| Electrical Ratings
|
UL/NEMA
|
IEC
|
| Power Circuit
|
Rated Operation Voltage
|
200…575Y
|
200…575V
|
| Rate Insulation Voltage
|
600V
|
500V
|
| Rated Impulsed Voltage
|
6 kV
|
6 kV
|
| Dielectric Withstand
|
2200V AC
|
2500V AC
|
| Operating Frequency
|
50/60 Hz
|
50/60 Hz
|
| Utilization Category
|
N/A
|
AC-3
|
| Protection Against Shock
|
N/A
|
IP2X
|
| Rated Operating Current Max.
|
3.0 A
|
| 5.5 A
|
| 7.6 A
|
| 16 A
|
| Control Circuit
|
Rated Operation Voltage
|
24V DC (+10%, -15%) A2 (should be grounded at voltage source)
|
|
|
120V AC (+10%, -15%) A2 (should be grounded at voltage source)
|
| 240V AC (+10%, -15%) A2 (should be grounded at voltage source)
|
| Rated Insulation Voltage
|
250V
|
250V
|
| Rated Impulsed Voltage
|
—
|
4 kV
|
| Dielectric Withstand
|
1500V AC
|
2000V AC
|
| Overvoltage Category
|
—
|
III
|
| Operating Frequency
|
50/60 Hz
|
| Short Circuit Protection
|
SCPD Performance Type 1
|
Current Rating
|
Voltage
|
480Y/277V
|
480/480V
|
600Y/347V
|
600V
|
| 1.1…3.0 A
|
Sym. Amps RMS
|
65 kA
|
65 kA
|
30 kA
|
30 kA
|
| 3.0…5.5 A
|
| 5.3…7.6 A
|
| 6.3…16 A
|
30 kA
|
30 kA
|
30 kA
|
30 kA
|
| SCPD List
|
Size per NEC Group Motor
|
—
|
|
|
| Power Requirements
|
|
|
Units
|
|
| Control Voltage (Nom)
|
Volts
|
24V DC
|
120V AC
|
240V AC
|
| Power supply (Nom)
|
Amps
|
0.170
|
0.110
|
0.060
|
| Total Control Power (Starting/Stopping)
|
VA (W)
|
(90 W)
|
35
|
35
|
| Total Control Power (Running)
|
VA (W)
|
(8 W)
|
28
|
28
|
| External Devices powered by Control Voltage
|
| Outputs (2) (1 A max. each)
|
Amps
|
2
|
2
|
2
|
| Total Control (Pick Up) with max outputs
|
VA (W)
|
(138 W)
|
275
|
515
|
| Total Control (Hold In) with max outputs
|
VA (W)
|
(56 W)
|
268
|
508
|
|
|
| Input Ratings
|
Rated Operation Voltage
|
24V DC
|
|
|
Rated Insulation Voltage
|
1500V AC
|
| Input On-State Voltage Range
|
10…26V DC
|
| Input On-State Current
|
3.0 mA @ 10V DC
|
| 7.2 mA @ 24V DC
|
| Input Off-State Voltage Range
|
0…5V DC
|
| Input Off-State Current
|
<1.5 mA
|
| Input Filter — Software Selectable
|
| Off to On
|
Settable from 0…64 ms in 1 ms increments
|
| On to Off
|
Settable from 0…64 ms in 1 ms increments
|
| Input Compatibility
|
N/A
|
IEC 1+
|
| Number of Inputs
|
4
|
| Sensor Source
|
| Voltage Status Only
|
11…25V DC from DeviceNet
|
| Current Available
|
50 mA max. per input, 200 mA total
|
| Output Ratings (Sourced from Control Circuit)
|
Rated Operation Voltage
|
250V AC/30V DC
|
250V AC/30V DC
|
|
|
Rated Insulation Voltage
|
250V
|
250V
|
| Dielectric Withstand
|
1500V AC
|
2000V AC
|
| Operating Frequency
|
50/60 Hz
|
50/60 Hz
|
| Type of Control Circuit
|
Electromechanical relay
|
| Type of Current
|
AC/DC
|
| Conventional Thermal Current Ith
|
Total of both outputs £ 2 A
|
| Type of Contacts
|
Normally open (N.O.)
|
| Number of Contacts
|
2
|
| ArmorPoint Ratings
|
Backplane Current Load
|
400 mA
|
|
|
|
|
UL/NEMA
|
IEC
|
| Environmental
|
Operating Temperature Range
|
-20…+40 °C (-4…+104 °F)
|
Storage and Transportation temperature range
|
25….+85 °C (13…+185 °F)
|
| Altitude
|
2000 m
|
| Humidity
|
5…95% (non-condensing)
|
| Pollution Degree
|
3
|
| Enclosure Ratings
|
NEMA 4/12/13
|
IP67
|
| Enclosure Ratings
|
NEMA 4X
|
IP69K
|
| Approximate Shipping Weight
|
16.8 kg (37 lb)
|
| Mechanical
|
Resistance to Shock
|
| Operational
|
15 G
|
| Non-Operational
|
30 G
|
| Resistance to Vibration
|
| Operational
|
1 G, 0.15 mm (0.006 in.) displacement
|
| Non-Operational
|
2.5 G, 0.38 mm (0.015 in.) displacement
|
| Power and Ground Terminals
|
| Wire Size
|
Primary/Secondary terminal: (#16 …#10 AWG)
|
Primary/Secondary terminal: 1.5…4.0 mm2
|
| Tightening Torque
|
Primary terminal: 10.8 lbin Secondary terminal: 4.5 lbin
|
Primary terminal: (1.2 Nm) Secondary terminal: (0.5 Nm)
|
| Wire Strip Length
|
0.35 in. (9 mm)
|
| Control and Safety Monitor Inputs
|
| Wire Size
|
(18…10 AWG)
|
1.0…4.0 mm2
|
| Tightening Torque
|
6.2 lbin
|
0.7 Nm
|
| Wire Strip Length
|
0.35 in. (9 mm)
|
| Other Rating
|
EMC Emission Levels
|
| Conducted Radio Frequency Emissions
|
Class A
|
| Radiated Emissions
|
Class A
|
| EMC Immunity Levels
|
| Electrostatic Discharge
|
4 kV contact and 8 kV Air
|
| Radio Frequency Electromagnetic Field
|
10V/m
|
| Fast Transient
|
2 kV
|
| Surge Transient
|
1 kV (12) L-L, 2 kV (2) L-N (earth)
|
| Overload Characteristics
|
| Overload Current Range
|
1.1…3.0 A
|
| 3.0…5.5 A
|
| 5.3…7.6 A
|
| 6.3…16 A
|
| Trip Class
|
10
|
| Trip Rating
|
120% of FLC setting
|
| Number of Poles
|
3
|
| DeviceNet Specifications
|
| DeviceNet Supply Voltage Rating
|
Range 11…25V DC, 24V DC nominal
|
| DeviceNet Input Current
|
167 mA @ 24V DC - 4.0 W
|
| 364 mA @ 11V DC - 4.0 W
|
| External Devices powered by DeviceNet
|
Sensors inputs 4 x 50 mA - total 200 mA
|
| Total w/max Sensor Inputs (4)
|
367 mA @ 24V DC - 8.8 W
|
| DeviceNet Input Current Surge
|
15 A for 250 ms
|
| DeviceNet Communications
|
| Baud Rates
|
125, 250, 500 kbps
|
| Distance Maximum
|
500 m (1630 ft) @ 125 kbps
|
| 200 m (656 ft) @ 250 kbps
|
| 100 m (328 ft) @ 500 kbps
|
| Certifications
|
cULus (File No. E96956) UL 508 EN/IEC 60947-4-2 CE Marked per Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC
|
|
|