Bulletin 283 ArmorStart Distributed Motor Controller

Product Overview


Click to enlarge - 280_Armorstart_SMC1hp_4c


Bulletin 283 ArmorStart Distributed Motor Controller


Standards Compliance and Certifications

Standards Compliance

UL 508
CSA C22.2, No. 14
EN/IEC 60947
EN/IEC 60947-1
CE Marked per Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/EC
CCC
ODVA for DeviceNet


Certifications

cULus (File No. E96956, Guides NMFT, NMFT7)

Mode of Operation

Soft Start

This method has the most general application. The motor is raised from an initial torque value to full voltage. This initial torque is adjustable to 15, 25, 35, or 65% of locked rotor torque. The motor voltage is gradually increased during the acceleration ramp time, which can be adjusted from 1…45 s.

Click to enlarge - 150-7_29-1


Current Limit Start

This starting mode is used when it is necessary to limit the maximum starting current. It can be adjusted for 150…450% of full load amps. Start times are selectable from 1…45 s.

Click to enlarge - 150-7_48-2


Selectable Kick Start

A kickstart, or boost, at the beginning of the start mode is intended to provide a current pulse of 450% of the full load current. The kickstart time is adjustable from 0.5…1.5 s. This allows the motor to develop additional torque at startup for loads which may need an initial boost.

Click to enlarge - 150-7_56-4


Soft Stop

The Soft Stop function can be used with applications that require an extended coast to rest. When enabled, the voltage ramp-down time can be selected from 1…90 s. The motor will stop when the motor voltage drops to a point where the load torque is greater than the motor torque.

Click to enlarge - 150-7_56-5


Overload Protection

The Bulletin 283 ArmorStart Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. The ArmorStart’s overload protection is programmable via the communication network providing the user with flexibility. The overload trip class allows for Class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.

Fault Diagnostics

Fault diagnostics capabilities built into the Bulletin 283 ArmorStart Distributed Motor Controller help you pinpoint a problem for easy troubleshooting and quick re-starting.



Factory-Installed Options

HOA Selector Keypad

The HOA Selector Keypad allows for local start/stop control.

Source Brake Contactor

An internal contactor is used to switch the electromechanical motor brake On/Off. The motor brake is powered from the main power circuit. A customer-accessible 3.0 A fuse is provided to protect the brake cable. Included is a 3-meter 3-pin cordset for connection to the motor brake, as standard.

Safety Monitor

The Safety Monitor Option allows for independent monitoring of the output status of the device. The function is implemented using a normally closed contact which complies with IEC 60947-5-1 for mechanically linked contacts. Two terminal blocks are provided as the inputs which maybe used with an external safety circuit. The external safety circuit monitors the status of the isolation contactor.

Catalog Number Explanation

283   D F   B   19Z 25   D CR Option 1 Option 2 Option 3
a    b    c    d    e    f    g    h    i    j    k

a
Bulletin Number
Code Description
283 Solid-State Starter

b
Communications
Code Description
D DeviceNet
A ArmorPoint

c
Enclosure Type
Code Description
F Type 4 (IP67)
S Type 4X

d
Input Line Voltage
Code Description
B 200…460V AC, 3-Phase, 50/60 Hz
C 200…575V AC, 3-Phase, 50/60 Hz

e
Controller Size/Control Voltage♣ 
24V DC 120V AC 240V AC
3Z 3D 3B
9Z 9D 9B
16Z 16D 16B
19Z 19D 19B

f
Short Circuit Protection
(Motor Circuit Protector)
Code Description
10 10 A Rated Device
25 25 A Rated Device

g
Overload Selection Current Range
Code Description
A 1.1…3.0 A
B 3.0…5.5 A
C 5.3…7.6 A
D 6.3…16.0 A

h
Control and 3-Phase Power Connections/Motor Cable Connection
(CR: Conduit/Round Media) or (RR: Round/Round Media)

Code
Description
Control Power 3-Phase Power Motor Cable
CR blank Conduit Entrance Conduit Entrance 3 m, unshielded cordset male 90°
CR W ⋆  Conduit Entrance Conduit Entrance No cable
RR blank Round Media (Male Receptacle) Round Media (Male Receptacle) 3 m, unshielded cordset male 90°
RR W ⋆  Round Media (Male Receptacle) Round Media (Male Receptacle) No cable

i
Option 1
Code Description
3 Hand/Off/Auto Selector Keypad

j
Option 2
Code Description
SB blank Source Brake Contactor
SB W ⋆  No cable

k
Option 3
Code Description
SM‡  Safety Monitor

⋆ See Accessories on Motor and Brake Cables for extended motor and source brake cable lengths.
‡ Not available with round media option (RR).
♣ See Product Selection tables for additional information.


Product Selection

Build a Catalog Number


DeviceNet Network Communication

IP67/NEMA Type 4 with conduit entrance, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.37 1.1 0.5 0.5 1.5 283D-FB3Z-10A-CR 283D-FB3D-10A-CR 283D-FB3B-10A-CR
3.0…5.5 1.5 2.2 1 1 3 283D-FB9Z-10B-CR 283D-FB9D-10B-CR 283D-FB9B-10B-CR
5.3…7.6 3 3 1.5 2 5 283D-FB16Z-10C-CR 283D-FB16D-10C-CR 283D-FB16B-10C-CR
6.3…16 4 5.5 3 5 10 283D-FB19Z-25D-CR 283D-FB19D-25D-CR 283D-FB19B-25D-CR
  

NEMA Type 4X with conduit entrance, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 283D-SB3Z-10A-CR 283D-SB3D-10A-CR 283D-SB3B-10A-CR
3.0…5.5 1.1 2.2 1 1 3 283D-SB9Z-10B-CR 283D-SB9D-10B-CR 283D-SB9B-10B-CR
5.3…7.6 1.5 3 1.5 2 5 283D-SB16Z-10C-CR 283D-SB16D-10C-CR 283D-SB16B-10C-CR
6.3…16 4 5.5 3 5 10 283D-SB19Z-25D-CR 283D-SB19D-25D-CR 283D-SB19B-25D-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 283D-FB3Z-10A-RR 283D-FB3D-10A-RR 283D-FB3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 283D-FB9Z-10B-RR 283D-FB9D-10B-RR 283D-FB9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 283D-FB16Z-25C-RR 283D-FB16D-10C-RR 283D-FB16B-10C-RR
6.3…16 4 5.5 3 5 10 283D-FB19Z-25D-RR 283D-FB19D-25D-RR 283D-FB19B-25D-RR
  

NEMA Type 4X with quick disconnects for ArmorConnect power media, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 283D-SB3Z-10A-RR 283D-SB3D-10A-RR 283D-SB3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 283D-SB9Z-10B-RR 283D-SB9D-10B-RR 283D-SB9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 283D-SB16Z-10C-RR 283D-SB16D-10C-RR 283D-SB16B-10C-RR
6.3…16 4 5.5 3 5 10 283D-SB19Z-25D-RR 283D-SB19D-25D-RR 283D-SB19B-25D-RR
  

IP67/NEMA Type 4 with conduit entrance, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283D-FC3Z-10A-CR 283D-FC3D-10A-CR 283D-FC3B-10A-CR
3.0…5.5 1.1 2.2 1 1 3 3 283D-FC9Z-10B-CR 283D-FC9D-10B-CR 283D-FC9B-10B-CR
5.3…7.6 1.5 3 1.5 2 5 5 283D-FC16Z-10C-CR 283D-FC16D-10C-CR 283D-FC16B-10C-CR
6.3…16 4 5.5 3 5 10 10 283D-FC19Z-25D-CR 283D-FC19D-25D-CR 283D-FC19B-25D-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283D-FC3Z-10A-RR 283D-FC3D-10A-RR 283D-FC3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 3 283D-FC9Z-10B-RR 283D-FC9D-10B-RR 283D-FC9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 5 283D-FC16Z-10C-RR 283D-FC16D-10C-RR 283D-FC16B-10C-RR
6.3…16 4 5.5 3 5 10 10 283D-FC19Z-25D-RR 283D-FC19D-25D-RR 283D-FC19B-25D-RR
  

NEMA Type 4X with conduit entrance, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283D-SC3Z-10A-CR 283D-SC3D-10A-CR 283D-SC3B-10A-CR
3.0…5.5 1.1 2.2 1 1 3 3 283D-SC9Z-10B-CR 283D-SC9D-10B-CR 283D-SC9B-10B-CR
5.3…7.6 1.5 3 1.5 2 5 5 283D-SC16Z-10C-CR 283D-SC16D-10C-CR 283D-SC16B-10C-CR
6.3…16 4 5.5 3 5 10 10 283D-SC19Z-25D-CR 283D-SC19D-25D-CR 283D-SC19B-25D-CR
  

NEMA Type 4X with quick disconnects for ArmorConnect power media, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283D-SC3Z-10A-RR 283D-SC3D-10A-RR 283D-SC3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 3 283D-SC9Z-10B-RR 283D-SC9D-10B-RR 283D-SC9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 5 283D-SC16Z-10C-RR 283D-SC16D-10C-RR 283D-SC16B-10C-RR
6.3…16 4 5.5 3 5 10 10 283D-SC19Z-25D-RR 283D-SC19D-25D-RR 283D-SC19B-25D-RR
  

ArmorPoint Bus Network Communication

IP67/NEMA Type 4 with conduit entrance, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.37 1.1 0.5 0.5 1.5 283A-FB3Z-10A-CR 283A-FB3D-10A-CR 283A-FB3B-10A-CR
3.0…5.5 1.5 2.2 1 1 3 283A-FB9Z-10B-CR 283A-FB9D-10B-CR 283A-FB9B-10B-CR
5.3…7.6 3 3 1.5 2 5 283A-FB16Z-10C-CR 283A-FB16D-10C-CR 283A-FB16B-10C-CR
6.3…16 4 5.5 3 5 10 283A-FB19Z-25D-CR 283A-FB19D-25D-CR 283A-FB19B-25D-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Up to 480V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
380/ 400/ 415V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 283A-FB3Z-10A-RR 283A-FB3D-10A-RR 283A-FB3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 283A-FB9Z-10B-RR 283A-FB9D-10B-RR 283A-FB9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 283A-FB16Z-10C-RR 283A-FB16D-10C-RR 283A-FB16B-10C-RR
6.3…16 4 5.5 3 5 10 283A-FB19Z-25D-RR 283A-FB19D-25D-RR 283A-FB19B-25D-RR
  

IP67/NEMA Type 4 with conduit entrance, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283A-FC3Z-10A-CR 283A-FC3D-10A-CR 283A-FC3B-10A-CR
3.0…5.5 1.1 2.2 1 1 3 3 283A-FC9Z-10B-CR 283A-FC9D-10B-CR 283A-FC9B-10B-CR
5.3…7.6 1.5 3 1.5 2 5 5 283A-FC16Z-10C-CR 283A-FC16B-10C-CR 283A-FC16B-10C-CR
6.3…16 4 5.5 3 5 10 10 283A-FC19Z-25D-CR 283A-FC19D-25D-CR 283A-FC19B-25D-CR
  

IP67/NEMA Type 4 with quick disconnects for ArmorConnect power media, Up to 575V AC

Current Rating [A] kW Hp 24V DC Control Voltage 120V AC Control Voltage 240V AC Control Voltage
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
Cat. No. Cat. No. Cat. No.
1.1…3.0 0.55 1.1 0.5 0.5 1.5 2 283A-FC3Z-10A-RR 283A-FC3D-10A-RR 283A-FC3B-10A-RR
3.0…5.5 1.1 2.2 1 1 3 3 283A-FC9Z-10B-RR 283A-FC9D-10B-RR 283A-FC9B-10B-RR
5.3…7.6 1.5 3 1.5 2 5 5 283A-FC16Z-10C-RR 283A-FC16B-10C-RR 283A-FC16B-10C-RR
6.3…16 4 5.5 3 5 10 10 283A-FC19Z-25D-RR 283A-FC19D-25D-RR 283A-FC19B-25D-RR
  

Options – Factory Installed

Description Cat. No. Modification
Click to enlarge - 283 HOA Hand/Off/Auto Selector Keypad -3
  Safety Monitor‡  -SM
  Supplied ArmorStart without motor cable -CRW
  Supplied ArmorStart with source brake cable -SB
  Supplied ArmorStart without source brake cable -SBW
  ArmorConnect Power Media Connectivity, ArmorStart supplied without motor cable -RRW
  
‡ Not available with round media option (RR).

Accessories

DeviceNet Media ∆ 

Description Length [m (ft)] Cat. No.
      Sealed
Click to enlarge - 280_281-13-1 KwikLink pigtail drops are Insulation Displacement Connector (IDC) with integral Class 1 round cables for interfacing devices or power supplies to flat cable 1 (3.3) 1485P-P1E4-B1-N5
2 (6.5) 1485P-P1E4-B2-N5
3 (9.8) 1485P-P1E4-B3-N5
6 (19.8) 1485P-P1E4-B6-N5
Click to enlarge - 1485P-P1N5-MN5KF_4c DeviceNet Mini- T-Port Tap Left Keyway 1485P-P1N5-MN5KM
Right Keyway 1485P-P1N5-MN5NF
Description Connector Cat. No.
Click to enlarge - 1485G-P#M5-R5_Product_Iso_4C Gray PVC Thin Cable Mini Straight Female
Mini Straight Male
1485G-P‡ N5-M5
Mini Straight Female
Mini Right Angle Male
1485G-P‡ W5-N5
Mini Right Angle Female
Mini Straight Male
1485G-P‡ M5-Z5
Mini Right Angle Female
Mini Straight Male
1485G-P‡ W5-Z5
Click to enlarge - 1485C-P#N5-M5_Product_Iso_4C Thick Cable Mini Straight Female
Mini Straight Male
1485C-P§ N5-M5
Mini Straight Female
Mini Right Angle Male
1485C-P§ W5-N5
Mini Right Angle Female
Mini Straight Male
1485C-P§ M5-Z5
Mini Right Angle Female
Mini Straight Male
1485C-P§ W5-Z5
Description Length m (ft) Cat. No.
Click to enlarge - 193DNCT_10_4c DeviceNet Configuration Terminal
Used to interface with objects on a DeviceNet network. Includes 1 m communications cable.
1 (3.3) 193-DNCT
Communication cable, color-coded bare leads 1 (3.3) 193-CB1
Communication cable, microconnector (male) 1 (3.3) 193-CM1
Panel Mount Adapter/Door Mount Bezel Kit 193-DNCT-BZ1
  
∆ See On-Machine Connectivity Catalog for complete cable selection information.
‡ Replace symbol with desired length in meters (Example: 1485G-P1N5-M5 for a 1 m cable). Standard cable lengths: 1, 2, 3, 4, 5, and 6 m.
§ Replace symbol with desired length in meters (Example: 1485C-P1N5-M5 for a 1 m cable). Standard cable lengths: 1, 2, 3, 4, 5, 6, 8, 10, 12, 18, 24, and 30 m.

Industrial EtherNet Media∆ 

Description Connector Type Unshielded
Cat. No.
M12, D-Code Patchcords and Cordsets
Click to enlarge - 1585D-M4TBDM Straight male to straight male 1585D-M4TBDM-⋆ 
Click to enlarge - 1585D-M4TBDE Straight male to right angle male 1585D-M4TBDE-⋆ 
Click to enlarge - 1585D-E4TBDE Right angle male to right angle male 1585D-E4TBDE-⋆ 
Click to enlarge - 1585D-M4TBDF Straight male to straight female 1585D-M4TBDF-⋆ 
Front Mount Receptacle
Click to enlarge - 1585D_D4TBJM1_Right_4C Front mount female to RJ45 1585D-D4TBJM-⋆ 
Transition Cable
Click to enlarge - 1585D-M4TBJM Straight male to RJ45 1585D-M4TBJM-⋆ 
  

Description Conductors Jacket Material Cable Type Jacket Color Cat. No.
RJ45 Patchcords
Click to enlarge - 1585J-M4_Product_4C 4-pair Riser PVC Unshielded twisted pair Teal 1585J-M8PBJM-⋆ 
High-flex TPE Teal 1585J-M8TBJM-⋆ 
M12 to RJ45 Bulkhead Adapter
Click to enlarge - 1585A-DD4JD_Product_Iso_4C
  • Transition from IP20 environment to IP67 environment

  • In-cabinet connectivity with RJ45 connector providing On-Machine solution with M12 D Code connector

  • Differential 100 W terminators used for unused pairs

  • Cat 5e
  • 1585A-DD4JD
      
    ⋆ Lengths available in 0.3, 0.6, 1, 2, 5, 10, 15, and additional increments of 5 m, up to 75 m.
    ∆ See On-Machine Connectivity Catalog for complete cable selection information.

    ArmorPoint® Media ♣ 

    Description Length [m (ft)] Cat. No.
    ArmorPoint Bus Extension Cable including Terminating Resistor 1 (3.3) 280A-EXT1
    Extension Cable to connect two ArmorStart Distributed Motor Controllers to ArmorPoint communication protocol 1 (3.3) 280A-EXTCABLE
      
    ♣  ArmorPoint media is only available with an IP67/NEMA Type 4 rating.

    Sensor Media ♠ 

    DeviceNet/ArmorPoint Communications
    Description ArmorStart I/O Connection Pin Count Connector Cat. No.
    Click to enlarge - 280_281-13-4 DC Micro Patchcord Input 4-pin Straight Female
    Straight Male
    889D-F4ACDM-♦ 
    Straight Female
    Right Angle Male
    889D-F4ACDE-♦ 
    Click to enlarge - 280_281-13-5 DC Micro V-Cable Input 4-pin Straight Female 879D-F4ACDM-♦ 
    Right Angle Female 879D-R4ACM-♦ 
    Click to enlarge - 280_281-13-6 AC Micro Patchcord Output 3-pin Straight Female
    Straight Male
    889R-F3AERM-♦ 
    Straight Female
    Right Angle Male
    889R-F3AERE-♦ 
      

    EtherNet/IP Communications
    Description ArmorStart I/O Connection Pin Count Connector Cat. No.
    Click to enlarge - 280_281-13-4 DC Micro Patchcord Input/Output 4-pin Straight Female
    Straight Male
    889D-F4ACDM-♦ 
    Straight Female
    Right Angle Male
    889D-F4ACDE-♦ 
    Click to enlarge - 280_281-13-5 DC Micro V-Cable Input 4-pin Straight Female 879D-F4ACDM-♦ 
    Right Angle Male 879D-R4ACM-♦ 
      
    ♠ See On-Machine Connectivity Catalog for complete cable selection information.
    ♦ Replace symbol with desired length in meters (Example: 889D-F4ACDM-1 for a 1 m cable). Standard cable lengths: 1, 2, 5, and 10 m.

    Motor and Brake Cables

    Click to enlarge - 280 cordset 90 degree  
    Description Cable Rating Length [m (ft)] Cat. No.
    Motor Cable Cordsets 90° M22 Motor Cordset IP67/NEMA Type 4 3 (9.8) 280-MTR22-M3
    6 (19.6) 280-MTR22-M6
    10 (32.8) 280-MTR22-M10
    14 (45.9) 280-MTR22-M14
    20 (65.6) 280-MTR22-M20
    90° M35 Motor Cordset IP67/NEMA Type 4 3 (9.8) 280-MTR35-M3
    6 (19.6) 280-MTR35-M6
    10 (32.8) 280-MTR35-M10
    14 (45.9) 280-MTR35-M14
    20 (65.6) 280-MTR35-M20
    90° M22 Motor Cordset IP69K/NEMA 4X 3 (9.8) 280S-MTR22-M3
    6 (19.6) 280S-MTR22-M6
    14 (45.9) 280S-MTR22-M14
    90° M35 Motor Cordset IP69K/NEMA 4X 6 (19.6) 280S-MTR35-M6
    14 (45.9) 280S-MTR35-M14
    Motor Cable Cordsets, High Flex⋆  90° M22 Motor Cordset IP67/NEMA Type 4 3 (9.8) 280-MTRF22-M3
    6 (19.6) 280-MTRF22-M6
    8 (26.2) 280-MTRF22-M8
    10 (32.8) 280-MTRF22-M10
    14 (45.9) 280-MTRF22-M14
    20 (65.6) 280-MTRF22-M20
    Motor Cable Cordsets,
    Shielded (VFD)
    90° M22 Motor Cordset IP67/NEMA Type 4 3 (9.8) 284-MTRS22-M3
    6 (19.6) 284-MTRS22-M6
    14 (45.9) 284-MTRS22-M14
    90° M22 Motor Cordset IP69K/NEMA Type 4X 3 (9.8) 284S-MTRS22-M3
    6 (19.6) 284S-MTRS22-M6
    14 (45.9) 284S-MTRS22-M14
    Extended Source/Control Brake Cable Cordsets 90° M25 Source Brake Cable IP67/NEMA Type 4 6 (19.6) 285-BRC25-M6
    14 (45.9) 285-BRC25-M14
    IP69K 6 (19.6) 285S-BRC25-M6
    14 (45.9) 285S-BRC25-M14
    Extended Source/Control Brake Cable Cordsets, High Flex⋆  90° M25 Source Brake Cable IP67/NEMA Type 4 3 (9.8) 285-BRCF25-M3
    6 (19.6) 285-BRCF25-M6
    10 (32.8) 285-BRCF25-M10
    14 (45.9) 285-BRCF25-M14
    20 (65.6) 285-BRCF25-M20
    Dynamic Brake Cables M22 Dynamic Brake Cable (DB Option) IP67/NEMA Type 4 3 (9.8) 285-DBK22-M3
    IP69K 3 (9.8) 285S-DBK22-M3
    Click to enlarge - 280_patchcord_90_degree  
    Description Description Cable Rating Length [m (ft)] Cat. No.
    Motor Cable Patchcords 90° Male/Straight Female M22 IP67/NEMA Type 4 1 (3.3) 280-MTR22-M1D
    3 (9.8) 280-MTR22-M3D
    90° Male/Straight Female M35 IP67/NEMA Type 4 1 (3.3) 280-MTR35-M1D
    3 (9.8) 280-MTR35-M3D
    90° Male/Straight Female M22 IP69K/NEMA Type 4X 1 (3.3) 280S-MTR22-M1D
    3 (9.8) 280S-MTR22-M3D
    90° Male/Straight Female M35 IP69K/NEMA Type 4X 1 (3.3) 280S-MTR35-M1D
    3 (9.8) 280S-MTR35-M3D
    Motor Cable Patchcords, Shielded (VFD) 90° Male/Straight Female M22 IP67/NEMA Type 4 1 (3.3) 284-MTRS22-M1D
    3 (9.8) 284-MTRS22-M3D
    90° Male/Straight Female M22 IP69K/NEMA Type 4X 1 (3.3) 284S-MTRS22-M1D
    3 (9.8) 284S-MTRS22-M3D
      
    ⋆ 14 million flex cycles, bend radius is maximum 8X the cable diameter (0.362 in. OD).

    Sealing Caps

    Click to enlarge - 1485A-C_Product2_GS Click to enlarge - 889A_sealcaps

      ArmorPoint DeviceNet EtherNet/IP
    Input Output Input Output Input Output
    Cat. No. Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
    Plastic Sealing Cap (M12)⋆  1485A-M12 1485A-M12 1485A-M12 1485A-M12 1485A-M12
    AC Micro Aluminum Sealing Cap⋆  889A-RMCAP 889A-RMCAP
    Stainless Steel Sealing Cap§  889AS-RMCAP 1485AS-C3 889AS-RMCAP
    Motor Connector Aluminum Sealing Cap (M22) for 10 A protection⋆  1485A-C1 1485A-C1 1485A-C1
    Motor Connector Aluminum Sealing Cap (M35) for 25 A protection⋆  889A-QMCAP 889A-QMCAP 889A-QMCAP
    Dynamic Brake Connector (M22) 1485A-C1 1485A-C1 1485A-C1
    Source/Control Brake Cap (M25) ∆  ∆  ∆ 
     
    ⋆ To achieve IP67 rating, sealing caps must be installed on all unused I/O connections.
    § To achieve IP69K/NEMA 4X rating, sealing caps must be installed on all unused I/O connections.
    ∆ Contact your local Rockwell Automation sales office or Allen-Bradley distributor.

    Handle and Cord Accessories

      Description Cat. No.
    Click to enlarge - 140M-C-M3_C Locking Tag
  • Padlock attachment to the lockable handles

  • Up to three padlocks 4…8 mm (5/16 in.) Æ shackle
  • 140M-C-M3
    Click to enlarge - 280-DISHDL Replacement At-Motor Disconnect Handle Kit
    includes: (1) handle, (1) guard, and (3) screws
    280-DISHDL
    Cord grips for ArmorStart devices with 10 A short circuit protection rating
    Click to enlarge - 2931NM_ArmorStartCordgrip 3/4 in. Strain relief cord connector and 3/4 in. lock nut
    Cable range: 0.31…0.56 in.
    Used with control power media cordset -
    Example cat. no.: 889N-M65GF-M2
    Thomas & Betts Cord Grip Cat. No. 2931NM
    1 in. Strain relief cord connector and 1 in. lock nut
    Cable range: 0.31…0.56 in.
    Used with control power media cordset -
    Example cat. no.: 280-PWR22G-M
    Thomas & Betts Cord Grip Cat. No. 2940NM
    Cord grips for ArmorStart devices with 25 A short circuit protection rating
    Click to enlarge - 2931NM_ArmorStartCordgrip 3/4 in. Strain relief cord connector and 3/4 in. lock nut
    Cable range: 0.31…0.56 in.
    Used with control power media cordset -
    Example cat. no.: 889N-M65GF-M2
    Thomas & Betts Cord Grip Cat. No. 2931NM
    1 in. Strain relief cord connector and 1 in. lock nut
    Cable range: 0.70…0.95 in.
    Used with three-phase power media cordset -
    Example cat. no.: 280-PWR35G-M1
    Thomas & Betts Cord Grip Cat. No. 2942NM
      

    ArmorStart Bulletin 284 Option DB (IP20) Resistor Installation Dimensions

    Dimensions are in millimeters (inches) and weights are in kilograms (pounds). Dimensions are not intended to be used for manufacturing purposes.

    Click to enlarge - dbresdim


    Frame Cat. No. Weight
    [kg (lb)]
    A AK-R2-091P500, AK-R2-047P500, AK-R2-360P500 1.1 (2.5)
    B AK-R2-030P1K2, AK-R2-120P1K2 2.7 (6)
      

    Recommended thermostat control wiring to prevent dynamic brake overheating

    Click to enlarge - 284_DB_thermostat


    Click to enlarge - 284_DB_thermostat_powerdiag


    Click to enlarge - 284_DB_thermostat_wirediag


    Peer-to-Peer Communications

    Click to enlarge - armorstart3_ZIP ZONE diagram


    (ZIP) Zone interlocking Parameters

    The Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower (0.5…10 Hp) motored conveyors. The ArmorStart Distributed Motor Controllers have built-in DeviceNet Communications, DeviceLogix technology, and the added Zone Interlocking Parameters (ZIP), which allow one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in a merge, diverter, and accumulation conveyor applications.


    ArmorStart to ArmorPoint Connectivity - (Networks other than DeviceNet)

    Click to enlarge - armorstart1


    When connecting to the Bulletin 1738 ArmorPoint Distributed I/O product, a network adapter and at least one ArmorPoint Digital Output, Digital Input, Analog, AC and Relay product, or Specialty product must be selected. The ArmorPoint Distributed I/O can accomodate up to 63 modules per network node. The cable that connects the ArmorPoint Distributed I/O product to the ArmorStart Distributed Motor Controller is the Cat. No. 280A-EXT1. The Cat. No. 280A-EXT1 includes an ArmorPoint bus extension cable and a network terminating resistor.

    Note:Access to DeviceLogix programming is available with RSNetworx for DeviceNet.


    Click to enlarge - armorstart2


    If an additional ArmorStart Distributed Motor Controller is to be connected, the Cat. No. 280A-EXTCABLE will be required. A maximum of two ArmorStart Distributed Motor Controllers can be connected to the Bulletin 1738 Distributed I/O.

    I/O Expansion with DeviceNet

    If the I/O capability of the Bulletin 280/281D ArmorStart Distributed Motor Controller needs to be expanded beyond the standard four inputs and two outputs, the ArmorStart Distributed Motor Controller with the DeviceNet communication protocol can be configured to the ADNX Architecture, in which the ArmorStart is part of the DeviceNet subnet, using the Cat. No. 1738-ADNX ArmorPoint Distributed I/O product.

    Click to enlarge - armorpoint_1738_explogic


    Bulletin 1738 ArmorPoint Distributed I/O Products

    Digital Output Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_dig_out 24V DC, eight source output with eight M12 connectors 1738-OB8EM12
    24V DC, eight source output with eight M8 connectors 1738-OB8EM8
    24V DC, four source output with four M12 connectors 1738-OB4EM12
    24V DC, four source output with four M8 connectors 1738-OB4EM8
    24V DC, two source output with two M12 connectors 1738-OB2EM12
    24V DC, two source output, 2 A prot. with two M12 connectors 1738-OB2EPM12
    24V DC, four sink output with four M12 connectors 1738-OV4EM12
      

    Digital Input Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_dig_in 24V DC, eight sink input with four M12 connectors, two points per connector 1738-IB8M12
    24V DC, eight sink input with eight M8 connectors 1738-IB8M8
    24V DC, eight sink input with one M23 connector 1738-IB8M23
    24V DC, four sink input with four M12 connectors 1738-IB4M12
    24V DC, four sink input with four M8 connectors 1738-IB4M8
    24V DC, two sink input with two M12 connectors 1738-IB2M12
    24V DC, four source input with four M12 connectors 1738-IV4M12
      

    Analog Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_anlg 24V DC analog current input with two M12 connectors 1738-IE2CM12
    24V DC analog voltage input with two M12 connectors 1738-IE2VM12
    24V DC analog current output with two M12 connectors 1738-OE2CM12
    24V DC analog voltage output with two M12 connectors 1738-OE2VM12
    24V DC, two thermocouple input 1738-IT2IM12
    24V DC, two RTD input 1738-IR2M12
      

    Power Supply Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_ps ArmorPoint I/O Field Potential Distributor Module 1738-FPD
    24V DC Expansion Power Supply 1738-EP24DC
      

    AC and Relay Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_ac_and_relay 24V DC Coil, N.O. DPST relay with two M12 connectors 1738-OW4M12
    24V DC Coil, N.O. DPST relay with two AC M12 connectors 1738-OW4M12AC
    120V AC, two input with two AC 4-pin M12 connectors 1738-IA2M12AC4
    120V AC, two input with two AC 3-pin M12 connectors 1738-IA2M12AC3
    120/230V AC, two output with two AC 3-pin M12 connectors 1738-OA2M12AC3
      

    Specialty Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_specialty ArmorPoint I/O RS-232 ASCII Serial Interface Module 1738-232ASCM12
    ArmorPoint I/O RS-485 ASCII Serial Interface Module 1738-485ASCM12
    24V DC Very High Speed Counter Module 1738-VHSC24M23
    ArmorPoint 5V Encoder/Counter Module 1738-IJM23
    ArmorPoint Synchronous Serial Interface Module with Absolute Encoder 1738-SSIM23
      

    Adapter Products

    Description Cat. No.
    Click to enlarge - armorpoint_1738_adapters ArmorPoint DeviceNet Adapter Module, Drop or Pass-through, with male and female M12 connectors 1738-ADN12
    ArmorPoint DeviceNet Adapter Module, Drop only, with male M18 connector 1738-ADN18
    ArmorPoint DeviceNet Adapter Module, Drop or Pass-through, with male and female M18 connectors 1738-ADN18P
    ArmorPoint DeviceNet 24V DC Adapter Module with subnet expansion 1738-ADNX
    ArmorPoint Redundant ControlNet Adapter Module 1738-ACNR
    ArmorPoint Ethernet/IP 10/100 Mbps Adapter Module 1738-AENT
    ArmorPoint I/O 2-Port EtherNet/IP Adapter (star, tree, linear, or ring topology)⋆  1738-AENTR
      
    ⋆ Requires a 24V DC expansion power unit (cat. no. 1738-EP24DC) when two ArmorStarts are connected to point bus.

    Specifications

    Connections

    Bulletin 283D ArmorStart with DeviceNet Communications

    Click to enlarge - 283D_front_callouts


    Bulletin 283A ArmorStart for the ArmorPoint Backplane

    Click to enlarge - 283A_front_callouts


    Bulletin 283 ArmorStart Power and Control Terminals

    Click to enlarge - 284_PowerControlTerminals


    Terminal Designations Number of Poles Description
    SM1⋆  2 Safety Monitor Input
    SM2⋆  2 Safety Monitor Input
    A1 (+) 2 Control Power Input
    A2 (-) 2 Control Power Common
    PE 2 Ground
    1/L1 2 Line Power Phase A
    3/L3 2 Line Power Phase B
    5/L5 2 Line Power Phase C
     
    ⋆ Only available with the Safety Monitor option.

    ArmorStart Receptacle Pin Outs

    Receptacle Connections for ArmorPoint Interface (OUT)

    Click to enlarge - 280_pinout_ArmorPointOut Pin 1: CAN high
    Pin 2: Common
    Pin 3: +5V
    Pin 4: CAN low
    Pin 5: Enable out
    Pin 7: Common
    Pin 8: NC (no connection)

    Receptacle Connections for ArmorPoint Interface (IN)

    Click to enlarge - 280_pinout_ArmorPointIn Pin 1: CAN high
    Pin 2: Common
    Pin 3: +5V
    Pin 4: CAN low
    Pin 5: Enable out
    Pin 7: Common
    Pin 8: PE

    Receptacle Connections for DeviceNet Connector

    Click to enlarge - 280_pinout_DNet Pin 1: Drain (no connection)
    Pin 2: +VDNET
    Pin 3: -VDNET
    Pin 4: CAN_H
    Pin 5: CAN_L

    Receptacle Connections for Input (M12)

    Click to enlarge - 280_pinout_AnalogIn Pin 1: +24V (A3 or DNET)
    Pin 2: Input 0
    Pin 3: Common
    Pin 4: Input 1
    Pin 5: NC (no connection)

    Receptacle Connections for Output, DeviceNet or ArmorPoint Version (M12)

    Click to enlarge - 280_pinout_DNetOutput Pin 1: PE
    Pin 2: Return
    Pin 3: Relay out

    Receptacle Connections for Incoming Control Power

    Click to enlarge - 280_pinout_ControlPowerIn Pin 1: Unswitched (A3)(red)
    Pin 2: Common (A2)(black)
    Pin 3: PE (green)
    Pin 4: Not used (blank)
    Pin 5: Switched (A1)(blue)
    Pin 6: Not used (white)

    Receptacle Connections for Source Brake

    Click to enlarge - 280_pinout_SourceContactor Pin 1: L1 (black)
    Pin 2: GND (green/yellow)
    Pin 3: L2 (white)

    Receptacle Connections for Motor Connector -
    5 Hp or less (M22)


    Click to enlarge - 280_pinout_Motor2HP Pin 1: T1 (black)
    Pin 2: T2 (white)
    Pin 3: T3 (red)
    Pin 4: Ground (green/yellow)

    Receptacle Connections for Motor Connector -
    10 Hp (M35)


    Click to enlarge - 280_pinout_Motor3HP Pin 1: T1 (black)
    Pin 2: Ground (green/yellow)
    Pin 3: T3 (red)
    Pin 4: T2 (white)

    Receptacle Connections for Incoming 3-phase Power -
    10 A Short Circuit Protection (M22)


    Click to enlarge - 280_pinout_3phPowerInM22 Pin 1: L1 (black)
    Pin 2: L2 (white)
    Pin 3: L3 (red)
    Pin 4: Ground (green/yellow)

    Receptacle Connections for Incoming 3-phase Power -
    25 A Short Circuit Protection (M35)


    Click to enlarge - 280_pinout_3phPowerInM35 Pin 1: L1 (black)
    Pin 2: Ground (green/yellow)
    Pin 3: L3 (red)
    Pin 4: L2 (white)

    Motor Overload Trip Curves

    Motor overload current parameter provides class 10 overload protection. Ambient insensitivity is inherent in the electronic design of the overload.

    Click to enlarge - 280_281-16-2


    Electrical Ratings UL/NEMA IEC
    Power Circuit Rated Operation Voltage 200…575Y 200…575V
    Rate Insulation Voltage 600V 500V
    Rated Impulsed Voltage 6 kV 6 kV
    Dielectric Withstand 2200V AC 2500V AC
    Operating Frequency 50/60 Hz 50/60 Hz
    Utilization Category N/A AC-3
    Protection Against Shock N/A IP2X
    Rated Operating Current Max. 280_-___-10A-* 3.0 A  
    280_-___-10B-* 5.5 A  
    280_-___-10C-* 7.6 A  
    280_-___-10D-* 16 A  
    Control Circuit Rated Operation Voltage 24V DC (+10%, -15%) A2 (should be grounded at voltage source)
    120V AC (+10%, -15%) A2 (should be grounded at voltage source)
    240V AC (+10%, -15%) A2 (should be grounded at voltage source)
    Rated Insulation Voltage 250V 250V
    Rated Impulsed Voltage 4 kV
    Dielectric Withstand 1500V AC 2000V AC
    Overvoltage Category III
    Operating Frequency 50/60 Hz
    Short Circuit Protection SCPD Performance Type 1 Current Rating Voltage 480Y/277V 480Y/480V 600Y/347V 600V
    1.1…3.0 A Sym. Amps RMS 65 kA 65 kA 30 kA 30 kA
    3.0…5.5 A
    5.3…7.6 A
    6.3…16 A 30 kA 30 kA 30 kA 30 kA
    SCPD List Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications
      

    Power Requirements
      Units  
    Control Voltage (Nom) Volts 24V DC 120V AC 240V AC
    Power supply (Nom) Amps 0.170 0.110 0.060
    Total Control Power (Starting/Stopping) VA (W) (90 W) 35 35
    Total Control Power (Running) VA (W) (8 W) 28 28
    External Devices powered by Control Voltage
    Outputs (2) (1 A max. each) Amps 2 2 2
    Total Control (Pick Up) with max outputs VA (W) (138 W) 275 515
    Total Control (Hold In) with max outputs VA (W) (56 W) 268 508
      

    Input Ratings Rated Operation Voltage 24V DC
    Rated Insulation Voltage 1500V AC
    Input On-State Voltage Range 10…26V DC
    Input On-State Current 3.0 mA @ 10V DC
    7.2 mA @ 24V DC
    Input Off-State Voltage Range 0…5V DC
    Input Off-State Current <1.5 mA
    Input Filter — Software Selectable
    Off to On Settable from 0…64 ms in 1 ms increments
    On to Off Settable from 0…64 ms in 1 ms increments
    Input Compatibility N/A IEC 1+
    Number of Inputs 4
    Sensor Source
    Voltage Status Only 11…25V DC from DeviceNet
    Current Available 50 mA max. per input, 200 mA total
    Output Ratings (Sourced from Control Circuit) Rated Operation Voltage 250V AC/30V DC 250V AC/30V DC
    Rated Insulation Voltage 250V 250V
    Dielectric Withstand 1500V AC 2000V AC
    Operating Frequency 50/60 Hz 50/60 Hz
    Type of Control Circuit Electromechanical relay
    Type of Current AC/DC
    Conventional Thermal Current Ith Total of both outputs £ 2 A
    Type of Contacts Normally open (N.O.)
    Number of Contacts 2
     

      UL/NEMA IEC
    Environmental Operating Temperature Range -20…+40 °C (-4…+104 °F)
    Storage and Transportation
    temperature range
    –25….+85 °C (–13…+185 °F)
    Altitude 2000 m
    Humidity 5…95% (non-condensing)
    Pollution Degree 3
    Enclosure Ratings NEMA 4/12/13 IP67
    Enclosure Ratings NEMA 4X IP69K
    Approximate Shipping Weight 16.8 kg (37 lb)
    Mechanical Resistance to Shock
    Operational 15 G
    Non-Operational 30 G
    Resistance to Vibration
    Operational 1 G, 0.15 mm (0.006 in.) displacement
    Non-Operational 2.5 G, 0.38 mm (0.015 in.) displacement
    Power and Ground Terminals
    Wire Size Primary/Secondary terminal:
    (#16 …#10 AWG)
    Primary/Secondary terminal:
    1.5…4.0 mm2
    Tightening Torque Primary terminal:
    10.8 lb•in
    Secondary terminal:
    4.5 lb•in
    Primary terminal:
    (1.2 N•m)
    Secondary terminal:
    (0.5 N•m)
    Wire Strip Length 0.35 in. (9 mm)
    Control and Safety Monitor Inputs
    Wire Size (18…10 AWG) 1.0…4.0 mm2
    Tightening Torque 6.2 lb•in 0.7 N•m
    Wire Strip Length 0.35 in. (9 mm)
    Disconnect Lock Out Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed 5/16 in. (8 mm) when closed, or damage will occur to disconnect guard.
    Other Rating EMC Emission Levels
    Conducted Radio Frequency Emissions Class A
    Radiated Emissions Class A
    EMC Immunity Levels
    Electrostatic Discharge 4 kV contact and 8 kV Air
    Radio Frequency Electromagnetic Field 10V/m
    Fast Transient 2 kV
    Surge Transient 1 kV (12) L-L, 2 kV (2) L-N (earth)
    Overload Characteristics
    Overload Current Range 1.1…3.0 A
    3.0…5.5 A
    5.3…7.6 A
    6.3…16 A
    Trip Class 10
    Trip Rating 120% of FLC setting
    Number of Poles 3
    DeviceNet Specifications
    DeviceNet Supply Voltage Rating Range 11…25V DC, 24V DC nominal
    DeviceNet Input Current 167 mA @ 24V DC - 4.0 W
    364 mA @ 11V DC - 4.0 W
    External Devices powered by DeviceNet Sensors inputs 4 x 50 mA - total 200 mA
    Total w/max Sensor Inputs (4) 367 mA @ 24V DC - 8.8 W
    DeviceNet Input Current Surge 15 A for 250 ms
    DeviceNet Communications
    Baud Rates 125, 250, 500 kbps
    Distance Maximum 500 m (1630 ft) @ 125 kbps
    200 m (656 ft) @ 250 kbps
    100 m (328 ft) @ 500 kbps
    ArmorPoint Backplane Current Load 400 mA
    Standards Compliance   UL 508; CSA C22.2, No. 14; EN/IEC 60947; EN/IEC 60947-1; CE Marked per Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/EC; CCC; ODVA for DeviceNet
    Certifications   cULus (File No. E96956, Guides NMFT, NMFT7)
      

    Approximate Dimensions

    Dimensions for IP67/NEMA Type 4 with Conduit Entrance

    Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

    Click to enlarge - 280 series c std smc sht1


    Dimensions for IP67/NEMA Type 4 with ArmorConnect Connectivity

    Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

    Click to enlarge - 280 series c std smc sht2


    Dimensions for NEMA Type 4X with Conduit Entrance

    Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

    Click to enlarge - 280 series c 4x smc sht1


    Dimensions for NEMA Type 4X with ArmorConnect Connectivity

    Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

    Click to enlarge - 280 series c 4x smc sht2