-FVD7P6Z-25-RR | 284D-FVD7P6D-25-RR | 284D-FVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-FVE1P7Z-10-RR | 284D-FVE1P7D-10-RR | 284D-FVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284D-FVE3P0Z-10-RR | 284D-FVE3P0D-10-RR | 284D-FVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284D-FVE4P2Z-10-RR | 284D-FVE4P2D-10-RR | 284D-FVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284D-FVE6P6Z-25-RR | 284D-FVE6P6D-25-RR | 284D-FVE6P6B-25-RR | |
DeviceNet Network Communication, Continued
NEMA Type 4X with conduit entrance, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SVB2P3Z-10-CR | 284D-SVB2P3D-10-CR | 284D-SVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284D-SVB5P0Z-10-CR | 284D-SVB5P0D-10-CR | 284D-SVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284D-SVB7P6Z-25-CR | 284D-SVB7P6D-25-CR | 284D-SVB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SVD1P4Z-10-CR | 284D-SVD1P4D-10-CR | 284D-SVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284D-SVD2P3Z-10-CR | 284D-SVD2P3D-10-CR | 284D-SVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284D-SVD4P0Z-10-CR | 284D-SVD4P0D-10-CR | 284D-SVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284D-SVD6P0Z-25-CR | 284D-SVD6P0D-25-CR | 284D-SVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284D-SVD7P6Z-25-CR | 284D-SVD7P6D-25-CR | 284D-SVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-SVE1P7Z-10-CR | 284D-SVE1P7D-10-CR | 284D-SVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284D-SVE3P0Z-10-CR | 284D-SVE3P0D-10-CR | 284D-SVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284D-SVE4P2Z-10-CR | 284D-SVE4P2D-10-CR | 284D-SVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284D-SVE6P6Z-25-CR | 284D-SVE6P6D-25-CR | 284D-SVE6P6B-25-CR | |
NEMA Type 4X with quick disconnects for ArmorConnect power media, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284D-SVB2P3Z-10-RR | 284D-SVB2P3D-10-RR | 284D-SVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284D-SVB5P0Z-10-RR | 284D-SVB5P0D-10-RR | 284D-SVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284D-SVB7P6Z-25-RR | 284D-SVB7P6D-25-RR | 284D-SVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284D-SVD1P4Z-10-RR | 284D-SVD1P4D-10-RR | 284D-SVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284D-SVD2P3Z-10-RR | 284D-SVD2P3D-10-RR | 284D-SVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284D-SVD4P0Z-10-RR | 284D-SVD4P0D-10-RR | 284D-SVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284D-SVD6P0Z-25-RR | 284D-SVD6P0D-25-RR | 284D-SVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284D-SVD7P6Z-25-RR | 284D-SVD7P6D-25-RR | 284D-SVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284D-SVE1P7Z-10-RR | 284D-SVE1P7D-10-RR | 284D-SVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284D-SVE3P0Z-10-RR | 284D-SVE3P0D-10-RR | 284D-SVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284D-SVE4P2Z-10-RR | 284D-SVE4P2D-10-RR | 284D-SVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284D-SVE6P6Z-25-RR | 284D-SVE6P6D-25-RR | 284D-SVE6P6B-25-RR | |
ArmorPoint Bus Network Communication
IP67/NEMA Type 4 with conduit entrance, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FVB2P3Z-10-CR | 284A-FVB2P3D-10-CR | 284A-FVB2P3B-10-CR |
| 0.75 | 1 | 5 | 284A-FVB5P0Z-10-CR | 284A-FVB5P0D-10-CR | 284A-FVB5P0B-10-CR | |
| 1.5 | 2 | 7.6 | 284A-FVB7P6Z-25-CR | 284A-FVB7P6D-25-CR | 284A-FVB7P6B-25-CR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FVD1P4Z-10-CR | 284A-FVD1P4D-10-CR | 284A-FVD1P4B-10-CR |
| 0.75 | 1 | 2.3 | 284A-FVD2P3Z-10-CR | 284A-FVD2P3D-10-CR | 284A-FVD2P3B-10-CR | |
| 1.5 | 2 | 4 | 284A-FVD4P0Z-10-CR | 284A-FVD4P0D-10-CR | 284A-FVD4P0B-10-CR | |
| 2.2 | 3 | 6 | 284A-FVD6P0Z-25-CR | 284A-FVD6P0D-25-CR | 284A-FVD6P0B-25-CR | |
| 3 | 5 | 7.6 | 284A-FVD7P6Z-25-CR | 284A-FVD7P6D-25-CR | 284A-FVD7P6B-25-CR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284A-FVE1P7Z-10-CR | 284A-FVE1P7D-10-CR | 284A-FVE1P7B-10-CR |
| 1.5 | 2 | 3 | 284A-FVE3P0Z-10-CR | 284A-FVE3P0D-10-CR | 284A-FVE3P0B-10-CR | |
| 2.2 | 3 | 4.2 | 284A-FVE4P2Z-10-CR | 284A-FVE4P2D-10-CR | 284A-FVE4P2B-10-CR | |
| 4 | 5 | 6.1 | 284A-FVE6P6Z-25-CR | 284A-FVE6P6D-25-CR | 284A-FVE6P6B-25-CR | |
IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC
| Input Voltage | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
| Cat. No. | Cat. No. | Cat. No. | ||||
| 200…240V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 2.3 | 284A-FVB2P3Z-10-RR | 284A-FVB2P3D-10-RR | 284A-FVB2P3B-10-RR |
| 0.75 | 1 | 5 | 284A-FVB5P0Z-10-RR | 284A-FVB5P0D-10-RR | 284A-FVB5P0B-10-RR | |
| 1.5 | 2 | 7.6 | 284A-FVB7P6Z-25-RR | 284A-FVB7P6D-25-RR | 284A-FVB7P6B-25-RR | |
| 380…480V, 50/60 Hz 3-Phase |
0.4 | 0.5 | 1.4 | 284A-FVD1P4Z-10-RR | 284A-FVD1P4D-10-RR | 284A-FVD1P4B-10-RR |
| 0.75 | 1 | 2.3 | 284A-FVD2P3Z-10-RR | 284A-FVD2P3D-10-RR | 284A-FVD2P3B-10-RR | |
| 1.5 | 2 | 4 | 284A-FVD4P0Z-10-RR | 284A-FVD4P0D-10-RR | 284A-FVD4P0B-10-RR | |
| 2.2 | 3 | 6 | 284A-FVD6P0Z-25-RR | 284A-FVD6P0D-25-RR | 284A-FVD6P0B-25-RR | |
| 3 | 5 | 7.6 | 284A-FVD7P6Z-25-RR | 284A-FVD7P6D-25-RR | 284A-FVD7P6B-25-RR | |
| 460…600V, 50/60 Hz 3-Phase |
0.75 | 1 | 1.7 | 284A-FVE1P7Z-10-RR | 284A-FVE1P7D-10-RR | 284A-FVE1P7B-10-RR |
| 1.5 | 2 | 3 | 284A-FVE3P0Z-10-RR | 284A-FVE3P0D-10-RR | 284A-FVE3P0B-10-RR | |
| 2.2 | 3 | 4.2 | 284A-FVE4P2Z-10-RR | 284A-FVE4P2D-10-RR | 284A-FVE4P2B-10-RR | |
| 4 | 5 | 6.1 | 284A-FVE6P6Z-25-RR | 284A-FVE6P6D-25-RR | 284A-FVE6P6B-25-RR | |
Options — Factory Installed
Accessories
DeviceNet Media ∆
Industrial EtherNet Media∆
ArmorPoint® Media ♣
| Description | Length [m (ft)] | Cat. No. |
| ArmorPoint Bus Extension Cable including Terminating Resistor | 1 (3.3) | 280A-EXT1 |
| Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol | 1 (3.3) | 280A-EXTCABLE |
| ♣ ArmorPoint media is only available with an IP67/NEMA Type 4 rating. | ||
Sensor Media ♠
Motor and Brake Cables
Sealing Caps
|
|
| ArmorPoint | DeviceNet | EtherNet/IP | ||||
| Input | Output | Input | Output | Input | Output | |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Plastic Sealing Cap (M12)⋆ | — | 1485A-M12 | 1485A-M12 | 1485A-M12 | 1485A-M12 | 1485A-M12 |
| AC Micro Aluminum Sealing Cap⋆ | — | 889A-RMCAP | — | 889A-RMCAP | — | — |
| Stainless Steel Sealing Cap§ | — | 889AS-RMCAP | 1485AS-C3 | 889AS-RMCAP | — | — |
| Motor Connector Aluminum Sealing Cap (M22) for 10 A protection⋆ | — | 1485A-C1 | — | 1485A-C1 | — | 1485A-C1 |
| Motor Connector Aluminum Sealing Cap (M35) for 25 A protection⋆ | — | 889A-QMCAP | — | 889A-QMCAP | — | 889A-QMCAP |
| Dynamic Brake Connector (M22) | — | 1485A-C1 | — | 1485A-C1 | — | 1485A-C1 |
| Source/Control Brake Cap (M25) | — | ∆ | — | ∆ | — | ∆ |
| ⋆ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections. | ||||||
| § To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections. | ||||||
| ∆ Contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||
Handle and Cord Accessories
ArmorStart Bulletin 284 Option DB (IP20) Resistor Installation Dimensions
Dimensions are in millimeters (inches) and weights are in kilograms (pounds). Dimensions are not intended to be used for manufacturing purposes.
|
| Frame | Cat. No. | Weight [kg (lb)] |
| A | AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 | 1.1 (2.5) |
| B | AK-R2-030P1K2, AK-R2-120P1K2 | 2.7 (6) |
Recommended thermostat control wiring to prevent dynamic brake overheating
|
|
|
Peer-to-Peer Communications
|
(ZIP) Zone interlocking Parameters
The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP), which allow one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.
ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)
|
When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Cat. No. 280A-EXT1. The Cat. No. 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.
Note:Access to DeviceLogix programming is available with RSNetworx for DeviceNet.
|
If an additional ArmorStart Distributed Motor Controller is to be connected, the Cat. No. 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.
I/O Expansion with DeviceNet
If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Cat. No. 1738-ADNX ArmorPoint Distributed I/O product.
|
Bulletin 1738 ArmorPoint Distributed I/O Products
Digital Output Products
Digital Input Products
Analog Products
Power Supply Products
| Description | Cat. No. | |
|
|
ArmorPoint I/O Field Potential Distributor Module | 1738-FPD |
| 24V DC Expansion Power Supply | 1738-EP24DC | |
AC and Relay Products
Specialty Products
Adapter Products
Specifications
Connections
Bulletin 284E ArmorStart with EtherNet/IP Communications
|
Bulletin 284D ArmorStart with DeviceNet Communications
|
Bulletin 284A ArmorStart for the ArmorPoint Bus Backplane
|
⋆ Only available with SVC.
ArmorStart Receptacle Pin Outs
Receptacle Connections for 0…10V Analog Input (M22)
|
Pin 1: 10V DC Pin 2: 0…10V input Pin 3: Analog common Pin 4: Analog output Pin 5: NC (no connection) |
Receptacle Connections for ArmorPoint Interface (OUT)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: NC (no connection) |
Receptacle Connections for ArmorPoint Interface (IN)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: PE |
Receptacle Connections for DeviceNet Connector
|
Pin 1: Drain (no connection) Pin 2: +VDNET Pin 3: -VDNET Pin 4: CAN_H Pin 5: CAN_L |
Receptacle Connections for EtherNet/IP (M12)
|
Pin 1: Tx+ Pin 2: Rx+ Pin 3: Tx- Pin 4: Rx- |
Receptacle Connections for Input (M12)
|
Pin 1: +24V (A3 or DNET) Pin 2: Input 0 Pin 3: Common Pin 4: Input 1 Pin 5: NC (no connection) |
Receptacle Connections for Output, EtherNet/IP Version (M12)
|
Pin 1: NC (no connection) Pin 2: NC (no connection) Pin 3: Common Pin 4: Output +24V DC (A1) Pin 5: NC (no connection) |
Receptacle Connections for Output, DeviceNet or ArmorPoint Version (M12)
|
Pin 1: PE Pin 2: Return Pin 3: Relay out |
Receptacle Connections for Dynamic Brake (M22)
|
Pin 1: GND (green/yellow) Pin 2: BR+ (black) Pin 3: BR- (white) |
Receptacle Connections for Incoming Control Power (M22)
|
Pin 1: Unswitched (A3)(red) Pin 2: Common (A2)(black) Pin 3: PE (green) Pin 4: Not used (blank) Pin 5: Switched (A1)(blue) Pin 6: Not used (white) |
Receptacle Connections for Source or Control Brake (M25)
|
Pin 1: L1 (black) Pin 2: GND (green/yellow) Pin 3: L2 (white) |
Receptacle Connections for Motor Connector (M22)
|
Pin 1: T1 (black) Pin 2: T2 (white) Pin 3: T3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
10 A Short Circuit Protection (M22)
|
Pin 1: L1 (black) Pin 2: L2 (white) Pin 3: L3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
25 A Short Circuit Protection (M35)
|
Pin 1: L1 (black) Pin 2: Ground (green/yellow) Pin 3: L3 (red) Pin 4: L2 (white) |
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…500V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Rated Maximum Operating Current | 2.5 A | ||||||
| 5.5 A | |||||||
| 16 A | |||||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| 120V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Short Circuit Protection | SCPD Performance Type 1 | Current Rating | Voltage | 480Y/277V | 480Y/480V | 600Y/347V | 600V |
| 10 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 25 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications | ||||||
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 1000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X | IP69K | ||
| Approximate Shipping Weight | 13.6 kg (30 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Wire Size | Primary/Secondary terminal: (16 …10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | (18…10 AWG) | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Disconnect Lock Out | Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed 5/16 in. (8 mm) when closed, or damage will occur to disconnect guard. | ||
| EMC Emission Levels | Conducted Radio Frequency Emissions | 10V rms Communication cables 10V rms (PE) 150 kHz…80 MHz |
|
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | Electrostatic Discharge | 4 kV contact and 8 kV Air | |
| Radio Frequency Electromagnetic Field | 10V/m, 80 KHz…1 GHz 3V/m, 1.4 GHz…2.0 GHz 1V/m, 2.0 GHz…2.7 GHz |
||
| Fast Transient | 2 kV (Power) 2 kV (PE) 1 kV (Communications and control) |
||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Standards Compliance | UL 508C; CSA C22.2, No. 14; EN50178; EN61800-3; EN/IEC 60947-4-2; CE Marked per Low Voltage 2006/95/EC; EMC Directive 2004/108/EC; CCC; ODVA for EtherNet/IP; ODVA for DeviceNet | ||
| Certifications | cULus (File No. E207834, Guide NMMS, NMMS7) | ||
| ArmorPoint and DeviceNet Versions — Control and I/O Power Requirements | ||||||||||
| Units | No Options | Brake or Output Contactor | With Brake and Output Contactor | |||||||
| Control Voltage | Volts | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC |
| Total Control VA (Pick Up) |
VA (W) | (11 W) | 16 | 24 | (13 W) | 38 | 46 | (16 W) | 60 | 68 |
| Total Control VA (Hold In) |
VA (W) | (11 W) | 16 | 24 | (13 W) | 20 | 28 | (16 W) | 24 | 32 |
| External Devices powered by Control Voltage | ||||||||||
| Outputs (2) (1 A max. each) |
Amps | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Total Control VA (Pick Up) with max. outputs | VA (W) | (59 W) | 256 | 504 | (61 W) | 278 | 548 | (64 W) | 300 | 548 |
| Total Control VA (Hold In) with max. outputs | VA (W) | (59 W) | 256 | 504 | (61 W) | 261 | 512 | (64 W) | 264 | 512 |
| UL/NEMA | IEC | ||
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings Sourced from control circuit - A1/A2 |
Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | ||
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| DeviceNet Specifications | DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | |
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| DeviceNet Input Current | 364 mA @ 11V DC - 4.0 W | ||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | Baud Rates | 125, 250, 500 kbps | |
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| Distance Maximum | 200 m (656 ft) @ 250 kbps | ||
| Distance Maximum | 100 m (328 ft) @ 500 kbps | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| EtherNet/IP Version - Control and I/O Power Requirements | ||||
| Control Voltage | Units | A1/A2⋆ | A3/A2 | A3/A2§ |
| Volts | 24V DC | |||
| Current | Amps | 0.375 | 0.125 | 0.35 |
| Total Control Power (no options) | Watts | 9 | 3 | 8.4 |
| Total Control Power (with Dynamic Brake or Output Contactor option) | Watts | 12 | 3 | 8.4 |
| Total Control Power (with Dynamic Brake and Output Contactor option) | Watts | 15 | 3 | 8.4 |
| ⋆ Add power requirements for outputs (1 A max.) to A1/A2. | ||||
| Add power requirements for intputs (200 mA max.) to A3/A2. | ||||
| § If A1 power is disconnected. | ||||
| UL/NEMA | IEC | ||
| Input Ratings Sourced from control circuit - A3/A2 |
Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…26.4V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings Sourced from control circuit - A1/A2 |
Rated Operation Voltage | 26.4V DC | |
| Rate Insulation Voltage | 250V | ||
| Dielectric Withstand | 1500V AC (UL) | 2000V AC (IEC) | |
| Type of Control Circuit | Solid state sourcing output | ||
| Type of Current | 24V DC | ||
| Conventional Thermal Current Ith | 0.5 A each, 1 A max. combined | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| Load Types | Resistive or light inductive | ||
| Surge Suppression | Integrated diode, clamps @ 35V DC | ||
| Thermo-Protection | Integrated short circuit and over current protection | ||
| Maximum Cycle Rate | 30 operations/minute capacitive and inductive loads | ||
| Maximum Blocking Voltage | 35V DC | ||
| Maximum On-State Voltage @ Maximum Output | 1.5V DC | ||
| Maximum Off-State Leakage Current | 10 mA | ||
| Device Level Ring (DLR) | Beacon-based performance including IEEE 1588 end to end transparent clock | ||
| Maximum Nodes | 50 | ||
| Fault Recovery | Ring recovery time is less than 3 ms for a 50 node network | ||
| EtherNet Port | 2 D-coded, 4-pin female M12 connecters | ||
| Ports | Embedded switch with 2 ports | ||
| IP Address | DHCP enabled by default | ||
| DHCP Timeout | 30 seconds | ||
| Communication Rate | 10/100 Mbs with auto negotiate half duplex and full duplex | ||
| Data | |||
| Web Server | Embedded web server | ||
| Security | Login and password configurable | ||
| Support Simple Mail Transfer Protocol (SMTP) | |||
| Configuration | Status, diagnostics, and configuration tabs | ||
| Device Connections | Supports scheduled (Class 1) and unscheduled (Class 3 & UCMM) connections | ||
| 6 - Class 3 connections are supported simultaneously | |||
| Minimum of 1 - Class 1 or maximum of 2 - Class 1, CIP connections (1 exclusive owner, 1 input only and 1 listen only) are supported | |||
| Class 1 Connection API: 2…3200 ms Class 3 Connection API: 100…10 000 ms |
|||
| 20 ms Request Packet Interval (RPI) default | |||
| 3 concurrent Encapsulation sessions | |||
| TCP port supports 5 concurrent incoming connections | |||
| Drive Characteristics | Sensorless Vector Performance | Sensorless Vector Control |
| Maximum Hp (kW)/ Input Voltage |
2 Hp (1.5 kW)/230V AC 5 Hp (3.3 kW)/480V AC |
2 Hp (1.5 kW)/230V AC 5 Hp (3.3 kW)/480V AC, 5 Hp (4.0 kW)/600V AC |
| Overload Capacity | 150% for 60 seconds, 200% for 3 seconds | 150% for 60 seconds, 200% for 3 seconds |
| Output Frequency (programmable) | 0…400 Hz | 0…400 Hz |
| Efficiency (typical) | 97.5% | 97.5% |
| Preset Speeds | 4 | 8 |
| Carrier Frequency | 2…16 kHz | 2…16 kHz |
| Skip Frequency | — | ü |
| Process Control Loop | — | ü (PID) |
| StepLogic Functionality | — | ü |
| Timer/Counter Functions | — | ü |
| Drive Ratings — VFD Output Current vs. Input Current | |||||||
| Line Voltage | Frequency [Hz] | 3-Phase kW Rating | 3-Phase Hp Rating | Output Current [A] | Input Current [A] | ||
| Sensorless Vector Control | Sensorless Vector Performance | Sensorless Vector Control | Sensorless Vector Performance | ||||
| 200 | 50 | 0.4 | — | 2.3 | — | 3.65 | — |
| 0.75 | — | 4.5 | — | 6.40 | — | ||
| 1.5 | — | 7.6 | — | 10.65 | — | ||
| 230 | 60 | — | 0.5 | 2.3 | 2.3 | 3.10 | 2.5 |
| — | 1 | 4.5 | 4.5 | 5.70 | 5.2 | ||
| — | 2 | 7.6 | 7.6 | 9.45 | 9.5 | ||
| 380 | 50 | 0.4 | — | 1.4 | — | 2.15 | — |
| 0.75 | — | 2.3 | — | 3.80 | — | ||
| 1.5 | — | 4.0 | — | 6.40 | — | ||
| 2.2 | — | 6.0 | — | 9.00 | — | ||
| 3.0 | — | 7.6 | — | 12.40 | — | ||
| 460 | 60 | — | 0.5 | 1.4 | 1.4 | 1.85 | 1.8 |
| — | 1 | 2.3 | 2.3 | 3.45 | 3.2 | ||
| — | 2 | 4.0 | 4.0 | 5.57 | 5.7 | ||
| — | 3 | 6.0 | 6.0 | 8.20 | 7.5 | ||
| — | 5 | 7.6 | 7.6 | 12.5 | 8.6 | ||
| 575 | 60 | — | 1 | 1.7 | — | 2.78 | — |
| — | 2 | 3.0 | — | 4.73 | — | ||
| — | 3 | 4.2 | — | 6.64 | — | ||
| — | 5 | 6.6 | — | 10.75 | — | ||
| Protective Specifications — Sensorless Vector Performance | |
| Motor Protection | I2t overload protection — 150% for 60 seconds, 200% for 3 seconds (provides Class 10 protection) |
| Overcurrent | 200% hardware limit, 300% instantaneous fault |
| Over Voltage | 200…240V AC Input — Trip occurs @ 405V DC bus voltage (equivalent to 290V AC incoming line) 380…460V AC Input — Trip occurs @ 810V DC bus voltage (equivalent to 575V AC incoming line) |
| Under Voltage | 200…240V AC Input — Trip occurs @ 210V DC bus voltage (equivalent to 150V AC incoming line) 380…480V AC Input — Trip occurs @ 390V DC bus voltage (equivalent to 275V AC incoming line) |
| Faultless Power Ride Through | 100 milliseconds |
| Control Specifications — Sensorless Vector Performance | |
| Carrier Frequency | 2…16 kHz drive rating based on 4 kHz |
| Frequency Accuracy — Digital Input | within ±0.05% of set output frequency |
| Speed Regulation (open loop with slip compensation) | ±2% of base speed across a 40:1 speed range |
| Stop Modes | Multiple programmable stop modes including: Ramp, Coast, DC-Brake, Ramp-to-Hold, and S Curve |
| Acceleration/Deceleration | Two independently programmable acceleration and deceleration times: each time may be programmed from 0…600 seconds in 0.1 second increments |
| Intermittent Overload | 150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds |
| Electronic Motor Overload Protection | Class 10 protection with speed sensitive response and power-down overload retention function |
| Sensorless Vector Performance (SVP) Minimum DB Resistance | |||
| Input Voltage | Drive Rating [kW] | Drive Rating [Hp] | Minimum DB Resistance [W] |
| 200…240V, 50/60 Hz, Three-Phase |
0.2 | 0.25 | 60 |
| 0.4 | 0.5 | 60 | |
| 0.75 | 1 | 60 | |
| 1.5 | 2 | 60 | |
| 480V, 50/60 Hz, Three-Phase |
0.4 | 0.5 | 121 |
| 0.75 | 1 | 121 | |
| 1.5 | 2 | 121 | |
| 2.2 | 3 | 97 | |
| 3.7 | 5 | 97 | |
| Protective Specifications — Sensorless Vector Control | |
| Motor Protection | I2t overload protection — 150% for 60 seconds, 200% for 3 seconds (provides Class 10 protection) |
| Overcurrent | 200% hardware limit, 300% instantaneous fault |
| Over Voltage | 200…240V AC Input Trip occurs @ 405V DC bus voltage (equivalent to 290V AC incoming line) 380…460V AC Input Trip occurs @ 810V DC bus voltage (equivalent to 575V AC incoming line) 460…600V AC Input Trip occurs @ 1005V DC bus voltage (equivalent to 711V AC incoming line) |
| Under Voltage | 200…240V AC Input Trip occurs @ 210V DC bus voltage (equivalent to 150V AC incoming line) 380…480V AC Input Trip occurs @ 390V DC bus voltage (equivalent to 275V AC incoming line) 460…600V AC Input If 600V rated trip occurs @ 487V DC bus voltage (344V AC incoming line); If 480V rated trip occurs @ 390V DC bus voltage (275V AC incoming line) |
| Faultless Power Ride Through | 100 milliseconds |
| Control Specifications — Sensorless Vector Control | |
| Carrier Frequency | 2…16 kHz drive rating based on 4 kHz |
| Frequency Accuracy — Digital Input | within ±0.05% of set output frequency |
| Speed Regulation (open loop with slip compensation) | ±1% of base speed across a 60:1 speed range |
| Stop Modes | Multiple programmable stop modes including: Ramp, Coast, DC-Brake, Ramp-to-Hold, and S Curve |
| Acceleration/Deceleration | Two independently programmable acceleration and deceleration times: each time may be programmed from 0…600 seconds in 0.1 second increments |
| Intermittent Overload | 150% overload capability for up to 1 minute, 200% overload capability for up to 3 seconds |
| Electronic Motor Overload Protection | Class 10 protection with speed sensitive response |
| Sensorless Vector Control (SVC) Minimum DB Resistance | |||
| Drive Rating | Minimum DB Resistance | ||
| Input Voltage | [kW] | [Hp] | [W] |
| 240V, 50/60 Hz, Three-Phase |
0.4 | 0.5 | 48 |
| 0.75 | 1 | 48 | |
| 1.5 | 2 | 48 | |
| 480V, 50/60 Hz, Three-Phase |
0.4 | 0.5 | 97 |
| 0.75 | 1 | 97 | |
| 1.5 | 2 | 97 | |
| 2.2 | 3 | 97 | |
| 4.0 | 5 | 77 | |
| 600V, 50/60 Hz, Three-Phase |
0.75 | 1 | 120 |
| 1.5 | 2 | 120 | |
| 2.2 | 3 | 82 | |
| 4.0 | 5 | 82 | |
Motor Overload Trip Curves
Motor overload current parameter provides class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
|
Approximate Dimensions
Dimensions for IP67/NEMA Type 4 with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for IP67/NEMA Type 4 with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with ArmorConnect Connectivity (1 Hp or less @ 230V AC and 2 Hp or less @ 480…575V AC)
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with ArmorConnect Connectivity (2 Hp or greater @ 230V AC and 3 Hp or greater @ 480…575V AC)
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|