Bulletin 284 ArmorStart Distributed Motor Controller

Product Overview


Click to enlarge - 280_Armorstart_VFD_1hp_4c


Bulletin 284 ArmorStart Distributed Motor Controller


Standards Compliance and Certifications

Standards Compliance

UL 508C
CSA C22.2, No. 14
EN/IEC 60947-1, EN 50178, EN 61800-3
CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC


Certifications

cULus (File No. E207834, Guide NMMS, NMMS7)

Description

The Bulletin 284 ArmorStart Distributed Motor Controller is an integrated, pre-engineered starter for variable frequency AC drive applications. The ArmorStart offers a robust IP67/NEMA Type 4 enclosure design, which is suitable for water wash-down environments. The ArmorStart products are also offered with NEMA Type 4X rating, suitable for environment wash down with caustic chemicals used in the food and beverage industry. The wash-down rating is 1000 psi for the NEMA Type 4X rated devices. The modular plug-and-play design offers simplicity in wiring the installation. The quick disconnects for the I/O, communication, and motor connection reduce the wiring time and eliminate wiring errors. The ArmorStart offers, as standard, four DC inputs and two relay outputs to be used with sensors and actuators respectively, for monitoring and controlling the application process. The ArmorStart’s LED status indication and built-in diagnostics capabilities allows ease of maintenance and troubleshooting. The optional Hand/Off/Auto (HOA) keypad allows for local start/stop control at the ArmorStart Distributed Motor Controller.

The Bulletin 284 ArmorStart Distributed Motor Controller offers short circuit protection per UL 508C and IEC 60947-1. The ArmorStart is rated for local-disconnect service by incorporating the Bulletin 140 Motor Protector as the local-disconnect, eliminating the need for additional components. The ArmorStart Distributed Motor Controllers are suitable for group motor installations.


Mode of Operation

Volts per Hertz (Sensorless Vector Performance)

This method provides excellent speed regulation and high levels of torque across the entire speed range of the drive, and improved speed regulation even as loading increases. Basic control yields the most cost effective performance when sensorless vector control is not required.

Click to enlarge - pf4_hs_graph
ArmorStart with Sensorless Vector Performance — 3 Hp, High Speed


Additional Features


Sensorless Vector Control (SVC)

Sensorless vector control provides exceptional speed regulation and very high levels of torque across the entire speed range of the drive.

Click to enlarge - pf40_hs_graph
ArmorStart with Sensorless Vector Control — 3 Hp, High Speed


Additional Features


Description of Features

Overload Protection

The Bulletin 284 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStart’s overload protection is programmable via the communication network providing the user with flexibility. The overload trip class allows for class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.

Gland Plate Entrance

The ArmorStart product offers two different methods for connecting incoming three-phase and control power to the device. One method offered is the traditional conduit entrance which provides a 3/4 and 1 in. conduit hole opening for wiring three-phase and control power. The second method offers connectivity to the ArmorConnect power media. Factory installed receptacles are provided for connectivity to both three-phase and control power media.

Motor Cable

With every Bulletin 284 ArmorStart Distributed Motor Controller, a 3–meter unshielded 4-conductor cordset is provided with each unit as standard. If the optional EMI filter is selected, a 3–meter shielded 4-conductor cordset is provided with each unit as standard.

LED Status Indication

The LED Status Indication provides four status LEDs and a Reset button. The LEDs provide status indication for the following:


Inputs

The inputs are single keyed (two inputs per connector), which are sourced from DeviceNet power (24V DC), with LED status indication.

Outputs

Two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power, which can be either, 24V DC, 120V AC, or 240V AC with LED status indication.

Fault Diagnostics

Fault diagnostics capabilities built into the Bulletin 284 ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.



Network and Expandable I/O Capabilities

The Bulletin 284D ArmorStart Distributed Motor Controller delivers enhanced control to access parameter settings and provides fault diagnostics, and remote start/stop control. DeviceNet is the communication protocol, provided with the ArmorStart including DeviceLogix.

The Bulletin 284A ArmorStart Distributed Motor Controller allows connectivity to the ArmorPoint backplane. The ArmorPoint I/O system can communicate using DeviceNet, ControlNet, or EtherNet communication protocols. In addition to the different network protocols, the ArmorPoint Distributed I/O products allow the I/O capability to be expanded beyond the standard two outputs. The two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power of 24V DC, 120V AC, or 240V AC. LED status indication is also provided, as standard with ArmorPoint. When using the ArmorPoint, a maximum of two ArmorPoint Distributed Motor Controllers can be connected to the ArmorPoint Distributed I/O product.


Factory Installed Options

HOA Selector Keypad with Jog Function

The HOA Selector Keypad with Jog Function allows for local start/stop control with capabilities to JOG and to Forward/Reverse motor direction.

EMI Filter

The EMI Filter option is required if the Bulletin 284 ArmorStart Distributed Motor requires to be CE compliant. If the EMI Filter is selected, a 3–meter shielded 4–conductor cordset is provided as standard. This option is only available with sensorless vector control.

Dynamic Brake Connector

A 3-meter, 3-pin cable for connection to a dynamic brake module is provided as standard when this option is selected. See Accessories on Dynamic Brake Modules ª  for available dynamic brake modules.

Control Brake Contactor

An internal contactor is used to switch the electromechanical motor brake On/Off. The motor brake is powered from the control voltage circuit. A customer accessible 3.0 A fuse is provided to protect the brake cable. One 3-meter 3-pin cable for connection to the motor brake is provided as standard when this option is selected.

Source Brake Contactor

An internal contactor is used to switch the electromechanical motor brake on/off. The motor brake is powered from the main power circuit. A customer accessible 3.0 A fuse is provided to protect the brake cable. A 3-meter, 3-pin cable for connection to the motor, is provided as standard when this option is selected.

Output Contactor

An internal contactor will be sourced from control voltage to isolate the load side of the Bulletin 284 ArmorStart Distributed Motor Controller. When control power is applied the output contactor is closed and when control power is removed the output contactor opens. There is no switching element such as a relay in the system. If control power is lost then the output contactor will open since its coil power is lost. A sequenced stop involving the output contact cannot be performed.

Shielded Motor Cable

A 3-meter shielded 4-conductor cordset is provided instead of the 3-meter unshielded 4-conductor cordset. If the EMI Filter is selected, a 3-meter shielded 4-conductor cordset is provided as standard.

Safety Monitor

The Safety Monitor Option allows for independent monitoring of the output status of the device. The function is implemented using a normally closed contact which complies with IEC 60947-5-1 for mechanically linked contacts. Two terminal blocks are provided as the inputs which maybe used with an external safety circuit. The external safety circuit monitors the status of the output contactor.

0…10V Analog Input

The Bulletin 284 Distributed Motor Controller with Sensorless Vector Control provides a 0…10V analog input. The 0…10V Analog Input, 15 A, factory-installed option provides a 0…10V external frequency command from the 0…10V or +/-10V analog input or remote potentiometer. A 5-pin micro receptacle is provided for connectivity for customer connection. A shielded 5-conductor cordset or patch cord is recommended.

Cat. No. Explanation

284   D F   H   D2P3   D 10 CR Option 1 Option 2 Option 3
a    b    c    d    e    f    g    h    i    j    k

a
Bulletin Number
Code Description
284 VFD Starter

b
Communications
Code Description
D DeviceNet™
A ArmorPoint

c
Enclosure Type
Code Description
F Type 4 (IP67)
S Type 4X

d
Torque Performance Mode
Code Description
H Volts per Hertz (Sensorless Vector Performance)

e
Output Current
200…240V 380…480V
Code Description Code Description
B2P3 2.3 A, 0.4 kW, 0.5 Hp D1P4 1.4 A, 0.4 kW, 0.5 Hp
B4P5 4.5 A, 0.75 kW, 1.0 Hp D2P3 2.3 A, 0.75 kW, 1.0 Hp
B7P6 7.6 A, 1.5 kW, 2.0 Hp D4P0 4.0 A, 1.5 kW, 2.0 Hp
D6P0 6.0 A, 2.2 kW, 3.0 Hp
D7P6 7.6 A, 3.3 kW, 5.0 Hp

f
Control Voltage
Code Description
Z 24V DC
D 120V AC
B 240V AC

g
Short Circuit Protection
(Motor Circuit Protector)
Code Description
10 10 A Rated Device
25 25 A Rated Device

h
Control and 3-Phase Power Connections / Motor Cable Connection
(CR: Conduit/Round Media) or (RR: Round/Round Media)

Code
Description
Control Power 3-Phase Power Motor Cable
CR blank Conduit Entrance Conduit Entrance 3 m, unshielded cordset male 90°
CR N Conduit Entrance Conduit Entrance 3 m, shielded cordset male 90°
CR W ¬  Conduit Entrance Conduit Entrance No cable
RR blank Round Media (Male Receptacle) Round Media (Male Receptacle) 3 m, unshielded cordset male 90°
RR N Round Media (Male Receptacle) Round Media (Male Receptacle) 3 m, shielded cordset male 90°
RR W ¬  Round Media (Male Receptacle) Round Media (Male Receptacle) No cable

i
Option 1
Code Description
3 Hand/Off/Auto Selector Keypad with Jog Function

j
Option 2
Code Description
CB blank Control Brake Contactor
CB W ¬  No cable
DB blank DB Brake Connector
SB blank Source Brake Contactor
SB W ¬  No cable

k
Option 3
Code Description
OC Output Contactor
SM T  Safety Monitor

¬ See Accessories on Cables for extended motor and brake cable lengths.
T The output contactor is included with the Safety Monitor option.


Product Selection

Build a Catalog Number


IP67/NEMA Type 4 with conduit entrance, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200...240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-FHB2P3Z-10-CR 284D-FHB2P3D-10-CR 284D-FHB2P3B-10-CR
0.75 1 4.5 284D-FHB4P5Z-10-CR 284D-FHB4P5D-10-CR 284D-FHB4P5B-10-CR
1.5 2 7.6 284D-FHB7P6Z-25-CR 284D-FHB7P6D-25-CR 284D-FHB7P6B-25-CR
380...480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-FHD1P4Z-10-CR 284D-FHD1P4D-10-CR 284D-FHD1P4B-10-CR
0.75 1 2.3 284D-FHD2P3Z-10-CR 284D-FHD2P3D-10-CR 284D-FHD2P3B-10-CR
1.5 2 4 284D-FHD4P0Z-10-CR 284D-FHD4P0D-10-CR 284D-FHD4P0B-10-CR
2.2 3 6 284D-FHD6P0Z-25-CR 284D-FHD6P0D-25-CR 284D-FHD6P0B-25-CR
3 5 7.6 284D-FHD7P6Z-25-CR 284D-FHD7P6D-25-CR 284D-FHD7P6B-25-CR
  

IP67/NEMA Type 4 with conduit entrance, ArmorPoint communications, and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284A-FHB2P3Z-10-CR 284A-FHB2P3D-10-CR 284A-FHB2P3B-10-CR
0.75 1 5 284A-FHB4P5Z-10-CR 284A-FHB4P5D-10-CR 284A-FHB4P5B-10-CR
1.5 2 7.6 284A-FHB7P6Z-25-CR 284A-FHB7P6D-25-CR 284A-FHB7P6B-25-CR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284A-FHD1P4Z-10-CR 284A-FHD1P4D-10-CR 284A-FHD1P4B-10-CR
0.75 1 2.3 284A-FHD2P3Z-10-CR 284A-FHD2P3D-10-CR 284A-FHD2P3B-10-CR
1.5 2 4 284A-FHD4P0Z-10-CR 284A-FHD4P0D-10-CR 284A-FHD4P0B-10-CR
2.2 3 6 284A-FHD6P0Z-25-CR 284A-FHD6P0D-25-CR 284A-FHD6P0B-25-CR
3 5 7.6 284A-FHD7P6Z-25-CR 284A-FHD7P6D-25-CR 284A-FHD7P6B-25-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-FHB2P3Z-10-RR 284D-FHB2P3D-10-RR 284D-FHB2P3B-10-RR
0.75 1 4.5 284D-FHB4P5Z-10-RR 284D-FHB4P5D-10-RR 284D-FHB4P5B-10-RR
1.5 2 7.6 284D-FHB7P6Z-25-RR 284D-FHB7P6D-25-RR 284D-FHB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-FHD1P4Z-10-RR 284D-FHD1P4D-10-RR 284D-FHD1P4B-10-RR
0.75 1 2.3 284D-FHD2P3Z-10-RR 284D-FHD2P3D-10-RR 284D-FHD2P3B-10-RR
1.5 2 4 284D-FHD4P0Z-10-RR 284D-FHD4P0D-10-RR 284D-FHD4P0B-10-RR
2.2 3 6 284D-FHD6P0Z-25-RR 284D-FHD6P0D-25-RR 284D-FHD6P0B-25-RR
3 5 7.6 284D-FHD7P6Z-25-RR 284D-FHD7P6D-25-RR 284D-FHD7P6B-25-RR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, ArmorPoint communications, and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284A-FHB2P3Z-10-RR 284A-FHB2P3D-10-RR 284A-FHB2P3B-10-RR
0.75 1 4.5 284A-FHB4P5Z-10-RR 284A-FHB4P5D-10-RR 284A-FHB4P5B-10-RR
1.5 2 7.6 284A-FHB7P6Z-25-RR 284A-FHB7P6D-25-RR 284A-FHB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284A-FHD1P4Z-10-RR 284A-FHD1P4D-10-RR 284A-FHD1P4B-10-RR
0.75 1 2.3 284A-FHD2P3Z-10-RR 284A-FHD2P3D-10-RR 284A-FHD2P3B-10-RR
1.5 2 4 284A-FHD4P0Z-10-RR 284A-FHD4P0D-10-RR 284A-FHD4P0B-10-RR
2.2 3 6 284A-FHD6P0Z-25-RR 284A-FHD6P0D-25-RR 284A-FHD6P0B-25-RR
3 5 7.6 284A-FHD7P6Z-25-RR 284A-FHD7P6D-25-RR 284A-FHD7P6B-25-RR
  

NEMA Type 4X with conduit entrance, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-SHB2P3Z-10-CR 284D-SHB2P3D-10-CR 284D-SHB2P3B-10-CR
0.75 1 4.5 284D-SHB4P5Z-10-CR 284D-SHB4P5D-10-CR 284D-SHB4P5B-10-CR
1.5 2 7.6 284D-SHB7P6Z-25-CR 284D-SHB7P6D-25-CR 284D-SHB7P6B-25-CR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-SHD1P4Z-10-CR 284D-SHD1P4D-10-CR 284D-SHD1P4B-10-CR
0.75 1 2.3 284D-SHD2P3Z-10-CR 284D-SHD2P3D-10-CR 284D-SHD2P3B-10-CR
1.5 2 4 284D-SHD4P0Z-10-CR 284D-SHD4P0D-10-CR 284D-SHD4P0B-10-CR
2.2 3 6 284D-SHD6P0Z-25-CR 284D-SHD6P0D-25-CR 284D-SHD6P0B-25-CR
3 5 7.6 284D-SHD7P6Z-25-CR 284D-SHD7P6D-25-CR 284D-SHD7P6B-25-CR
  

NEMA Type 4X with quick disconnects for ArmorConnect power media, DeviceNet communications and Volts per Hertz torque performance, Up to 480V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-SHB2P3Z-10-RR 284D-SHB2P3D-10-RR 284D-SHB2P3B-10-RR
0.75 1 4.5 284D-SHB4P5Z-10-RR 284D-SHB4P5D-10-RR 284D-SHB4P5B-10-RR
1.5 2 7.6 284D-SHB7P6Z-25-RR 284D-SHB7P6D-25-RR 284D-SHB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-SHD1P4Z-10-RR 284D-SHD1P4D-10-RR 284D-SHD1P4B-10-RR
0.75 1 2.3 284D-SHD2P3Z-10-RR 284D-SHD2P3D-10-RR 284D-SHD2P3B-10-RR
1.5 2 4 284D-SHD4P0Z-10-RR 284D-SHD4P0D-10-RR 284D-SHD4P0B-10-RR
2.2 3 6 284D-SHD6P0Z-25-RR 284D-SHD6P0D-25-RR 284D-SHD6P0B-25-RR
3 5 7.6 284D-SHD7P6Z-25-RR 284D-SHD7P6D-25-RR 284D-SHD7P6B-25-RR
  

Cat. No. Explanation

284 D F V D2P3 D 10 CR Option 1 Option 2 Option 3
a b    c d e f    g    h    i    j    k

a
Bulletin Number
Code Description
284 UFD Starter

b
Communications
Code Description
D DeviceNet™
A ArmorPoint

c
Enclosure Type
Code Description
F Type 4 (IP67)
S Type 4X

d
Torque Performance Mode
Code Description
V Sensorless Vector Control and Volts per Hertz

e
Output Current
200…240V 380…480V 500…600V
Code Description Code Description Code Description
B2P3 2.3 A, 0.4 kW, 0.5 Hp D1P4 1.4 A, 0.4 kW, 0.5 Hp E1P7 1.7 A, 0.75 kW, 1.0 Hp
B5P0 5.0 A, 0.75 kW, 1.0 Hp D2P3 2.3 A, 0.75 kW, 1.0 Hp E3P0 3.0 A, 1.5 kW, 2.0 Hp
B7P6 7.6 A, 1.5 kW, 2.0 Hp D4P0 4.0 A, 1.5 kW, 2.0 Hp E4P2 4.2 A, 2.2 kW, 3.0 Hp
D6P0 6.0 A, 2.2 kW, 3.0 Hp E6P6 6.6 A, 4.0 kW, 5.0 Hp
D7P6 7.6 A, 3.3 kW, 5.0 Hp

f
Control Voltage
Code Description
Z 24V DC
D 120V AC
B 240V AC

g
Short Circuit Protection (Motor Circuit Protector)
Code Description
10 10 A Rated Device
25 25 A Rated Device

h
Control and 3-Phase Power Connections / Motor Cable Connection
(CR: Conduit/Round Media) or (RR: Round/Round Media)

Code
Description
Control Power 3-Phase Power Motor Cable
CR blank Conduit Entrance Conduit Entrance 3 m, unshielded cordset male 90°
CR N Conduit Entrance Conduit Entrance 3 m, shielded cordset male 90°
CR W ¬  Conduit Entrance Conduit Entrance No cable
RR blank Round Media (Male Receptacle) Round Media (Male Receptacle) 3 m, unshielded cordset male 90°
RR N Round Media (Male Receptacle) Round Media (Male Receptacle) 3 m, shielded cordset male 90°
RR W ¬  Round Media (Male Receptacle) Round Media (Male Receptacle) No cable

i
Option 1
Code Description
3 Hand/Off/Auto Selector Keypad with Jog Function

j
Option 2
Code Description
CB blank Control Brake Contactor
CB W ¬  No cable
DB blank DB Brake Connector
SB blank Source Brake Contactor
SB W ¬  No cable

k
Option 3
Code Description
EMI EMI Filter
OC Output Contactor

¬ See Accessories on Cables for extended motor and brake cable lengths.
T The output contactor is included with the Safety Monitor option.


Product Selection

Build a Catalog Number


IP67/NEMA Type 4 with conduit entrance, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200...240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-FVB2P3Z-10-CR 284D-FVB2P3D-10-CR 284D-FVB2P3B-10-CR
0.75 1 5 284D-FVB5P0Z-10-CR 284D-FVB5P0D-10-CR 284D-FVB5P0B-10-CR
1.5 2 7.6 284D-FVB7P6Z-25-CR 284D-FVB7P6D-25-CR 284D-FVB7P6B-25-CR
380...480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-FVD1P4Z-10-CR 284D-FVD1P4D-10-CR 284D-FVD1P4B-10-CR
0.75 1 2.3 284D-FVD2P3Z-10-CR 284D-FVD2P3D-10-CR 284D-FVD2P3B-10-CR
1.5 2 4 284D-FVD4P0Z-10-CR 284D-FVD4P0D-10-CR 284D-FVD4P0B-10-CR
2.2 3 6 284D-FVD6P0Z-25-CR 284D-FVD6P0D-25-CR 284D-FVD6P0B-25-CR
3 5 7.6 284D-FVD7P6Z-25-CR 284D-FVD7P6D-25-CR 284D-FVD7P6B-25-CR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284D-FVE1P7Z-10-CR 284D-FVE1P7D-10-CR 284D-FVE1P7B-10-CR
1.5 2 3 284D-FVE3P0Z-10-CR 284D-FVE3P0D-10-CR 284D-FVE3P0B-10-CR
2.2 3 4.2 284D-FVE4P2Z-10-CR 284D-FVE4P2D-10-CR 284D-FVE4P2B-10-CR
4 5 6.1 284D-FVE6P6Z-25-CR 284D-FVE6P6D-25-CR 284D-FVE6P6B-25-CR
  

IP67/NEMA Type 4 with conduit entrance, ArmorPoint communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284A-FVB2P3Z-10-CR 284A-FVB2P3D-10-CR 284A-FVB2P3B-10-CR
0.75 1 5 284A-FVB5P0Z-10-CR 284A-FVB5P0D-10-CR 284A-FVB5P0B-10-CR
1.5 2 7.6 284A-FVB7P6Z-25-CR 284A-FVB7P6D-25-CR 284A-FVB7P6B-25-CR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284A-FVD1P4Z-10-CR 284A-FVD1P4D-10-CR 284A-FVD1P4B-10-CR
0.75 1 2.3 284A-FVD2P3Z-10-CR 284A-FVD2P3D-10-CR 284A-FVD2P3B-10-CR
1.5 2 4 284A-FVD4P0Z-10-CR 284A-FVD4P0D-10-CR 284A-FVD4P0B-10-CR
2.2 3 6 284A-FVD6P0Z-25-CR 284A-FVD6P0D-25-CR 284A-FVD6P0B-25-CR
3 5 7.6 284A-FVD7P6Z-25-CR 284A-FVD7P6D-25-CR 284A-FVD7P6B-25-CR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284A-FVE1P7Z-10-CR 284A-FVE1P7D-10-CR 284A-FVE1P7B-10-CR
1.5 2 3 284A-FVE3P0Z-10-CR 284A-FVE3P0D-10-CR 284A-FVE3P0B-10-CR
2.2 3 4.2 284A-FVE4P2Z-10-CR 284A-FVE4P2D-10-CR 284A-FVE4P2B-10-CR
4 5 6.1 284A-FVE6P6Z-25-CR 284A-FVE6P6D-25-CR 284A-FVE6P6B-25-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-FVB2P3Z-10-RR 284D-FVB2P3D-10-RR 284D-FVB2P3B-10-RR
0.75 1 5 284D-FVB5P0Z-10-RR 284D-FVB5P0D-10-RR 284D-FVB5P0B-10-RR
1.5 2 7.6 284D-FVB7P6Z-25-RR 284D-FVB7P6D-25-RR 284D-FVB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-FVD1P4Z-10-RR 284D-FVD1P4D-10-RR 284D-FVD1P4B-10-RR
0.75 1 2.3 284D-FVD2P3Z-10-RR 284D-FVD2P3D-10-RR 284D-FVD2P3B-10-RR
1.5 2 4 284D-FVD4P0Z-10-RR 284D-FVD4P0D-10-RR 284D-FVD4P0B-10-RR
2.2 3 6 284D-FVD6P0Z-25-RR 284D-FVD6P0D-25-RR 284D-FVD6P0B-25-RR
3 5 7.6 284D-FVD7P6Z-25-RR 284D-FVD7P6D-25-RR 284D-FVD7P6B-25-RR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284D-FVE1P7Z-10-RR 284D-FVE1P7D-10-RR 284D-FVE1P7B-10-RR
1.5 2 3 284D-FVE3P0Z-10-RR 284D-FVE3P0D-10-RR 284D-FVE3P0B-10-RR
2.2 3 4.2 284D-FVE4P2Z-10-RR 284D-FVE4P2D-10-RR 284D-FVE4P2B-10-RR
4 5 6.1 284D-FVE6P6Z-25-RR 284D-FVE6P6D-25-RR 284D-FVE6P6B-25-RR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, ArmorPoint communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284A-FVB2P3Z-10-RR 284A-FVB2P3D-10-RR 284A-FVB2P3B-10-RR
0.75 1 5 284A-FVB5P0Z-10-RR 284A-FVB5P0D-10-RR 284A-FVB5P0B-10-RR
1.5 2 7.6 284A-FVB7P6Z-25-RR 284A-FVB7P6D-25-RR 284A-FVB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284A-FVD1P4Z-10-RR 284A-FVD1P4D-10-RR 284A-FVD1P4B-10-RR
0.75 1 2.3 284A-FVD2P3Z-10-RR 284A-FVD2P3D-10-RR 284A-FVD2P3B-10-RR
1.5 2 4 284A-FVD4P0Z-10-RR 284A-FVD4P0D-10-RR 284A-FVD4P0B-10-RR
2.2 3 6 284A-FVD6P0Z-25-RR 284A-FVD6P0D-25-RR 284A-FVD6P0B-25-RR
3 5 7.6 284A-FVD7P6Z-25-RR 284A-FVD7P6D-25-RR 284A-FVD7P6B-25-RR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284A-FVE1P7Z-10-RR 284A-FVE1P7D-10-RR 284A-FVE1P7B-10-RR
1.5 2 3 284A-FVE3P0Z-10-RR 284A-FVE3P0D-10-RR 284A-FVE3P0B-10-RR
2.2 3 4.2 284A-FVE4P2Z-10-RR 284A-FVE4P2D-10-RR 284A-FVE4P2B-10-RR
4 5 6.1 284A-FVE6P6Z-25-RR 284A-FVE6P6D-25-RR 284A-FVE6P6B-25-RR
  

NEMA Type 4X with conduit entrance, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-SVB2P3Z-10-CR 284D-SVB2P3D-10-CR 284D-SVB2P3B-10-CR
0.75 1 5 284D-SVB5P0Z-10-CR 284D-SVB5P0D-10-CR 284D-SVB5P0B-10-CR
1.5 2 7.6 284D-SVB7P6Z-25-CR 284D-SVB7P6D-25-CR 284D-SVB7P6B-25-CR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-SVD1P4Z-10-CR 284D-SVD1P4D-10-CR 284D-SVD1P4B-10-CR
0.75 1 2.3 284D-SVD2P3Z-10-CR 284D-SVD2P3D-10-CR 284D-SVD2P3B-10-CR
1.5 2 4 284D-SVD4P0Z-10-CR 284D-SVD4P0D-10-CR 284D-SVD4P0B-10-CR
2.2 3 6 284D-SVD6P0Z-25-CR 284D-SVD6P0D-25-CR 284D-SVD6P0B-25-CR
3 5 7.6 284D-SVD7P6Z-25-CR 284D-SVD7P6D-25-CR 284D-SVD7P6B-25-CR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284D-SVE1P7Z-10-CR 284D-SVE1P7D-10-CR 284D-SVE1P7B-10-CR
1.5 2 3 284D-SVE3P0Z-10-CR 284D-SVE3P0D-10-CR 284D-SVE3P0B-10-CR
2.2 3 4.2 284D-SVE4P2Z-10-CR 284D-SVE4P2D-10-CR 284D-SVE4P2B-10-CR
4 5 6.1 284D-SVE6P6Z-25-CR 284D-SVE6P6D-25-CR 284D-SVE6P6B-25-CR
  

NEMA Type 4X with quick disconnects for ArmorConnect power media, DeviceNet communications, Sensorless Vector Control, and Volts per Hertz torque performance, Up to 575V AC

Input Voltage 3-Phase kW Rating 3-Phase Hp Rating Output Current 24V DC
Control Voltage
120V AC
Control Voltage
240V AC
Control Voltage
Cat. No. Cat. No. Cat. No.
200…240V, 50/60 Hz
3-Phase
0.4 0.5 2.3 284D-SVB2P3Z-10-RR 284D-SVB2P3D-10-RR 284D-SVB2P3B-10-RR
0.75 1 5 284D-SVB5P0Z-10-RR 284D-SVB5P0D-10-RR 284D-SVB5P0B-10-RR
1.5 2 7.6 284D-SVB7P6Z-25-RR 284D-SVB7P6D-25-RR 284D-SVB7P6B-25-RR
380…480V, 50/60 Hz
3-Phase
0.4 0.5 1.4 284D-SVD1P4Z-10-RR 284D-SVD1P4D-10-RR 284D-SVD1P4B-10-RR
0.75 1 2.3 284D-SVD2P3Z-10-RR 284D-SVD2P3D-10-RR 284D-SVD2P3B-10-RR
1.5 2 4 284D-SVD4P0Z-10-RR 284D-SVD4P0D-10-RR 284D-SVD4P0B-10-RR
2.2 3 6 284D-SVD6P0Z-25-RR 284D-SVD6P0D-25-RR 284D-SVD6P0B-25-RR
3 5 7.6 284D-SVD7P6Z-25-RR 284D-SVD7P6D-25-RR 284D-SVD7P6B-25-RR
460…600V, 50/60 Hz
3-Phase
0.75 1 1.7 284D-SVE1P7Z-10-RR 284D-SVE1P7D-10-RR 284D-SVE1P7B-10-RR
1.5 2 3 284D-SVE3P0Z-10-RR 284D-SVE3P0D-10-RR 284D-SVE3P0B-10-RR
2.2 3 4.2 284D-SVE4P2Z-10-RR 284D-SVE4P2D-10-RR 284D-SVE4P2B-10-RR
4 5 6.1 284D-SVE6P6Z-25-RR 284D-SVE6P6D-25-RR 284D-SVE6P6B-25-RR
  

Options – Factory Installed

Description Cat. No. Modification
Click to enlarge - ArmorStart_284panel_007564_bw Hand/Off/Auto Selector Keypad -3
  Safety Monitor -SM
  EMI Filter -EMI
  Output Contactor -OC
  Shielded motor cable Enclosure Rating -CRN
IP67
NEMA Type 4X
  Supplied without motor cable IP67 -CRW
NEMA Type 4X
  Supplied with control brake cable IP67 -CB
NEMA Type 4X
  Supplied without control brake cable IP67 -CBW
NEMA Type 4X
  Supplied with source brake cable IP67 -SB
NEMA Type 4X
  Supplied without source brake cable IP67 -SBW
NEMA Type 4X
  0…10 Analog Input IP67 -A10
NEMA Type 4X
  Dynamic Brake Connector IP67 -DB
NEMA Type 4X
  Connectivity to ArmorConnect Power Media supplied with shielded motor cable Short Circuit Protection Rating Enclosure Rating -RRN
10 A IP67
NEMA Type 4X
25 A IP67
NEMA Type 4X
  Connectivity to ArmorConnect Power Media supplied without motor cable 10 A IP67 -RRW
NEMA Type 4X
25 A IP67
NEMA Type 4X
  

Accessories

Sealing Caps

Description For Use With Cat. No.
Plastic Sealing Cap (M12)¬  Input I/O Connection 1485A-M12
AC Micro Aluminum Sealing Cap - External¬  Output I/O Connection 889A-RMCAP
Stainless Steel Sealing Cap (M12)T  Input I/O Connection 1485AS-C3
Stainless Steel Sealing Cap (M12)T  Output I/O Connection 889AS-RMCAP
  
¬ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections.
T To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections.

Cables

Description Cable Rating Length [m (ft)] Cat. No.
Extended Motor Cable Cordsets  
90° M22 Motor Cordset IP67/NEMA Type 4 6 (19.6) 280-MTR22-M6
14 (45.9) 280-MTR22-M14
90° M22 Motor Cordset IP69K 6 (19.6) 280S-MTR22-M6
14 (45.9) 280S-MTR22-M14
Motor Cable Patchcords  
90° Male/Straight Female M22 IP67/NEMA Type 4 1 (3.3) 280-MTR22-M1D
3 (9.8) 280-MTR22-M3D
90° Male/Straight Female M22 IP69K 1 (3.3) 280S-MTR22-M1D
3 (9.8) 280S-MTR22-M3D
Shielded Motor Cable Cordsets  
90° M22 Motor Cordset IP67/NEMA Type 4 6 (19.6) 284-MTRS22-M6
90° M22 Motor Cordset IP67/NEMA Type 4 14 (45.9) 284-MTRS22-M14
90° M22 Motor Cordset IP69K 6 (19.6) 284S-MTRS22-M6
90° M22 Motor Cordset IP69K 14 (45.9) 284S-MTRS22-M14
Shielded Motor Cable Patchcords  
90° Male/Straight Female M22 IP67/NEMA Type 4 1 (3.3) 284-MTRS22-M1D
90° Male/Straight Female M22 IP67/NEMA Type 4 3 (9.8) 284-MTRS22-M3D
90° Male/Straight Female M22 IP69K 1 (3.3) 284S-MTRS22-M1D
90° Male/Straight Female M22 IP69K 3 (9.8) 284S-MTRS22-M3D
Extended Brake Cable Cordsets  
90° M25 Source Brake Cable IP67/NEMA Type 4 6 (19.6) 285-BRC25-M6
90° M25 Source Brake Cable IP67/NEMA Type 4 14 (45.9) 285-BRC25-M14
90° M25 Source Brake Cable IP69K 6 (19.6) 285S-BRC25-M6
90° M25 Source Brake Cable IP69K 14 (45.9) 285S-BRC25-M14
  

ArmorPoint® Media § 

Description Length [m (ft)] Cat. No.
ArmorPoint Bus Extension Cable including Terminating Resistor 1 (3.3) 280A-EXT1
Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol 1 (3.3) 280A-EXTCABLE
  
§  ArmorPoint media is only available with an IP67/NEMA Type 4 rating.

DeviceNet Media § 

Description Length [m (ft)] Cat. No.
      Sealed
Click to enlarge - 280_281-13-1 KwikLink pigtail drops are Insulation Displacement Connector (IDC) with integral Class 1 round cables for interfacing devices or power supplies to flat cable 1 (3.3) 1485P-P1E4-B1-N5
2 (6.5) 1485P-P1E4-B2-N5
3 (9.8) 1485P-P1E4-B3-N5
6 (19.8) 1485P-P1E4-B6-N5
Click to enlarge - 1485P-P1N5-MN5KF_4c DeviceNet Mini- T-Port Tap Left Keyway 1485P-P1N5-MN5KM
Right Keyway 1485P-P1N5-MN5NF
Description Connector Cat. No.
Click to enlarge - 1485G-P#M5-R5_Product_Iso_4C Gray PVC Thin Cable Mini Straight Female
Mini Straight Male
1485G-PT N5-M5
Mini Straight Female
Mini Right Angle Male
1485G-PT W5-N5
Mini Right Angle Female
Mini Straight Male
1485G-PT M5-Z5
Mini Right Angle Female
Mini Straight Male
1485G-PT W5-Z5
Click to enlarge - 1485C-P#N5-M5_Product_Iso_4C Thick Cable Mini Straight Female
Mini Straight Male
1485C-P‡ N5-M5
Mini Straight Female
Mini Right Angle Male
1485C-P‡ W5-N5
Mini Right Angle Female
Mini Straight Male
1485C-P‡ M5-Z5
Mini Right Angle Female
Mini Straight Male
1485C-P‡ W5-Z5
Description Length m (ft) Cat. No.
Click to enlarge - 193DNCT_10_4c DeviceNet Configuration Terminal
Used to interface with objects on a DeviceNet network. Includes 1 m communications cable.
1 (3.3) 193-DNCT
Communication cable, color-coded bare leads 1 (3.3) 193-CB1
Communication cable, microconnector (male) 1 (3.3) 193-CM1
Panel Mount Adapter/Door Mount Bezel Kit 193-DNCT-BZ1
  
§ See publication M116-CA001_-EN-P for complete cable selection information.
T Replace symbol with desired length in meters (Example: 1485G-P1N5-M5 for a 1 m cable). Standard cable lengths: 1, 2, 3, 4, 5, and 6 m.
‡ Replace symbol with desired length in meters (Example: 1485C-P1N5-M5 for a 1 m cable). Standard cable lengths: 1, 2, 3, 4, 5, 6, 8, 10, 12, 18, 24, and 30 m.

Sensor Media z 

Description ArmorStart I/O Connection Pin Count Connector Cat. No.
Click to enlarge - 280_281-13-4 DC Micro Patchcord Input 5-pin Straight Female
Straight Male
889D-F4ACDM-Ø 
Straight Female
Right Angle Male
889D-F4ACDE-Ø 
Click to enlarge - 280_281-13-5 DC Micro V-Cable Input 5-pin Straight Female 879D-F4ACDM-Ø 
Right Angle Male 879D-R4ACM-Ø 
Click to enlarge - 280_281-13-6 AC Micro Patchcord Output 3-pin Straight Female
Straight Male
889R-F3AERM-Ø 
Straight Female
Right Angle Male
889R-F3AERE-Ø 
  
z See publication M116-CA001_-EN-P for complete cable selection information.
Ø Replace symbol with desired length in meters (Example: 889D-F4ACDM-1 for a 1 m cable). Standard cable lengths: 1, 2, 5, and 10 m.
Note:Stainless steel versions may be ordered by adding an “S” to the cat. no. (Example: 889DS-F4ACDM-1).

Dynamic Brake Modules ª 

Drive Ratings Cat. No. § 
Input Voltage kW Hp Min. Resistance [W]
240V, 50/60 Hz, 3-Phase 0.4 0.5 48 AK-R2-091P500
0.75 1.0 48 AK-R2-091P500
1.5 2.0 48 AK-R2-091P500
2.2 3.0 32 AK-R2-047P500
3.7 5.0 32 AK-R2-047P500
480V, 50/60 Hz, 3-Phase 0.4 0.5 97 AK-R2-360P500
0.75 1.0 97 AK-R2-360P500
1.5 2.0 97 AK-R2-360P500
2.2 3.0 77 AK-R2-120P1K2
4.0 5.0 77 AK-R2-120P1K2
  
§ The resistors listed in this table are rated for 5% duty cycle.
ª Dynamic brake modules have an IP00 rating.

Peer-to-Peer Communications

Click to enlarge - armorstart3_ZIP ZONE diagram


The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP) which allows one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.

ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)

Click to enlarge - armorstart1


When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Bulletin 280A-EXT1. The 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.

Note:Access to DeviceLogix programming is available with RSNetworx for DeviceNet.


Click to enlarge - armorstart2


If an additional ArmorStart Distributed Motor Controller is to be connected, the Bulletin 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.

I/O Expansion with DeviceNet

If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Bulletin 1738-ADNX ArmorPoint Distributed I/O product.

Click to enlarge - armorpoint_1738_explogic


Bulletin 1738 ArmorPoint Distributed I/O Products

Digital Output Products

Description Cat. No.
Click to enlarge - armorpoint_1738_dig_out 24V DC, eight source output with eight M12 connectors 1738-OB8EM12
24V DC, eight source output with eight M8 connectors 1738-OB8EM8
24V DC, four source output with four M12 connectors 1738-OB4EM12
24V DC, four source output with four M8 connectors 1738-OB4EM8
24V DC, two source output with two M12 connectors 1738-OB2EM12
24V DC, two source output, 2 A prot. with two M12 connectors 1738-OB2EPM12
24V DC, four sink output with four M12 connectors 1738-OV4EM12
  

Digital Input Products

Description Cat. No.
Click to enlarge - armorpoint_1738_dig_in 24V DC, eight sink input with four M12 connectors, two points per connector 1738-IB8M12
24V DC, eight sink input with eight M8 connectors 1738-IB8M8
24V DC, eight sink input with one M23 connector 1738-IB8M23
24V DC, four sink input with four M12 connectors 1738-IB4M12
24V DC, four sink input with four M8 connectors 1738-IB4M8
24V DC, two sink input with two M12 connectors 1738-IB2M12
24V DC, four source input with four M12 connectors 1738-IV4M12
  

Analog Products

Description Cat. No.
Click to enlarge - armorpoint_1738_anlg 24V DC analog current input with two M12 connectors 1738-IE2CM12
24V DC analog voltage input with two M12 connectors 1738-IE2VM12
24V DC analog current output with two M12 connectors 1738-OE2CM12
24V DC analog voltage output with two M12 connectors 1738-OE2VM12
24V DC, two thermocouple input 1738-IT2IM12
24V DC, two RTD input 1738-IR2M12
  

Power Supply Products

Description Cat. No.
Click to enlarge - armorpoint_1738_ps ArmorPoint I/O Field Potential Distributor Module 1738-FPD
24V DC Expansion Power Supply 1738-EP24DC
  

AC and Relay Products

Description Cat. No.
Click to enlarge - armorpoint_1738_ac_and_relay 24V DC Coil, N.O. DPST relay with two M12 connectors 1738-OW4M12
24V DC Coil, N.O. DPST relay with two AC M12 connectors 1738-OW4M12AC
120V AC, two input with two AC 4-pin M12 connectors 1738-IA2M12AC4
120V AC, two input with two AC 3-pin M12 connectors 1738-IA2M12AC3
120/230V AC, two output with two AC 3-pin M12 connectors 1738-OA2M12AC3
  

Specialty Products

Description Cat. No.
Click to enlarge - armorpoint_1738_specialty ArmorPoint I/O RS-232 ASCII Serial Interface Module 1738-232ASCM12
ArmorPoint I/O RS-485 ASCII Serial Interface Module 1738-485ASCM12
24V DC Very High Speed Counter Module 1738-VHSC24M23
ArmorPoint 5V Encoder/Counter Module 1738-IJM23
ArmorPoint Synchronous Serial Interface Module with Absolute Encoder 1738-SSIM23
  

Adapter Products

Description Cat. No.
Click to enlarge - armorpoint_1738_adapters ArmorPoint DeviceNet Adapter Module, Drop or Pass-through, with male and female M12 connectors 1738-ADN12
ArmorPoint DeviceNet Adapter Module, Drop only, with male M18 connector 1738-ADN18
ArmorPoint DeviceNet Adapter Module, Drop or Pass-through, with male and female M18 connectors 1738-ADN18P
ArmorPoint DeviceNet 24V DC Adapter Module with subnet expansion 1738-ADNX
ArmorPoint Redundant ControlNet Adapter Module 1738-ACNR
ArmorPoint Ethernet/IP 10/100 Mbps Adapter Module 1738-AENT
  

Specifications

Electrical Ratings UL/NEMA IEC
Power Circuit Rated Operation Voltage 200…575V 200…500V
Rate Insulation Voltage 600V 600V
Rated Impulsed Voltage 6 kV 6 kV
Dielectric Withstand 2200V AC 2500V AC
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category N/A AC-3
Protection Against Shock N/A IP2X
Control Circuit Rated Operation Voltage 24V DC (+10%, -15%) A2 (should be grounded at voltage source)
120V AC (+10%, -15%) A2 (should be grounded at voltage source)
240V AC (+10%, -15%) A2 (should be grounded at voltage source)
Rate Insulation Voltage 250V 250V
Rated Impulsed Voltage 4 kV
Dielectric Withstand 1500V AC 2000V AC
Overvoltage Category III
Operating Frequency 50/60 Hz  
Short Circuit Protection SCPD performance Type 1 Current Rating Voltage 480Y/277V 480/480V 600Y/347V 600V
10 A Sym. Amps RMS 65 kA 65 kA 30 kA 30 kA
25 A 30 kA 30 kA 30 kA 30 kA
SCPD List Size per NEC Group Motor
  

Power Requirements
  Units No Options Brake or Output Contactor w/ Brake and Output Contactor
Control Voltage Volts 24V DC 120V AC 240V AC 24V DC 120V AC 240V AC 24V DC 120V AC 240V AC
Total Control VA (Pick Up) VA (W) (11 W) 16 24 (13 W) 38 46 (16 W) 60 68
Total Control VA (Hold In) VA (W) (11 W) 16 24 (13 W) 20 28 (16 W) 24 32
External Devices powered by Control Voltage
Outputs (2)
(1 A max. each)
Amps 2 2 2 2 2 2 2 2 2
Total Control VA (Pick Up) with max outputs VA (W) (59 W) 256 504 (61 W) 278 548 (64 W) 300 548
Total Control VA (Hold In) with max outputs VA (W) (59 W) 256 504 (61 W) 261 512 (64 W) 264 512
  

Input Ratings Rated Operation Voltage 24V DC
Input On-State Voltage Range 10…26V DC
Input On-State Current 3.0 mA @ 10V DC
7.2 mA @ 24V DC
Input Off-State Voltage Range 0…5V DC
Input Off-State Current <1.5 mA
Input Filter — Software Selectable
Off to On Settable from 0…64 ms in 1 ms increments
On to Off Settable from 0…64 ms in 1 ms increments
Input Compatibility N/A IEC 1+
Number of Inputs 4
Sensor Source
Voltage Status Only 11…25V DC from DeviceNet
Current Available 50 mA max. per input, 200 mA total
Output Ratings (Sourced from Control Circuit) Rated Operation Voltage 240V AC/30V DC 240V AC/30V DC
Rate Insulation Voltage 250V 250V
Dielectric Withstand 1500V AC 2000V AC
Operating Frequency 50/60 Hz 50/60 Hz
Type of Control Circuit Electromechanical relay
Type of Current AC/DC
Conventional Thermal Current Ith Total of both outputs £ 2 A
Type of Contacts Normally open (N.O.)
Number of Contacts 2
ArmorPoint Ratings Backplane Current Load 400 mA
  

  UL/NEMA IEC
Environmental Operating Temperature Range -20…+40 °C (-4…+104 °F)
Storage and Transportation
Temperature Range
–25….+85 °C (–13…+185 °F)
Altitude 1000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings NEMA 4/12/13 IP67
NEMA 4X IP69K
Approximate Shipping Weight 13.6 kg (30 lb)
Mechanical Resistance to Shock
Operational 15 G
Non-Operational 30 G
Resistance to Vibration
Operational 1 G, 0.15 mm (0.006 in.) displacement
Non-Operational 2.5 G, 0.38 mm (0.015 in.) displacement
Wire Size Primary/Secondary terminal:
(16 …10 AWG)
Primary/Secondary terminal:
1.5…4.0 mm2
Tightening Torque Primary terminal:
10.8 lb•in
Secondary terminal:
4.5 lb•in
Primary terminal:
(1.2 N•m)
Secondary terminal:
(0.5 N•m)
Wire Strip Length 0.35 in. (9 mm)
Control and Safety Monitor Inputs
Wire Size (18…10 AWG) 1.0…4.0 mm2
Tightening Torque 6.2 lb•in 0.7 N•m
Wire Strip Length 0.35 in. (9 mm)
Other Rating EMC Emission Levels
Conducted Radio Frequency Emissions Class A
Radiated Emissions Class A
EMC Immunity Levels
Electrostatic Discharge 4 kV contact and 8 kV Air
Radio Frequency Electromagnetic Field 10V/m
Fast Transient 2 kV
Surge Transient 1 kV (12) L-L, 2 kV (2) L-N (earth)
Overload Characteristics
Trip Class 10
Overload Protection I2t overload protection - 150% for 60 s, 200% for 30 s
Number of Poles 3
DeviceNet Specifications
DeviceNet Supply Voltage Rating Range 11…25V DC, 24V DC nominal
DeviceNet Input Current 167 mA @ 24V DC - 4.0 W
364 mA @ 11V DC - 4.0 W
External Devices powered by DeviceNet Sensors inputs 4 x 50 mA - total 200 mA
Total w/max Sensor Inputs (4) 367 mA @ 24V DC - 8.8 W
DeviceNet Input Current Surge 15 A for 250 ms
DeviceNet Communications
Baud Rates 125, 250, 500 kbps
Distance Maximum 500 m (1630 ft) @ 125 kbps
200 m (656 ft) @ 250 kbps
100 m (328 ft) @ 500 kbps
Certifications cULus (File No. E207834)
UL 508C
EN/IEC 60947-1, EN 50178, EN 61800-3
CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC
  

External Connections for Input Connector

Click to enlarge - 280_281-16-1


External Connections for Output Connector

Click to enlarge - 280_281-16-3


External Connections for DeviceNet Connector

Click to enlarge - 280_281-16-5


External Connections for Motor Connector

Click to enlarge - pin_external_motor


External Connections for Brake Contactor Connector

Click to enlarge - pin_external_brake_1


External Connections for Dynamic Brake Connection

Click to enlarge - pin_external_brakea


External Connections for ArmorPoint Interface (IN)

Click to enlarge - 280_281_8pin_in


External Connections for ArmorPoint Interface (OUT)

Click to enlarge - 280_281_8pin_out


External Connections for 0…10V Analog Input

Click to enlarge - 280_281-16-1a


Overload Curves

Click to enlarge - mtrovrld

Approximate Dimensions

Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, IP67/NEMA Type 4 with Conduit Entrance

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c std 2hp sht1


Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, IP67/NEMA Type 4 with ArmorConnect Connectivity

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c std 2hp sht2 lft


Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, IP67/NEMA Type 4 with Conduit Entrance

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c std 5hp sht1


Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, IP67/NEMA Type 4 with ArmorConnect Connectivity

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c std 5hp sht2 lft


Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, NEMA Type 4X with Conduit Entrance

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c 4x 2hp sht1


Dimensions for 1 Hp and below @ 230V AC, 2 Hp and below @ 460V AC, and 2 Hp and below @ 575V AC, NEMA Type 4X with ArmorConnect Connectivity

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c 4x 2hp sht2 lft


Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, NEMA Type 4X with Conduit Entrance

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c 4x 5hp sht1


Dimensions for 2 Hp @ 230V AC, 3 Hp and above @ 460V AC, and 3 Hp and above @ 575V AC, NEMA Type 4X with ArmorConnect Connectivity

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Click to enlarge - 280 series c 4x 5hp sht2 lft


Dynamic Brake Modules

Dimensions are in millimeters (inches) and weights are in kilograms (pounds). Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - dbresdim


Frame Cat. No. Weight
[kg (lb)]
A AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 1.1 (2.5)
B AK-R2-030P1K2, AK-R2-120P1K2 2.7 (6)