Bulletin 280/281 ArmorStart Distributed Motor Controller
| Product Overview |
|
280/281 ArmorStart Distributed Motor Controller
- On-Machine starting solution
- Full-voltage and reversing
- Horsepower range 0.5…10 Hp (0.37…7.5 kW)
- Robust IP67/NEMA Type 4 and NEMA Type 4X enclosure rating
- Modular plug and play design
- Quick disconnect connections for I/O, communications, motor, three-phase and control power
- Gland plate entry: conduit entrance or ArmorConnect power media
- Four inputs and two outputs (expandable with ArmorPoint)
- LED status indication
- DeviceNet communications
- DeviceLogix component technology
- Peer-to-peer communication (ZIP)
- Connectivity to ArmorPoint distributed I/O products
- ControlNet and EtherNet communications via ArmorPoint
- Factory installed options:
- Hand/Off/Auto (HOA) keypad configuration
- Safety monitor
- Hand/Off/Auto (HOA) keypad configuration
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2, No. 14
EN/IEC 60947-1
CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC
CCC
Certifications
cULus (File No. E3125, Guides NLDX, NLDX7)
Description
The Bulletin 280/281 ArmorStart Distributed Motor Controller is an integrated, pre-engineered, starter for full-voltage and reversing applications. The ArmorStart offers a robust IP67/NEMA Type 4 enclosure design, which is suitable for water wash-down environments. The ArmorStart products are also offered with NEMA Type 4X rating, suitable for environment wash down with caustic chemicals used in the food and beverage industry. The wash-down rating is 1000 psi for the NEMA Type 4X rated devices. The modular plug-and-play design offers simplicity in wiring the installation. The quick disconnects for the I/O, communications, and motor connection reduce the wiring time and eliminate wiring errors. The ArmorStart offers as standard, four DC inputs and two relay outputs to be used with sensors and actuators respectively, for monitoring and controlling the application process. The ArmorStarts LED status indication and built-in diagnostics capabilities allows ease of maintenance and troubleshooting. The optional Hand/Off/Auto (HOA) keypad allows for local start/stop control at the ArmorStart Distributed Motor Controller.
The Bulletin 280/281 ArmorStart Distributed Motor Controller offers short-circuit protection per UL 508 and IEC 60947. The ArmorStart is rated for local-disconnect service by incorporating the Bulletin 140 Motor Protector as the local-disconnect, eliminating the need for additional components. The ArmorStart Distributed Motor Controllers are suitable for group motor installations.
Mode of Operation
Full-Voltage Start
This method is used in applications requiring across-the-line starting. Full in-rush current and locked-rotor torque are realized. The ArmorStart Bulletin 280 offers full-voltage starting, and the Bulletin 281 offers full-voltage starting for reversing applications.
Description of Features
Overload Protection
The Bulletin 280/281 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStarts overload protection is programmable via the communication network providing the user with flexibility. The overload trip class can be selected for class 10, 15, or 20 protection. Ambient insensitivity is inherent in the electronic design of the overload.
Inputs
The inputs are single keyed (two inputs per connector), which are sourced from DeviceNet power (24V DC), with LED status indication.
Outputs
Two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power, which can be either, 24V DC, 120V AC, or 240V AC with LED status indication.
Gland Plate Entrance
The ArmorStart product offers two different methods for connecting incoming three-phase and control power to the device. One method offered is the traditional conduit entrance which provides a 3/4 and 1 in. conduit hole opening for wiring three-phase and control power. The second method offers connectivity to the ArmorConnect power media. Factory installed receptacles are provided for connectivity to both three-phase and control power media.
Motor Cable
With every Bulletin 280/281 ArmorStart Distributed Motor Controller, a 3-meter unshielded 4-conductor cordset is provided with each unit as standard.
LED Status Indication
The LED Status Indication provides four status LEDs and a Reset button. The LEDs provide status indication for the following:
- POWER LED
The LED is illuminated solid green when control power is present and with the proper polarity
- RUN LED
This LED is illuminated solid green when a start command and control power are present
- NETWORK LED
This bicolor (red/green) LEDs indicates the status of the communication link
- FAULT LED
Indicates Controller Fault (trip) condition
- The Reset Button as a local trip reset.
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.
- Short Circuit
- Overload
- Phase Loss
- Control Power Loss
- Control Power Fuse Detection
- I/O Fault
- Output Power Fuse Detection
- Overtemperature
- Phase Imbalance
- DeviceNet Power Loss
- EEPROM Fault
- Hardware Fault
Network and Expandable I/O Capabilities
The Bulletin 280D/281D ArmorStart Distributed Motor Controller delivers enhanced control to access parameter settings and provides fault diagnostics and remote start/stop control. DeviceNet is the communication protocol provided with the ArmorStart, including DeviceLogix.
The Bulletin 280A/281A ArmorStart Distributed Motor Controller allows connectivity to the ArmorPoint backplane. The ArmorPoint I/O system can communicate using DeviceNet, ControlNet, or EtherNet communication protocols. In addition to the different network protocols, the ArmorPoint Distributed I/O products allow the I/O capability to be expanded beyond the standard two outputs. The two dual-key relay output connectors are supplied as standard. The outputs are sourced from the control voltage power of 24V DC, 120V AC, or 240V AC. LED status indication is also provided. When using the ArmorPoint, a maximum of two ArmorPoint Distributed Motor Controllers can be connected to the ArmorPoint Distributed I/O product.
Cat. No. Explanation
| 280 | D | | F | 12Z | | 10 | C | | CR | | Option 1 | | Option 2 | |||
| a | b | c | d | e | f | g | h | i |
| a | |
| Bulletin Number | |
| Code | Description |
| 280 | Full Voltage Starter |
| 281 | Reversing Starter |
| b | |
| Communications | |
| Code | Description |
| D | DeviceNet™ |
| A | ArmorPoint |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | ||
| Contactor Size/Control Voltage | ||
| 24V DC | 120V AC | 240V AC |
| 12Z | 12D | 12B |
| 23Z | 23D | 23B |
| e | |
| Short Circuit Protection (Motor Circuit Protector) |
|
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| f | |
| Overload Selection Current Range | |
| Code | Description |
| A | 0.24…1.2 A |
| B | 0.5…2.5 A |
| C | 1.1…5.5 A |
| D | 3.2…16 A |
| g | ||||
| Control and 3-Phase Power Connections/Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | W ¬ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | W ¬ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| h | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad |
| 3FR | Hand/Off/Auto Selector Keypad with Forward/Reverse |
| i | |
| Option 2 | |
| Code | Description |
| SM | Safety Monitor |
¬ See Accessories on Accessories for extended motor cable lengths.
Product Selection
| Build a Catalog Number |
Full-voltage starters — IP67/NEMA Type 4 with conduit entrance and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-F12Z-10A-CR | 280D-F12D-10A-CR | 280D-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-F12Z-10B-CR | 280D-F12D-10B-CR | 280D-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-F12Z-10C-CR | 280D-F12D-10C-CR | 280D-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-F23Z-25D-CR | 280D-F23D-25D-CR | 280D-F23B-25D-CR |
Full-voltage starters — IP67/NEMA Type 4 with conduit entrance and ArmorPoint communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280A-F12Z-10A-CR | 280A-F12D-10A-CR | 280A-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280A-F12Z-10B-CR | 280A-F12D-10B-CR | 280A-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280A-F12Z-10C-CR | 280A-F12D-10C-CR | 280A-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280A-F23Z-25D-CR | 280A-F23D-25D-CR | 280A-F23B-25D-CR |
Full-voltage starters — IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-F12Z-10A-RR | 280D-F12D-10A-RR | 280D-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-F12Z-10B-RR | 280D-F12D-10B-RR | 280D-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-F12Z-10C-RR | 280D-F12D-10C-RR | 280D-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-F23Z-25D-RR | 280D-F23D-25D-RR | 280D-F23B-25D-RR |
Full-voltage starters — IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media and ArmorPoint communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280A-F12Z-10A-RR | 280A-F12D-10A-RR | 280A-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280A-F12Z-10B-RR | 280A-F12D-10B-RR | 280A-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280A-F12Z-10C-RR | 280A-F12D-10C-RR | 280A-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280A-F23Z-25D-RR | 280A-F23D-25D-RR | 280A-F23B-25D-RR |
Full-voltage starters — NEMA Type 4X with conduit entrance and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-S12Z-10A-CR | 280D-S12D-10A-CR | 280D-S12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-S12Z-10B-CR | 280D-S12D-10B-CR | 280D-S12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-S12Z-10C-CR | 280D-S12D-10C-CR | 280D-S12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-S23Z-25D-CR | 280D-S23D-25D-CR | 280D-S23B-25D-CR |
Full-voltage starters — NEMA Type 4X with quick disconnects for ArmorConnect power media and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-S12Z-10A-RR | 280D-S12D-10A-RR | 280D-S12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-S12Z-10B-RR | 280D-S12D-10B-RR | 280D-S12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-S12Z-10C-RR | 280D-S12D-10C-RR | 280D-S12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-S23Z-25D-RR | 280D-S23D-25D-RR | 280D-S23B-25D-RR |
Reversing starters — IP67/NEMA Type 4 with conduit entrance and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-F12Z-10A-CR | 281D-F12D-10A-CR | 281D-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-F12Z-10B-CR | 281D-F12D-10B-CR | 281D-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-F12Z-10C-CR | 281D-F12D-10C-CR | 281D-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-F23Z-25D-CR | 281D-F23D-25D-CR | 281D-F23B-25D-CR |
Reversing starters — IP67/NEMA Type 4 with conduit entrance and ArmorPoint communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281A-F12Z-10A-CR | 281A-F12D-10A-CR | 281A-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281A-F12Z-10B-CR | 281A-F12D-10B-CR | 281A-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281A-F12Z-10C-CR | 281A-F12D-10C-CR | 281A-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281A-F23Z-25D-CR | 281A-F23D-25D-CR | 281A-F23B-25D-CR |
Reversing starters — IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-F12Z-10A-RR | 281D-F12D-10A-RR | 281D-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-F12Z-10B-RR | 281D-F12D-10B-RR | 281D-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-F12Z-10C-RR | 281D-F12D-10C-RR | 281D-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-F23Z-25D-RR | 281D-F23D-25D-RR | 281D-F23B-25D-RR |
Reversing starters — IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media and ArmorPoint communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281A-F12Z-10A-RR | 281A-F12D-10A-RR | 281A-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281A-F12Z-10B-RR | 281A-F12D-10B-RR | 281A-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281A-F12Z-10C-RR | 281A-F12D-10C-RR | 281A-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281A-F23Z-25D-RR | 281A-F23D-25D-RR | 281A-F23B-25D-RR |
Reversing starters — NEMA Type 4X with conduit entrance and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-S12Z-10A-CR | 281D-S12D-10A-CR | 281D-S12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-S12Z-10B-CR | 281D-S12D-10B-CR | 281D-S12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-S12Z-10C-CR | 281D-S12D-10C-CR | 281D-S12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-S23Z-25D-CR | 281D-S23D-25D-CR | 281D-S23B-25D-CR |
Reversing starters — NEMA Type 4X with quick disconnects for ArmorConnect power media and DeviceNet communications, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-S12Z-10A-RR | 281D-S12D-10A-RR | 281D-S12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-S12Z-10B-RR | 281D-S12D-10B-RR | 281D-S12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-S12Z-10C-RR | 281D-S12D-10C-RR | 281D-S12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-S23Z-25D-RR | 281D-S23D-25D-RR | 281D-S23B-25D-RR |
Options Factory Installed
Accessories
Sealing Caps
| Description | For Use With | Cat. No. |
| Plastic Sealing Cap (M12)¬ | Input I/O Connection | 1485A-M12 |
| AC Micro Aluminum Sealing Cap - External¬ | Output I/O Connection | 889A-RMCAP |
| Stainless Steel Sealing Cap (M12)T | Input I/O Connection | 1485AS-C3 |
| Stainless Steel Sealing Cap (M12)T | Output I/O Connection | 889AS-RMCAP |
| ¬ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections. | ||
| T To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections. | ||
Cables
| Description | Cable Rating | Length m (ft) | Cat. No. |
| Extended Motor Cable Cordsets | |||
| 90° M22 Motor Cordset | IP67/NEMA Type 4 | 6 (19.6) | 280-MTR22-M6 |
| 14 (45.9) | 280-MTR22-M14 | ||
| 90° M35 Motor Cordset | IP67/NEMA Type 4 | 6 (19.6) | 280-MTR35-M6 |
| 14 (45.9) | 280-MTR35-M14 | ||
| 90° M22 Motor Cordset | IP69K | 6 (19.6) | 280S-MTR22-M6 |
| 14 (45.9) | 280S-MTR22-M14 | ||
| 90° M35 Motor Cordset | IP69K | 6 (19.6) | 280S-MTR35-M6 |
| 14 (45.9) | 280S-MTR35-M14 | ||
| Motor Cable Patchcords | |||
| 90° Male/Straight Female M22 | IP67/NEMA Type 4 | 1 (3.3) | 280-MTR22-M1D |
| 3 (9.8) | 280-MTR22-M3D | ||
| 90° Male/Straight Female M35 | IP67/NEMA Type 4 | 1 (3.3) | 280-MTR35-M1D |
| 3 (9.8) | 280-MTR35-M3D | ||
| 90° Male/Straight Female M22 | IP69K | 1 (3.3) | 280S-MTR22-M1D |
| 3 (9.8) | 280S-MTR22-M3D | ||
| 90° Male/Straight Female M35 | IP69K | 1 (3.3) | 280S-MTR35-M1D |
| 3 (9.8) | 280S-MTR35-M3D | ||
ArmorPoint® Media §
| Description | Length m (ft) | Cat. No. |
| ArmorPoint Bus Extension Cable including Terminating Resistor | 1 (3.3) | 280A-EXT1 |
| Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol | 1 (3.3) | 280A-EXTCABLE |
| § ArmorPoint media is only available with an IP67/NEMA Type 4 rating. | ||
DeviceNet Media §
Sensor Media z
Peer-to-Peer Communications
|
The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP) which allows one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.
ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)
|
When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Bulletin 280A-EXT1. The 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.
Note: Access to DeviceLogix programming is available with RSNetworx for DeviceNet.
If an additional ArmorStart Distributed Motor Controller is to be connected, the Bulletin 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.
|
I/O Expansion with DeviceNet
If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Bulletin 1738-ADNX ArmorPoint Distributed I/O product.
|
Bulletin 1738 ArmorPoint Distributed I/O Products
Digital Output Products
Digital Input Products
Analog Products
Power Supply Products
| Description | Cat. No. | |
|
|
ArmorPoint I/O Field Potential Distributor Module | 1738-FPD |
| 24V DC Expansion Power Supply | 1738-EP24DC | |
AC and Relay Products
Specialty Products
Adapter Products
Specifications
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…575V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Rated Operating Current Max. | 1.2 A | ||||||
| 2.5 A | |||||||
| 5.5 A | |||||||
| 16 A | |||||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| 120V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | ||||||
| Short Circuit Protection | SCPD Performance Type 1 | Current Rating | Voltage | 480Y/277V | 480/480V | 600Y/347V | 600V |
| 0.24…1.2 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 0.5…2.5 A | |||||||
| 1.1…5.5 A | |||||||
| 3.2…16 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NEC Group Motor | — | |||||
| Power Requirements | |||||||
| Units | W/O HOA | W/ HOA | |||||
| Control Voltage | Volts | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC |
| Contactor (Pick Up) | Amps | 0.71 | 0.583 | 0.292 | 0.71 | 0.583 | 0.292 |
| Contactor (Hold In) | Amps | 0.063 | 0.075 | 0.038 | 0.063 | 0.075 | 0.038 |
| Total Control Power (Pick Up) | VA (W) | (17 W) | 70 | 70 | (21 W) | 83 | 84 |
| Total Control Power (Hold In) | VA (W) | (1.50 W) | 9 | 9 | (5.58 W) | 22 | 23 |
| External Devices powered by Control Voltage | |||||||
| Outputs (2) (1 A max. each) | Amps | 2 | 2 | 2 | 2 | 2 | 2 |
| Total Control (Pick Up) with max outputs | VA (W) | (65 W) | 310 | 550 | (73 W) | 336 | 579 |
| Total Control (Hold In) with max outputs | VA (W) | (50 W) | 249 | 489 | (58 W) | 275 | 518 |
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings (Sourced from Control Circuit) | Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 2000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X | IP69K | ||
| Approximate Shipping Weight | 6.8 kg (15 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Power and Ground Terminals | |||
| Wire Size | Primary/Secondary terminal: (#16 …#10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary Terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | (18…10 AWG) | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Other Rating | EMC Emission Levels | ||
| Conducted Radio Frequency Emissions | Class A | ||
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | |||
| Electrostatic Discharge | 4 kV contact and 8 kV Air | ||
| Radio Frequency Electromagnetic Field | 10V/m | ||
| Fast Transient | 2 kV | ||
| Surge Transient | 1 kV L-L, 2 kV L-N (earth) | ||
| Overload Characteristics | |||
| Overload Current Range | 0.24…1.2 A | ||
| 0.5…2.5 A | |||
| 1.1…5.5 A | |||
| 3.2…16 A | |||
| Trip Classes | 10, 15, 20 | ||
| Trip Rating | 120% of FLC setting | ||
| Number of poles | 3 | ||
| DeviceNet Specifications | |||
| DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | ||
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| 364 mA @ 11V DC - 4.0 W | |||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | |||
| Baud Rates | 125, 250, 500 kbps | ||
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| 200 m (656 ft) @ 250 kbps | |||
| 100 m (328 ft) @ 500 kbps | |||
| Certifications | cULus (File No. E3125) UL 508 EN/IEC 60947-4-1 CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC |
||
External Connections for Input Connector
|
External Connections for Output Connector
|
External Connections for Motor Connector (£ 3 Hp @ 460V AC)
|
External Connections for Motor Connector (> 3 Hp @ 460V AC)
|
External Connections for ArmorPoint Interface (IN)
|
External Connections for ArmorPoint Interface (OUT)
|
Overload Curves
|
|
|
Approximate Dimensions
Dimensions for IP67/NEMA Type 4 with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for IP67/NEMA Type 4 with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|