Bulletin 280/281 ArmorStart Distributed Motor Controller
| Product Overview |
|
280/281 ArmorStart Distributed Motor Controller
- On-Machine starting solution
- Full-voltage and reversing
- Horsepower range 0.5…10 Hp (0.37…7.5 kW)
- Robust IP67/NEMA Type 4 or NEMA Type 4X enclosure rating
- Quick disconnect connections for I/O, communications, motor, three-phase and control power
- Gland plate entry: conduit entrance or ArmorConnect power media
- LED status indication
- EtherNet/IP, DeviceNet, or ControlNet communications
- Local logic technology using DeviceLogix
- Peer-to-peer communication (ZIP) (not available with EtherNet communications)
- Connectivity to ArmorPoint distributed I/O products
- Factory installed options:
- Hand/Off/Auto (HOA) keypad configuration
- Safety monitor
- Hand/Off/Auto (HOA) keypad configuration
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2, No. 14
EN/IEC 60947-4
EN/IEC 60947-4-1
CE Marked per Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/EC
CCC
ODVA for EtherNet/IP and DeviceNet
Certifications
cULus (File No. E3125, Guides NLDX, NLDX7)
Mode of Operation
Full-Voltage Start
This method is used in applications requiring across-the-line starting. Full in-rush current and locked-rotor torque are realized. The ArmorStart Bulletin 280 offers full-voltage starting, and the Bulletin 281 offers full-voltage starting for reversing applications.
|
Overload Protection
The Bulletin 280/281 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStarts overload protection is programmable via the communication network providing the user with flexibility. The overload trip class can be selected for class 10, 15, or 20 protection. Ambient insensitivity is inherent in the electronic design of the overload.
Fault Diagnostics
Fault diagnostics capabilities built in the ArmorStart Distributed Motor Controller:
- Short Circuit
- Overload
- Phase Loss
- Control Power Loss
- Control Power Fuse Detection
- I/O Fault
- Output Power Fuse Detection
- Overtemperature
- Phase Imbalance
- DeviceNet Power Loss
- EEPROM Fault
- Hardware Fault
- Output Power Fuse Detection
- Overtemperature
- Phase Imbalance
- EEPROM Fault
- Hardware Fault
Factory-Installed Options
HOA Selector Keypad
The HOA Selector Keypad allows local start/stop control.
Safety Monitor
The Safety Monitor Option allows independent monitoring of the output status of the device. The function is implemented using a normally closed contact which complies with IEC 60947-5-1 for mechanically linked contacts. Two terminal blocks are provided as the inputs which maybe used with an external safety circuit. The external safety circuit monitors the status of the isolation contactor.
Catalog Number Explanation
| 280 | D | | F | 12Z | | 10 | C | | CR | | Option 1 | | Option 2 | |||
| a | b | c | d | e | f | g | h | i |
| a | |
| Bulletin Number | |
| Code | Description |
| 280 | Full-Voltage Starter |
| 281 | Reversing Starter |
| b | |
| Communications | |
| Code | Description |
| A | ArmorPoint |
| D | DeviceNet |
| E | EtherNet/IP |
| c | |
| Enclosure Type | |
| Code | Description |
| F | Type 4 (IP67) |
| S | Type 4X |
| d | ||
| Contactor Size/Control Voltage♣ | ||
| 24V DC | 120V AC | 240V AC |
| 12Z | 12D | 12B |
| 23Z | 23D | 23B |
| e | |
| Short Circuit Protection (Motor Circuit Protector) |
|
| Code | Description |
| 10 | 10 A Rated Device |
| 25 | 25 A Rated Device |
| f | |
| Overload Selection Current Range | |
| Code | Description |
| A | 0.24…1.2 A |
| B | 0.5…2.5 A |
| C | 1.1…5.5 A |
| D | 3.2…16 A |
| g | ||||
| Control and 3-Phase Power Connections/Motor Cable Connection (CR: Conduit/Round Media) or (RR: Round/Round Media) |
||||
Code |
Description | |||
| Control Power | 3-Phase Power | Motor Cable | ||
| CR | blank | Conduit Entrance | Conduit Entrance | 3 m, unshielded cordset male 90° |
| CR | W ⋆ | Conduit Entrance | Conduit Entrance | No cable |
| RR | blank | Round Media (Male Receptacle) | Round Media (Male Receptacle) | 3 m, unshielded cordset male 90° |
| RR | W ⋆ | Round Media (Male Receptacle) | Round Media (Male Receptacle) | No cable |
| h | |
| Option 1 | |
| Code | Description |
| 3 | Hand/Off/Auto Selector Keypad |
| 3FR | Hand/Off/Auto Selector Keypad with Forward/Reverse |
| i | |
| Option 2 | |
| Code | Description |
| SM§ | Safety Monitor |
⋆ See Accessories on Motor and Brake Cables for extended motor cable lengths.
Not available with EtherNet/IP or ArmorPoint versions.
§ Not available with EtherNet/IP version, also not available with round media option (RR).
♣ See Product Selection tables for additional information.
Product Selection
| Build a Catalog Number |
EtherNet/IP Network Communication
Full-voltage starters — IP67/NEMA Type 4 with conduit entrance, Up to 480V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage | |||
| 230V AC, 50 Hz | 400V AC, 50 Hz | 200V AC, 60 Hz | 230V AC, 60 Hz | 460V AC, 60 Hz | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 280E-F12Z-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 280E-F12Z-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 280E-F12Z-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 280E-F23Z-25D-CR |
Full-voltage starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 480V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage | |||
| 230V AC, 50 Hz | 400V AC, 50 Hz | 200V AC, 60 Hz | 230V AC, 60 Hz | 460V AC, 60 Hz | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 280E-F12Z-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 280E-F12Z-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 280E-F12Z-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 280E-F23Z-25D-RR |
Reversing starters — IP67/NEMA Type 4 with conduit entrance, Up to 480V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage | |||
| 230V AC, 50 Hz | 400V AC, 50 Hz | 200V AC, 60 Hz | 230V AC, 60 Hz | 460V AC, 60 Hz | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 281E-F12Z-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 281E-F12Z-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 281E-F12Z-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 281E-F23Z-25D-CR |
Reversing starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 480V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage | |||
| 230V AC, 50 Hz | 400V AC, 50 Hz | 200V AC, 60 Hz | 230V AC, 60 Hz | 460V AC, 60 Hz | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 281E-F12Z-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 281E-F12Z-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 281E-F12Z-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 281E-F23Z-25D-RR |
DeviceNet Network Communications
Full-voltage starters — IP67/NEMA Type 4 with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-F12Z-10A-CR | 280D-F12D-10A-CR | 280D-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-F12Z-10B-CR | 280D-F12D-10B-CR | 280D-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-F12Z-10C-CR | 280D-F12D-10C-CR | 280D-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-F23Z-25D-CR | 280D-F23D-25D-CR | 280D-F23B-25D-CR |
Full-voltage starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-F12Z-10A-RR | 280D-F12D-10A-RR | 280D-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-F12Z-10B-RR | 280D-F12D-10B-RR | 280D-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-F12Z-10C-RR | 280D-F12D-10C-RR | 280D-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-F23Z-25D-RR | 280D-F23D-25D-RR | 280D-F23B-25D-RR |
DeviceNet Network Communication, Continued
Full-voltage starters — NEMA Type 4X with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-S12Z-10A-CR | 280D-S12D-10A-CR | 280D-S12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-S12Z-10B-CR | 280D-S12D-10B-CR | 280D-S12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-S12Z-10C-CR | 280D-S12D-10C-CR | 280D-S12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-S23Z-25D-CR | 280D-S23D-25D-CR | 280D-S23B-25D-CR |
Full-voltage starters — NEMA Type 4X with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280D-S12Z-10A-RR | 280D-S12D-10A-RR | 280D-S12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280D-S12Z-10B-RR | 280D-S12D-10B-RR | 280D-S12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280D-S12Z-10C-RR | 280D-S12D-10C-RR | 280D-S12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280D-S23Z-25D-RR | 280D-S23D-25D-RR | 280D-S23B-25D-RR |
Reversing starters — IP67/NEMA Type 4 with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-F12Z-10A-CR | 281D-F12D-10A-CR | 281D-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-F12Z-10B-CR | 281D-F12D-10B-CR | 281D-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-F12Z-10C-CR | 281D-F12D-10C-CR | 281D-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-F23Z-25D-CR | 281D-F23D-25D-CR | 281D-F23B-25D-CR |
Reversing starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-F12Z-10A-RR | 281D-F12D-10A-RR | 281D-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-F12Z-10B-RR | 281D-F12D-10B-RR | 281D-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-F12Z-10C-RR | 281D-F12D-10C-RR | 281D-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-F23Z-25D-RR | 281D-F23D-25D-RR | 281D-F23B-25D-RR |
Reversing starters — NEMA Type 4X with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-S12Z-10A-CR | 281D-S12D-10A-CR | 281D-S12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-S12Z-10B-CR | 281D-S12D-10B-CR | 281D-S12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-S12Z-10C-CR | 281D-S12D-10C-CR | 281D-S12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-S23Z-25D-CR | 281D-S23D-25D-CR | 281D-S23B-25D-CR |
Reversing starters — NEMA Type 4X with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281D-S12Z-10A-RR | 281D-S12D-10A-RR | 281D-S12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281D-S12Z-10B-RR | 281D-S12D-10B-RR | 281D-S12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281D-S12Z-10C-RR | 281D-S12D-10C-RR | 281D-S12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281D-S23Z-25D-RR | 281D-S23D-25D-RR | 281D-S23B-25D-RR |
ArmorPoint Bus Network Communication
Full-voltage starters — IP67/NEMA Type 4 with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280A-F12Z-10A-CR | 280A-F12D-10A-CR | 280A-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280A-F12Z-10B-CR | 280A-F12D-10B-CR | 280A-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280A-F12Z-10C-CR | 280A-F12D-10C-CR | 280A-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280A-F23Z-25D-CR | 280A-F23D-25D-CR | 280A-F23B-25D-CR |
Full-voltage starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 280A-F12Z-10A-RR | 280A-F12D-10A-RR | 280A-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 280A-F12Z-10B-RR | 280A-F12D-10B-RR | 280A-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 280A-F12Z-10C-RR | 280A-F12D-10C-RR | 280A-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 280A-F23Z-25D-RR | 280A-F23D-25D-RR | 280A-F23B-25D-RR |
Reversing starters — IP67/NEMA Type 4 with conduit entrance, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281A-F12Z-10A-CR | 281A-F12D-10A-CR | 281A-F12B-10A-CR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281A-F12Z-10B-CR | 281A-F12D-10B-CR | 281A-F12B-10B-CR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281A-F12Z-10C-CR | 281A-F12D-10C-CR | 281A-F12B-10C-CR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281A-F23Z-25D-CR | 281A-F23D-25D-CR | 281A-F23B-25D-CR |
Reversing starters — IP67/NEMA Type 4 with ArmorConnect power media connections, Up to 575V AC
| Current Rating [A] | kW | Hp | 24V DC Control Voltage |
120V AC Control Voltage |
240V AC Control Voltage |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
Cat. No. | Cat. No. | Cat. No. | |
| 0.24…1.2 | 0.18 | 0.37 | — | — | 0.5 | 0.5 | 281A-F12Z-10A-RR | 281A-F12D-10A-RR | 281A-F12B-10A-RR |
| 0.5…2.5 | 0.37 | 0.75 | 0.5 | 0.5 | 1 | 1.5 | 281A-F12Z-10B-RR | 281A-F12D-10B-RR | 281A-F12B-10B-RR |
| 1.1…5.5 | 1.1 | 2.2 | 1 | 1 | 3 | 3 | 281A-F12Z-10C-RR | 281A-F12D-10C-RR | 281A-F12B-10C-RR |
| 3.2…16 | 4 | 7.5 | 3 | 5 | 10 | 10 | 281A-F23Z-25D-RR | 281A-F23D-25D-RR | 281A-F23B-25D-RR |
Options — Factory Installed
Accessories
DeviceNet Media ∆
Industrial EtherNet Media∆
ArmorPoint® Media ♣
| Description | Length [m (ft)] | Cat. No. |
| ArmorPoint Bus Extension Cable including Terminating Resistor | 1 (3.3) | 280A-EXT1 |
| Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol | 1 (3.3) | 280A-EXTCABLE |
| ♣ ArmorPoint media is only available with an IP67/NEMA Type 4 rating. | ||
Sensor Media ♠
Motor and Brake Cables
Sealing Caps
|
|
| ArmorPoint | DeviceNet | EtherNet/IP | ||||
| Input | Output | Input | Output | Input | Output | |
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |
| Plastic Sealing Cap (M12)⋆ | — | 1485A-M12 | 1485A-M12 | 1485A-M12 | 1485A-M12 | 1485A-M12 |
| AC Micro Aluminum Sealing Cap⋆ | — | 889A-RMCAP | — | 889A-RMCAP | — | — |
| Stainless Steel Sealing Cap§ | — | 889AS-RMCAP | 1485AS-C3 | 889AS-RMCAP | — | — |
| Motor Connector Aluminum Sealing Cap (M22) for 10 A protection⋆ | — | 1485A-C1 | — | 1485A-C1 | — | 1485A-C1 |
| Motor Connector Aluminum Sealing Cap (M35) for 25 A protection⋆ | — | 889A-QMCAP | — | 889A-QMCAP | — | 889A-QMCAP |
| Dynamic Brake Connector (M22) | — | 1485A-C1 | — | 1485A-C1 | — | 1485A-C1 |
| Source/Control Brake Cap (M25) | — | ∆ | — | ∆ | — | ∆ |
| ⋆ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections. | ||||||
| § To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections. | ||||||
| ∆ Contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||
Handle and Cord Accessories
ArmorStart Bulletin 284 Option DB (IP20) Resistor Installation Dimensions
Dimensions are in millimeters (inches) and weights are in kilograms (pounds). Dimensions are not intended to be used for manufacturing purposes.
|
| Frame | Cat. No. | Weight [kg (lb)] |
| A | AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 | 1.1 (2.5) |
| B | AK-R2-030P1K2, AK-R2-120P1K2 | 2.7 (6) |
Recommended thermostat control wiring to prevent dynamic brake overheating
|
|
|
Peer-to-Peer Communications
|
(ZIP) Zone interlocking Parameters
The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP), which allow one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.
ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)
|
When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Cat. No. 280A-EXT1. The Cat. No. 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.
Note:Access to DeviceLogix programming is available with RSNetworx for DeviceNet.
|
If an additional ArmorStart Distributed Motor Controller is to be connected, the Cat. No. 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.
I/O Expansion with DeviceNet
If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Cat. No. 1738-ADNX ArmorPoint Distributed I/O product.
|
Bulletin 1738 ArmorPoint Distributed I/O Products
Digital Output Products
Digital Input Products
Analog Products
Power Supply Products
| Description | Cat. No. | |
|
|
ArmorPoint I/O Field Potential Distributor Module | 1738-FPD |
| 24V DC Expansion Power Supply | 1738-EP24DC | |
AC and Relay Products
Specialty Products
Adapter Products
Specifications
Connections
Bulletin 280E/281E ArmorStart with EtherNet/IP Communications
|
Bulletin 280D/281D ArmorStart with DeviceNet Communications
|
Bulletin 280A/281A ArmorStart for the ArmorPoint Backplane
|
Bulletin 280/281 ArmorStart DeviceNet Power and Control Terminals
|
| Terminal Designations | Number of Poles | Description |
| SM1⋆ | 2 | Safety Monitor Input |
| SM2⋆ | 2 | Safety Monitor Input |
| A1 (+) | 2 | Control Power Input |
| A2 (-) | 2 | Control Power Common |
| PE | 2 | Ground |
| 1/L1 | 2 | Line Power Phase A |
| 3/L3 | 2 | Line Power Phase B |
| 5/L5 | 2 | Line Power Phase C |
| ⋆ Only available with the Safety Monitor option. | ||
Bulletin 280/281 ArmorStart EtherNet Power and Control Terminals
|
| Terminal Designations | Number of Poles | Description |
| A1 (+) | 2 | Control Power Input |
| A2 (-) | 2 | Control Power Common |
| A3 (+) | 2 | Unswitched 24V Control |
| PE | 2 | Ground |
| 1/L1 | 2 | Line Power Phase A |
| 3/L3 | 2 | Line Power Phase B |
| 5/L5 | 2 | Line Power Phase C |
| ⋆ Only available with the Safety Monitor option. | ||
|
ArmorStart Receptacle Pin Outs
Receptacle Connections for ArmorPoint Interface (OUT)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: NC (no connection) |
Receptacle Connections for ArmorPoint Interface (IN)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: PE |
Receptacle Connections for DeviceNet Connector
|
Pin 1: Drain (no connection) Pin 2: +VDNET Pin 3: -VDNET Pin 4: CAN_H Pin 5: CAN_L |
Receptacle Connections for EtherNet/IP (M12)
|
Pin 1: Tx+ Pin 2: Rx+ Pin 3: Tx- Pin 4: Rx- |
Receptacle Connections for Input (M12)
|
Pin 1: +24V (A3 or DNET) Pin 2: Input 0 Pin 3: Common Pin 4: Input 1 Pin 5: NC (no connection) |
Receptacle Connections for Output, EtherNet/IP Version (M12)
|
Pin 1: NC (no connection) Pin 2: NC (no connection) Pin 3: Common Pin 4: Output +24V DC (A1) Pin 5: NC (no connection) |
Receptacle Connections for Output, DeviceNet or ArmorPoint Version (M12)
|
Pin 1: PE Pin 2: Return Pin 3: Relay out |
Receptacle Connections for Incoming Control Power
|
Pin 1: Unswitched (A3)(red) Pin 2: Common (A2)(black) Pin 3: PE (green) Pin 4: Not used (blank) Pin 5: Switched (A1)(blue) Pin 6: Not used (white) |
Receptacle Connections for Motor Connector -
3 Hp or less (M22)
|
Pin 1: T1 (black) Pin 2: T2 (white) Pin 3: T3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Motor Connector -
10 Hp (M35)
|
Pin 1: T1 (black) Pin 2: Ground (green/yellow) Pin 3: T3 (red) Pin 4: T2 (white) |
Receptacle Connections for Incoming 3-phase Power -
10 A Short Circuit Protection (M22)
|
Pin 1: L1 (black) Pin 2: L2 (white) Pin 3: L3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
25 A Short Circuit Protection (M35)
|
Pin 1: L1 (black) Pin 2: Ground (green/yellow) Pin 3: L3 (red) Pin 4: L2 (white) |
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…575V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Rated Operating Current Max. | 280_-___-10A-* | 1.2 A | |||||
| 280_-___-10B-* | 2.5 A | ||||||
| 280_-___-10C-* | 5.5 A | ||||||
| 280_-___-10D-* | 16 A | ||||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| 120V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | ||||||
| Short Circuit Protection | SCPD Performance Type 1 | Current Rating | Voltage | 480Y/277V | 480Y/480V | 600Y/347V | 600V |
| 0.24…1.2 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 0.5…2.5 A | |||||||
| 1.1…5.5 A | |||||||
| 3.2…16 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications | ||||||
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 2000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X§ | IP69K | ||
| Approximate Shipping Weight | 18.1 kg (40 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Power and Ground Terminals | |||
| Wire Size | Primary/Secondary terminal: (#16 …#10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary Terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | #18…#10 AWG | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Disconnect Lock Out | Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed 5/16 in. (8 mm) when closed, or damage will occur to disconnect guard. | ||
| EMC Emission Levels | Conducted Radio Frequency Emissions | 10V rms Communication cables 10V rms (PE) 150 KHz…80 MHz |
|
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | Electrostatic Discharge | 4 kV contact and 8 kV Air | |
| Radio Frequency Electromagnetic Field | 10V/m, 80 KHz…1 GHz 3V/m, 1.4 GHz…2.0 GHz 1V/m, 2.0 GHz…2.7 GHz |
||
| Fast Transient | 2 kV (Power) 2 kV (PE) 1 kV (Communications and control) |
||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Overload Rating | Overload Current Range | 280_-___-10A-* | 0.24…1.2 A |
| 280_-___-10B-* | 0.5…2.5 A | ||
| 280_-___-10C-* | 1.1…5.5 A | ||
| 280_-___-10D-* | 3.2…16 A | ||
| Trip Classes | 10, 15, 20 | ||
| Trip Rating | 120% of FLC setting | ||
| Number of poles | 3 | ||
| Standards Compliance | UL 508; CSA C22.2, No. 14; EN/IEC 60947-4; EN/IEC 60947-4-1; CE Marked per Low Voltage 2006/95/EC; EMC Directive 2004/108/EC; CCC; ODVA for EtherNet/IP; ODVA for DeviceNet | ||
| Certifications | cULus (File No. E3125, Guides NLDX, NLDX7) | ||
| § Used when caustic chemicals are used in food and beverage applications. The wash down rating is 1000 psi. | |||
| ArmorPoint and DeviceNet Versions — Control and I/O Power Requirements | |||||||
| Units | W/O HOA | W/ HOA | |||||
| Control Voltage | Volts | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC |
| Contactor (Pick Up) | Amps | 0.71 | 0.583 | 0.292 | 0.71 | 0.583 | 0.292 |
| Contactor (Hold In) | Amps | 0.063 | 0.075 | 0.038 | 0.063 | 0.075 | 0.038 |
| Total Control Power (Pick Up) | VA (W) | (17 W) | 70 | 70 | (21 W) | 83 | 84 |
| Total Control Power (Hold In) | VA (W) | (1.50 W) | 9 | 9 | (5.58 W) | 22 | 23 |
| External Devices powered by Control Voltage | |||||||
| Outputs (2) (1 A max. each) | Amps | 2 | 2 | 2 | 2 | 2 | 2 |
| Total Control (Pick Up) with max outputs | VA (W) | (65 W) | 310 | 550 | (73 W) | 336 | 579 |
| Total Control (Hold In) with max outputs | VA (W) | (50 W) | 249 | 489 | (58 W) | 275 | 518 |
| UL/NEMA | IEC | ||
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings (Sourced from Control Circuit) | Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| DeviceNet Specifications | DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | |
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| DeviceNet Input Current | 364 mA @ 11V DC - 4.0 W | ||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | Baud Rates | 125, 250, 500 kbps | |
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| Distance Maximum | 200 m (656 ft) @ 250 kbps | ||
| Distance Maximum | 100 m (328 ft) @ 500 kbps | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| EtherNet/IP Version - Control and I/O Power Requirements | ||||||
| A1/A2⋆ | A3/A2 | A1/A2⋆ | A3/A2 | A3/A2§ | ||
| Units | W/O HOA | W/ HOA | ||||
| Control Voltage | Volts | 24V DC | ||||
| Module Inrush | Amps | 0.92 | 0.30 | 1.09 | 0.125 | 0.295 |
| Module Steady | Amps | 0.06 | 0.30 | 0.23 | 0.125 | 0.295 |
| Total Control Power (Pick Up) | Watts | 22.08 | 7.20 | 26.16 | 3.00 | 7.08 |
| Total Control Power (Running) | Watts | 1.44 | 7.20 | 5.52 | 3.00 | 7.08 |
| ⋆ Add power requirements for outputs (1 A max.) to A1/A2. | ||||||
| Add power requirements for inputs (200 mA max.) to A3/A2. | ||||||
| § If A1 power is disconnected. | ||||||
| UL/NEMA | IEC | ||
| Input Ratings Sourced from control circuit - A3/A2 |
Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…26.4V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings Sourced from Control Circuit - A1/A2 |
Rated Operation Voltage | 26.4V DC | |
| Rate Insulation Voltage | 250V | ||
| Dielectric Withstand | 1500V AC (UL) | 2000V AC (IEC) | |
| Type of Control Circuit | Solid state sourcing output | ||
| Type of Current | 24V DC | ||
| Conventional Thermal Current Ith | 0.5 A each, 1 A max. combined | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| Load Types | Resistive or light inductive | ||
| Surge Suppression | Integrated diode, clamps @ 35V DC | ||
| Thermo-Protection | Integrated short circuit and over current protection | ||
| Maximum Cycle Rate | 30 operations/minute capacitive and inductive loads | ||
| Maximum Blocking Voltage | 35V DC | ||
| Maximum On-State Voltage @ Maximum Output | 1.5V DC | ||
| Maximum Off-State Leakage Current | 10 mA | ||
| Device Level Ring (DLR) | Beacon-based performance including IEEE 1588 end to end transparent clock | ||
| Maximum Nodes | 50 | ||
| Fault Recovery | Ring recovery time is less than 3 ms for a 50 node network | ||
| EtherNet Port | EtherNet Receptacles | 2 D-coded, 4-pin female M12 connecters | |
| Ports | Embedded switch with 2 ports | ||
| IP Address | DHCP enabled by default | ||
| DHCP Timeout | 30 seconds | ||
| Communication Rate | 10/100 Mbs with auto negotiate half duplex and full duplex | ||
| Data | |||
| Web Server | Embedded web server | ||
| Security | Login and password configurable | ||
| Support Simple Mail Transfer Protocol (SMTP) | |||
| Configuration | Status, diagnostics, and configuration tabs | ||
| Device Connections | Supports scheduled (Class 1) and unscheduled (Class 3 & UCMM) connections | ||
| 6 - Class 3 connections are supported simultaneously | |||
| Minimum of 1 - Class 1 or maximum of 2 - Class 1, CIP connections (1 exclusive owner, 1 input only and 1 listen only) are supported | |||
| Class 1 Connection API: 2…3200 ms, Class 3 Connection API: 100…10 000 ms | |||
| 20 ms Request Packet Interval (RPI) default | |||
| 3 concurrent Encapsulation sessions | |||
| TCP port supports 5 concurrent incoming connections | |||
Motor Overload Trip Curves
Motor overload current parameter provides class 10,15, and 20 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
|
|
|
Approximate Dimensions
Dimensions for IP67/NEMA Type 4 with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for IP67/NEMA Type 4 with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with Conduit Entrance
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|
Dimensions for NEMA Type 4X with ArmorConnect Connectivity
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.
|