Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Distributed Starters (Networked) > Bulletin 280/281 ArmorStart Distributed Motor Controller
Bulletin 280/281 ArmorStart Distributed Motor Controller
| Introduction | Standards Compliance and Certifications | Description | Catalog Number Explanation | Product Selection |
| Options — Factory Installed | Accessories | Specifications | Approximate Dimensions |
Connections
Bulletin 280E/281E ArmorStart with EtherNet/IP Communications
|
Bulletin 280D/281D ArmorStart with DeviceNet Communications
|
Bulletin 280A/281A ArmorStart for the ArmorPoint Backplane
|
Bulletin 280/281 ArmorStart DeviceNet Power and Control Terminals
|
| Terminal Designations | Number of Poles | Description |
| SM1⋆ | 2 | Safety Monitor Input |
| SM2⋆ | 2 | Safety Monitor Input |
| A1 (+) | 2 | Control Power Input |
| A2 (-) | 2 | Control Power Common |
| PE | 2 | Ground |
| 1/L1 | 2 | Line Power Phase A |
| 3/L3 | 2 | Line Power Phase B |
| 5/L5 | 2 | Line Power Phase C |
| ⋆ Only available with the Safety Monitor option. | ||
Bulletin 280/281 ArmorStart EtherNet Power and Control Terminals
|
| Terminal Designations | Number of Poles | Description |
| A1 (+) | 2 | Control Power Input |
| A2 (-) | 2 | Control Power Common |
| A3 (+) | 2 | Unswitched 24V Control |
| PE | 2 | Ground |
| 1/L1 | 2 | Line Power Phase A |
| 3/L3 | 2 | Line Power Phase B |
| 5/L5 | 2 | Line Power Phase C |
| ⋆ Only available with the Safety Monitor option. | ||
|
ArmorStart Receptacle Pin Outs
Receptacle Connections for ArmorPoint Interface (OUT)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: NC (no connection) |
Receptacle Connections for ArmorPoint Interface (IN)
|
Pin 1: CAN high Pin 2: Common Pin 3: +5V Pin 4: CAN low Pin 5: Enable out Pin 7: Common Pin 8: PE |
Receptacle Connections for DeviceNet Connector
|
Pin 1: Drain (no connection) Pin 2: +VDNET Pin 3: -VDNET Pin 4: CAN_H Pin 5: CAN_L |
Receptacle Connections for EtherNet/IP (M12)
|
Pin 1: Tx+ Pin 2: Rx+ Pin 3: Tx- Pin 4: Rx- |
Receptacle Connections for Input (M12)
|
Pin 1: +24V (A3 or DNET) Pin 2: Input 0 Pin 3: Common Pin 4: Input 1 Pin 5: NC (no connection) |
Receptacle Connections for Output, EtherNet/IP Version (M12)
|
Pin 1: NC (no connection) Pin 2: NC (no connection) Pin 3: Common Pin 4: Output +24V DC (A1) Pin 5: NC (no connection) |
Receptacle Connections for Output, DeviceNet or ArmorPoint Version (M12)
|
Pin 1: PE Pin 2: Return Pin 3: Relay out |
Receptacle Connections for Incoming Control Power
|
Pin 1: Unswitched (A3)(red) Pin 2: Common (A2)(black) Pin 3: PE (green) Pin 4: Not used (blank) Pin 5: Switched (A1)(blue) Pin 6: Not used (white) |
Receptacle Connections for Motor Connector -
3 Hp or less (M22)
|
Pin 1: T1 (black) Pin 2: T2 (white) Pin 3: T3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Motor Connector -
10 Hp (M35)
|
Pin 1: T1 (black) Pin 2: Ground (green/yellow) Pin 3: T3 (red) Pin 4: T2 (white) |
Receptacle Connections for Incoming 3-phase Power -
10 A Short Circuit Protection (M22)
|
Pin 1: L1 (black) Pin 2: L2 (white) Pin 3: L3 (red) Pin 4: Ground (green/yellow) |
Receptacle Connections for Incoming 3-phase Power -
25 A Short Circuit Protection (M35)
|
Pin 1: L1 (black) Pin 2: Ground (green/yellow) Pin 3: L3 (red) Pin 4: L2 (white) |
| Electrical Ratings | UL/NEMA | IEC | |||||
| Power Circuit | Rated Operation Voltage | 200…575V | 200…575V | ||||
| Rate Insulation Voltage | 600V | 600V | |||||
| Rated Impulsed Voltage | 6 kV | 6 kV | |||||
| Dielectric Withstand | 2200V AC | 2500V AC | |||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||||
| Utilization Category | N/A | AC-3 | |||||
| Protection Against Shock | N/A | IP2X | |||||
| Rated Operating Current Max. | 280_-___-10A-* | 1.2 A | |||||
| 280_-___-10B-* | 2.5 A | ||||||
| 280_-___-10C-* | 5.5 A | ||||||
| 280_-___-10D-* | 16 A | ||||||
| Control Circuit | Rated Operation Voltage | 24V DC (+10%, -15%) A2 (should be grounded at voltage source) | |||||
| 120V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source) | |||||||
| Rate Insulation Voltage | 250V | 250V | |||||
| Rated Impulsed Voltage | — | 4 kV | |||||
| Dielectric Withstand | 1500V AC | 2000V AC | |||||
| Overvoltage Category | — | III | |||||
| Operating Frequency | 50/60 Hz | ||||||
| Short Circuit Protection | SCPD Performance Type 1 | Current Rating | Voltage | 480Y/277V | 480Y/480V | 600Y/347V | 600V |
| 0.24…1.2 A | Sym. Amps RMS | 65 kA | 65 kA | 30 kA | 30 kA | ||
| 0.5…2.5 A | |||||||
| 1.1…5.5 A | |||||||
| 3.2…16 A | 30 kA | 30 kA | 30 kA | 30 kA | |||
| SCPD List | Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications | ||||||
| UL/NEMA | IEC | ||
| Environmental | Operating Temperature Range | -20…+40 °C (-4…+104 °F) | |
| Storage and Transportation Temperature Range |
25….+85 °C (13…+185 °F) | ||
| Altitude | 2000 m | ||
| Humidity | 5…95% (non-condensing) | ||
| Pollution Degree | 3 | ||
| Enclosure Ratings | NEMA 4/12/13 | IP67 | |
| NEMA 4X§ | IP69K | ||
| Approximate Shipping Weight | 18.1 kg (40 lb) | ||
| Mechanical | Resistance to Shock | ||
| Operational | 15 G | ||
| Non-Operational | 30 G | ||
| Resistance to Vibration | |||
| Operational | 1 G, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G, 0.38 mm (0.015 in.) displacement | ||
| Power and Ground Terminals | |||
| Wire Size | Primary/Secondary terminal: (#16 …#10 AWG) |
Primary/Secondary terminal: 1.5…4.0 mm2 |
|
| Tightening Torque | Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin |
Primary Terminal: (1.2 Nm) Secondary terminal: (0.5 Nm) |
|
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Control and Safety Monitor Inputs | |||
| Wire Size | #18…#10 AWG | 1.0…4.0 mm2 | |
| Tightening Torque | 6.2 lbin | 0.7 Nm | |
| Wire Strip Length | 0.35 in. (9 mm) | ||
| Disconnect Lock Out | Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed 5/16 in. (8 mm) when closed, or damage will occur to disconnect guard. | ||
| EMC Emission Levels | Conducted Radio Frequency Emissions | 10V rms Communication cables 10V rms (PE) 150 KHz…80 MHz |
|
| Radiated Emissions | Class A | ||
| EMC Immunity Levels | Electrostatic Discharge | 4 kV contact and 8 kV Air | |
| Radio Frequency Electromagnetic Field | 10V/m, 80 KHz…1 GHz 3V/m, 1.4 GHz…2.0 GHz 1V/m, 2.0 GHz…2.7 GHz |
||
| Fast Transient | 2 kV (Power) 2 kV (PE) 1 kV (Communications and control) |
||
| Surge Transient | 1 kV (12) L-L, 2 kV (2) L-N (earth) | ||
| Overload Rating | Overload Current Range | 280_-___-10A-* | 0.24…1.2 A |
| 280_-___-10B-* | 0.5…2.5 A | ||
| 280_-___-10C-* | 1.1…5.5 A | ||
| 280_-___-10D-* | 3.2…16 A | ||
| Trip Classes | 10, 15, 20 | ||
| Trip Rating | 120% of FLC setting | ||
| Number of poles | 3 | ||
| Standards Compliance | UL 508; CSA C22.2, No. 14; EN/IEC 60947-4; EN/IEC 60947-4-1; CE Marked per Low Voltage 2006/95/EC; EMC Directive 2004/108/EC; CCC; ODVA for EtherNet/IP; ODVA for DeviceNet | ||
| Certifications | cULus (File No. E3125, Guides NLDX, NLDX7) | ||
| § Used when caustic chemicals are used in food and beverage applications. The wash down rating is 1000 psi. | |||
| ArmorPoint and DeviceNet Versions — Control and I/O Power Requirements | |||||||
| Units | W/O HOA | W/ HOA | |||||
| Control Voltage | Volts | 24V DC | 120V AC | 240V AC | 24V DC | 120V AC | 240V AC |
| Contactor (Pick Up) | Amps | 0.71 | 0.583 | 0.292 | 0.71 | 0.583 | 0.292 |
| Contactor (Hold In) | Amps | 0.063 | 0.075 | 0.038 | 0.063 | 0.075 | 0.038 |
| Total Control Power (Pick Up) | VA (W) | (17 W) | 70 | 70 | (21 W) | 83 | 84 |
| Total Control Power (Hold In) | VA (W) | (1.50 W) | 9 | 9 | (5.58 W) | 22 | 23 |
| External Devices powered by Control Voltage | |||||||
| Outputs (2) (1 A max. each) | Amps | 2 | 2 | 2 | 2 | 2 | 2 |
| Total Control (Pick Up) with max outputs | VA (W) | (65 W) | 310 | 550 | (73 W) | 336 | 579 |
| Total Control (Hold In) with max outputs | VA (W) | (50 W) | 249 | 489 | (58 W) | 275 | 518 |
| UL/NEMA | IEC | ||
| Input Ratings | Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…25V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings (Sourced from Control Circuit) | Rated Operation Voltage | 240V AC/30V DC | 240V AC/30V DC |
| Rate Insulation Voltage | 250V | 250V | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Type of Control Circuit | Electromechanical relay | ||
| Type of Current | AC/DC | ||
| Conventional Thermal Current Ith | Total of both outputs £ 2 A | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| DeviceNet Specifications | DeviceNet Supply Voltage Rating | Range 11…25V DC, 24V DC nominal | |
| DeviceNet Input Current | 167 mA @ 24V DC - 4.0 W | ||
| DeviceNet Input Current | 364 mA @ 11V DC - 4.0 W | ||
| External Devices powered by DeviceNet | Sensors inputs 4 x 50 mA - total 200 mA | ||
| Total w/max Sensor Inputs (4) | 367 mA @ 24V DC - 8.8 W | ||
| DeviceNet Input Current Surge | 15 A for 250 ms | ||
| DeviceNet Communications | Baud Rates | 125, 250, 500 kbps | |
| Distance Maximum | 500 m (1630 ft) @ 125 kbps | ||
| Distance Maximum | 200 m (656 ft) @ 250 kbps | ||
| Distance Maximum | 100 m (328 ft) @ 500 kbps | ||
| ArmorPoint Ratings | Backplane Current Load | 400 mA | |
| EtherNet/IP Version - Control and I/O Power Requirements | ||||||
| A1/A2⋆ | A3/A2 | A1/A2⋆ | A3/A2 | A3/A2§ | ||
| Units | W/O HOA | W/ HOA | ||||
| Control Voltage | Volts | 24V DC | ||||
| Module Inrush | Amps | 0.92 | 0.30 | 1.09 | 0.125 | 0.295 |
| Module Steady | Amps | 0.06 | 0.30 | 0.23 | 0.125 | 0.295 |
| Total Control Power (Pick Up) | Watts | 22.08 | 7.20 | 26.16 | 3.00 | 7.08 |
| Total Control Power (Running) | Watts | 1.44 | 7.20 | 5.52 | 3.00 | 7.08 |
| ⋆ Add power requirements for outputs (1 A max.) to A1/A2. | ||||||
| Add power requirements for inputs (200 mA max.) to A3/A2. | ||||||
| § If A1 power is disconnected. | ||||||
| UL/NEMA | IEC | ||
| Input Ratings Sourced from control circuit - A3/A2 |
Rated Operation Voltage | 24V DC | |
| Input On-State Voltage Range | 10…26V DC | ||
| Input On-State Current | 3.0 mA @ 10V DC | ||
| 7.2 mA @ 24V DC | |||
| Input Off-State Voltage Range | 0…5V DC | ||
| Input Off-State Current | <1.5 mA | ||
| Input Filter — Software Selectable | |||
| Off to On | Settable from 0…64 ms in 1 ms increments | ||
| On to Off | Settable from 0…64 ms in 1 ms increments | ||
| Input Compatibility | N/A | IEC 1+ | |
| Number of Inputs | 4 | ||
| Sensor Source | |||
| Voltage Status Only | 11…26.4V DC from DeviceNet | ||
| Current Available | 50 mA max. per input, 200 mA total | ||
| Output Ratings Sourced from Control Circuit - A1/A2 |
Rated Operation Voltage | 26.4V DC | |
| Rate Insulation Voltage | 250V | ||
| Dielectric Withstand | 1500V AC (UL) | 2000V AC (IEC) | |
| Type of Control Circuit | Solid state sourcing output | ||
| Type of Current | 24V DC | ||
| Conventional Thermal Current Ith | 0.5 A each, 1 A max. combined | ||
| Type of Contacts | Normally open (N.O.) | ||
| Number of Contacts | 2 | ||
| Load Types | Resistive or light inductive | ||
| Surge Suppression | Integrated diode, clamps @ 35V DC | ||
| Thermo-Protection | Integrated short circuit and over current protection | ||
| Maximum Cycle Rate | 30 operations/minute capacitive and inductive loads | ||
| Maximum Blocking Voltage | 35V DC | ||
| Maximum On-State Voltage @ Maximum Output | 1.5V DC | ||
| Maximum Off-State Leakage Current | 10 mA | ||
| Device Level Ring (DLR) | Beacon-based performance including IEEE 1588 end to end transparent clock | ||
| Maximum Nodes | 50 | ||
| Fault Recovery | Ring recovery time is less than 3 ms for a 50 node network | ||
| EtherNet Port | EtherNet Receptacles | 2 D-coded, 4-pin female M12 connecters | |
| Ports | Embedded switch with 2 ports | ||
| IP Address | DHCP enabled by default | ||
| DHCP Timeout | 30 seconds | ||
| Communication Rate | 10/100 Mbs with auto negotiate half duplex and full duplex | ||
| Data | |||
| Web Server | Embedded web server | ||
| Security | Login and password configurable | ||
| Support Simple Mail Transfer Protocol (SMTP) | |||
| Configuration | Status, diagnostics, and configuration tabs | ||
| Device Connections | Supports scheduled (Class 1) and unscheduled (Class 3 & UCMM) connections | ||
| 6 - Class 3 connections are supported simultaneously | |||
| Minimum of 1 - Class 1 or maximum of 2 - Class 1, CIP connections (1 exclusive owner, 1 input only and 1 listen only) are supported | |||
| Class 1 Connection API: 2…3200 ms, Class 3 Connection API: 100…10 000 ms | |||
| 20 ms Request Packet Interval (RPI) default | |||
| 3 concurrent Encapsulation sessions | |||
| TCP port supports 5 concurrent incoming connections | |||
Motor Overload Trip Curves
Motor overload current parameter provides class 10,15, and 20 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.
|
|
|