Bulletin 100 DeviceNet Starter Auxiliary™
|
Bulletin 100 — DeviceNet Starter Auxiliary™ (DSA) Module
- DeviceLogix™ Component Technology
- Rotary Address Switches
- Reduced Engineering, Installation, and Startup Costs
- 24V DC or 120V AC Inputs
- High-Capacity Transistor or Relay Outputs
- Diagnostics Over Communication
- ODVA Compliance v2.0 Tested
- LED Input and Output Status Indication
The DeviceNet Starter Auxiliary (DSA) module enables a simple integration of contactors and sensors into the DeviceNet network. Components with minimum I/O requirements (e.g., four inputs and two outputs) are predominant. The DSA has high-capacity outputs that eliminate the need for interposing relays. This makes the DSA ideal for use with motor starters, circuit breakers, contactors, motor protectors, soft starters, sensors, reed switches, tracer switches and control protectors.
The DeviceLogix component technology incorporated into the DSA allows it to be programmed with up to 42 function blocks to execute simple logic locally. This functionality can be used to solve high-speed applications, controlled shut down, or other local operations. DeviceLogix capability in the DSA module can be configured with RSNetworx 3.00 or later.
Standards Compliance
IEC 60947
UL 508
CSA C22.2 No. 14
EN50081-2, EN50082-2
Approvals
CE
cULus Listed
Product Selection
- Removable connectors
- Slender 22.5 mm wide profile
- Screw or DIN Rail mounting
- Rotary node address switches
- DeviceNet address settable via hardware or software — no need to adjust rotary node address switches
| No. of Inputs | No. of Outputs | Cat. No. |
| 4 (120V AC) | 2 Relay (250V rated) | 100-DNY41R |
| 4 (24V DC) | 2 Relay (250V rated) | 100-DNY42R |
| 4 (24V DC) | 2 Solid-State (24V DC) | 100-DNY42S |
Specifications
| Electrical Data | ||
| DeviceNet supply voltage | 11…25V DC | |
| DeviceNet input current | max. 270 mA | |
| Surge current at powerup | <3 A for 5 ms | |
| Site Conditions | ||
| Ambient temperature | Operation | 0…60°C (32…140°F) |
| Storage | 40…85°C (40…185°F) | |
| Humidity | 0…95% (without condensation) | |
| Shock | Operation | 30 G, peak acceleration |
| Off-state | 50 G, peak acceleration | |
| Vibration resistance | 2.5 G, at 10…500 Hz | |
| DeviceNet Communication | ||
| Baud rate | 125, 250, 500 kBit/s | |
| Distance maximum | 500 m (1640 ft.) with 125 kBit/s 200 m (656 ft.) with 250 kBit/s 100 m (328 ft.) with 500 kBit/s |
|
| Connection | ||
| Connection capacity: (dependent on wire type) | 0.25…2.5 mm2/0.25…2.5 mm2/24…12 AWG | |
| Wire type | min. 75°C | |
| Tightening torque | 0.5…0.6 Nm (4.4…5.3 lb-in) | |
Input Specifications
| Cat. Nos. | 100-DNY21R, 100-DNY41R | 100-DNY42R, 100-DNY42S | |
| Inputs per device | 4 | 4 | |
| On-state voltage range Off-state voltage |
80…132V AC 40V, at 60 Hz |
10… 30V DC 5.5V DC |
|
| On-state current | 1.2…2.0 mA | 3 mA, at 10V (min)…11 mA, at 30V | |
| Off-state current | 0.6 mA min. | 1.5 mA max. | |
| Transition | Voltage | 40…79V AC | 5…10V DC |
| Current | 0.6…1.2 mA | 1.5…3 mA | |
| Sensor Source | Voltage | — | 19…25V DC |
| Current | — | 35 mA | |
Output Specifications
| Cat. No. | 100-DNY41R, 100-DNY42R (Relay Outputs) |
100-DNY42S (Transistor Outputs) |
|
| Outputs per device | 2 | 2 | |
| Voltage range | max. 240V AC, 30V DC | 15…30V DC, ±0.0% | |
| Switching capacity | max. | 3600 VA UL: B 300 IEC: AC-15: 5 A |
— |
| Thermal continuous current per output | max. | 5 A | — |
| On-State voltage drop | max. | — | 0.25V at 2 A |
| On-State current per output | max. | — | 2 A |
| Maximum off-state leakage current | — | 1.5 mA | |
| Surge current per output | — | 4 A for 50 ms | |
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
|