SMC™-3 Smart Motor Controllers

Product Overview


Click to enlarge - 150-7_1-5


Bulletin 150 — Smart Motor Controllers — SMC™-3 Smart Motor Controller

The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay and a built-in SCR bypass contactor on all three phases, allowing a smaller footprint than other soft starters on the market. This product is designed for many applications, including compressors, chillers, pumps, conveyors, and crushers. Modes of operation for the controller are as follows:


The controllers offer two voltage ranges: 200…480V AC and 200…600V AC. All voltage ranges will operate at either 50 or 60 Hz.


This catalog is based on the minimum information needed to select an SMC soft starter for applications with low starting torque requirements. For product selection involving loads with high starting torque requirements (large fan, rock crusher, chipper, etc.), use of the free tools available from the Rockwell Automation Website is recommended:

http://www.ab.com/industrialcontrols/products/solid-state_motor_control/software/


Standards Compliance

UL 508
CSA C22.2 No.14
EN/IEC 60947-1
EN/IEC 60947-4-2


Certifications

cULus Listed (Open Type) (File No. E96956, Guides NMFT, NMFT7)
CSA Certified (File No. LR 1234)
CE Marked (Open Type) per EMC and Low Voltage Directive
CCC Certified


Modes of Operation


Note: For detailed information about the different modes of operation, see The SMC controllers provide the following modes of operation:

Soft Start

This method has the most general application. The motor is raised from an initial torque value to full voltage. This initial torque can be adjusted to 0%, 25%, 35%, or 65% of locked rotor torque. The motor voltage is gradually increased during the acceleration ramp time, which can be adjusted from 2, 5, 10, 15, 20, 25, or 30 s.

Click to enlarge - 150-7_29-1


Current Limit Start

This starting mode is used when it is necessary to limit the maximum starting current. It can be adjusted to 150%, 250%, 350%, or 450% of full load amps. Start times are selectable from 2, 5, 10, 15, 20, 25, or 30 s.

Click to enlarge - 150-7_48-2


Selectable Kick Start

A kickstart, or boost, at the beginning of the start mode is intended to provide a current pulse of 450% of full load current. The kickstart time is adjustable from 0.5…1.5 seconds. This allows the motor to develop additional torque during starting for loads which may need a boost to get initial shaft rotation.

Click to enlarge - 150-7_56-4


Soft Stop

The Soft Stop function can be used with applications that require an extended stop time. When enabled, the voltage ramp down time can be selected to one, two, or three times the starting time. The motor will stop when the motor voltage drops to a point where the load torque is greater than the motor torque.

Click to enlarge - 150-7_56-5

Electronic Motor Overload Protection

The SMC-3 controller incorporates, as standard, electronic motor overload protection. This motor overload protection is accomplished electronically with the use of current transformers on each of the three phases. The controller’s overload protection is programmable, providing the user with flexibility. The overload trip class selection consists of either OFF, 10, 15, or 20. The trip current is easily selected by adjusting the rotary potentiometer to the motor full-load current rating. Trip reset is selectable to either automatic or manual mode.

Note:Trip rating is 120% of dial setting.

Over-temperature

The SMC-3 monitors the SCR temperature by means of internal thermistors. When the power poles maximum rated temperature is reached, the microcomputer switches off the SMC, a TEMP fault is indicated via LED, and the 97/98 fault contact closes.

Phase Reversal Protection

When enabled via a DIP switch, 3-phase input power will be verified before starting. If input power phasing is detected to be incorrect, the start will be aborted and a fault indicated.

Phase Loss/Open Load

The unit will not attempt a start if there is a single-phase condition on the line. This protects from motor burnout during single-phase starting.

Phase Imbalance

The unit monitors for imbalance between phase currents. To prevent motor damage, the unit will trip if the difference between the minimum phase current and the maximum phase current exceeds 65% for 3 s, and a fault will be indicated.

Shorted SCR

Prior to every start and during starting, the unit will check all SCRs for shorts and unit load connections to the motor. If there is a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR or open load fault will be indicated. This prevents damage from phase imbalance.

Push to Test

The unit with control wiring can be tested for fault conditions by using the Push to Test function. Hold down the Reset button for 7 s to activate the fault Aux (97, 98) and shut down the SMC-3. To clear, either push the Reset button or cycle control power to the device.

LED Description (Number of Flashes)

1. Overload
2. Overtemperature
3. Phase Reversal
4. Phase Loss/Open Load
5. Phase Imbalance
6. Shorted SCR
7. Test


Open and Non-Combination

150 C    30    F    B    D 8L
a    b    c    d    e    f    g

a    b    c    d
Bulletin Number Controller Type Ampere Ratings Enclosure Type
Code Description Code Description Code Description Code Description
150 Solid-State Controller C SMC-3 3 3 A N Open
      9 9 A F NEMA 4/12 (IP65)
16 16 A   
19 19 A
25 25 A
30 30 A
37 37 A
43 43 A
60 60 A
85 85 A
108 108 A
135 135 A
201 201 A
251 251 A
317 317 A
361 361 A
480 480 A
  
e    f    g   
Input Line Voltage
Open Type
Control Voltage Options (see Options for a full listing)
Code Description Code Description Code Description
B 200…460V AC, 3-Phase, 50/60 Hz D 100…240V AC 8L Line Mounted Protective Module (Enclosed Type only)
C 200…600V AC, 3-Phase, 50/60 Hz R 24V AC/DC (Open Type only) 8M Load-Mounted Protective Module
Non-Combination Enclosed Only    8B Line- and Load-Mounted Protective Modules
H 200…208V AC, 3-Phase, 50/60 Hz Load-side MOVs are not available with pump and braking options, or when used with inside-the-delta connections.
A 230V AC, 3-Phase, 50/60 Hz   
B 400…460V AC, 3-Phase, 50/60 Hz    
C 500…575V AC, 3-Phase, 50/60 Hz    

Combination

152H C    30    F    BD    43 8L
a    b    c    d    e    f    g

a    b    c    d    e
Bulletin Number Controller Type Ampere Ratings Enclosure Type Input Line Voltage
Open Type
Code Description Code Description Code Description Code Description Code Description
152H‡  Solid-State Controller with Fusible Disconnect C SMC-3 3 3 A F NEMA Type 4/12 (IP65) HD 200…208V AC, 3-Phase, 50/60 Hz
153H‡  Solid-State Controller with Circuit Breaker    9 9 A X‡  NEMA Type 3R (IP44) AD 230V AC, 3-Phase, 50/60 Hz
   16 16 A    BD‡  400…460V AC, 3-Phase, 50/60 Hz
19 19 A CD 500…575V AC, 3-Phase, 50/60 Hz
25‡  25 A   
30 30 A
37 37 A
43‡  43 A
60 60 A
85‡  85 A
108‡  108 A
135‡  135 A
201‡  201 A
251 251 A
317‡  317 A
361‡  361 A
480‡  480 A
  
f
Horsepower
Cat. No. Hp Rating    Cat. No. Hp Rating    Cat. No. Hp Rating    Cat. No. Hp Rating    Cat. No. Hp Rating
33 0.5 39 5 46‡  40 52‡  150 60 450
34 0.75 40 7.5 47‡  50 54 200 61 500
35 1 41‡  10 48‡  60 56‡  250 62 600
36 1.5 42‡  15 49‡  75 57‡  300 63 700
37 2 43‡  20 50‡  100 58‡  350 65 800
38 3 44‡  25 51‡  125 59‡  400 67 1000
45‡  30
  
g   
Options (see Options for a full listing)
Code Description
8L Line-Mounted Protective Module
8M Load-Mounted Protective Module
8B Line- and Load-Mounted Protective Modules
Load-side MOVs are not available with Pump and Braking options, or when used with inside-the-delta connections.
‡ Pump Panel only available for noted configuration. Start push button, external reset, HOA, and transformer are included as standard.

Open Type and Non-Combination Enclosed (IP65, NEMA 4/12) Controllers — For use with Line-Connected Motors

Build a Catalog Number


Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type — Line-Connected Motors IP65 (Type 4/12) Enclosed
Non-Combination Controllers♣ 
Cat. No. Cat. No.
200/208 1…3 0.5 100…240V AC, 50/60 Hz 150-C3NBD 150-C3FHD
24V AC/DC 150-C3NBR
3…9 0.75…2 100…240V AC, 50/60 Hz 150-C9NBD 150-C9FHD
24V AC/DC 150-C9NBR
5.3…16 1.5…3 100…240V AC, 50/60 Hz 150-C16NBD 150-C16FHD
24V AC/DC 150-C16NBR
6.3…19 1.5…3 100…240V AC, 50/60 Hz 150-C19NBD 150-C25FHD
24V AC/DC 150-C19NBR
9.2…25 3…7.5 100…240V AC, 50/60 Hz 150-C25NBD 150-C25FHD
24V AC/DC 150-C25NBR
10…30 3…7.5 100…240V AC, 50/60 Hz 150-C30NBD 150-C30FHD
24V AC/DC 150-C30NBR
12.3…37 5…10 100…240V AC, 50/60 Hz 150-C37NBD 150-C37FHD
24V AC/DC 150-C37NBR
14.3…43 5…10 100…240V AC, 50/60 Hz 150-C43NBD 150-C43FHD
24V AC/DC 150-C43NBR
20…60 7.5…15 100…240V AC, 50/60 Hz 150-C60NBD 150-C60FHD
24V AC/DC 150-C60NBR
28.3…85 10…25 100…240V AC, 50/60 Hz 150-C85NBD 150-C85FHD
24V AC/DC 150-C85NBR
27…108 20…30 100…240V AC, 50/60 Hz 150-C108NBD 150-C108FHD
24V AC/DC∆  150-C108NBR
34…135 25…40 100…240V AC, 50/60 Hz 150-C135NBD 150-C135FHD
24V AC/DC∆  150-C135NBR
67…201 40…60 100…240V AC, 50/60 Hz 150-C201NBD 150-C201FHD
24V AC/DC∆  150-C201NBR
84…251 50…75 100…240V AC, 50/60 Hz 150-C251NBD 150-C251FHD
24V AC/DC∆  150-C251NBR
106…317 60…100 100…240V AC, 50/60 Hz 150-C317NBD 150-C317FHD
24V AC/DC∆  150-C317NBR
120…361 75…125 100…240V AC, 50/60 Hz 150-C361NBD 150-C361FHD
24V AC/DC∆  150-C361NBR
160…480 100…150 100…240V AC, 50/60 Hz 150-C480NBD 150-C480FHD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
♣ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type — Line-Connected Motors IP65 (Type 4/12) Enclosed
Non-Combination Controllers♣ 
Cat. No. Cat. No.
230 1…3 0.55 0.5 100…240V AC, 50/60 Hz 150-C3NBD 150-C3FAD
24V AC/DC 150-C3NBR
3…9 2.2 0.75…2 100…240V AC, 50/60 Hz 150-C9NBD 150-C9FAD
24V AC/DC 150-C9NBR
5.3…16 4 1.5…5 100…240V AC, 50/60 Hz 150-C16NBD 150-C16FAD
24V AC/DC 150-C16NBR
6.3…19 4 2…5 100…240V AC, 50/60 Hz 150-C19NBD 150-C25FAD
24V AC/DC 150-C19NBR
9.2…25 5.5 3…7.5 100…240V AC, 50/60 Hz 150-C25NBD 150-C25FAD
24V AC/DC 150-C25NBR
10…30 7.5 5…10 100…240V AC, 50/60 Hz 150-C30NBD 150-C30FAD
24V AC/DC 150-C30NBR
12.3…37 7.5 5…10 100…240V AC, 50/60 Hz 150-C37NBD 150-C37FAD
24V AC/DC 150-C37NBR
14.3…43 11 5…15 100…240V AC, 50/60 Hz 150-C43NBD 150-C43FAD
24V AC/DC 150-C43NBR
20…60 15 7.5…20 100…240V AC, 50/60 Hz 150-C60NBD 150-C60FAD
24V AC/DC 150-C60NBR
28.3…85 22 15…30 100…240V AC, 50/60 Hz 150-C85NBD 150-C85FAD
24V AC/DC 150-C85NBR
27…108 30 20…40 100…240V AC, 50/60 Hz 150-C108NBD 150-C108FAD
24V AC/DC∆  150-C108NBR
34…135 37 25…50 100…240V AC, 50/60 Hz 150-C135NBD 150-C135FAD
24V AC/DC∆  150-C135NBR
67…201 55 40…75 100…240V AC, 50/60 Hz 150-C201NBD 150-C201FAD
24V AC/DC∆  150-C201NBR
84…251 75 50…100 100…240V AC, 50/60 Hz 150-C251NBD 150-C251FAD
24V AC/DC∆  150-C251NBR
106…317 90 60…125 100…240V AC, 50/60 Hz 150-C317NBD 150-C317FAD
24V AC/DC∆  150-C317NBR
120…361 110 75…150 100…240V AC, 50/60 Hz 150-C361NBD 150-C361FAD
24V AC/DC∆  150-C361NBR
160…480 132 100…200 100…240V AC, 50/60 Hz 150-C480NBD 150-C480FAD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
♣ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type — Line-Connected Motors IP65 (Type 4/12) Enclosed
Non-Combination Controllers♣ 
Cat. No. Cat. No.
380/400/
415/460
1…3 1.1 0.5…1.5 100…240V AC, 50/60 Hz 150-C3NBD 150-C3FBD
24V AC/DC 150-C3NBR
3…9 4 1.5…5 100…240V AC, 50/60 Hz 150-C9NBD 150-C9FBD
24V AC/DC 150-C9NBR
5.3…16 7.5 5…10 100…240V AC, 50/60 Hz 150-C16NBD 150-C16FBD
24V AC/DC 150-C16NBR
6.3…19 7.5 5…10 100…240V AC, 50/60 Hz 150-C19NBD 150-C19NBR
24V AC/DC 150-C19NBR
9.2…25 11 7.5…15 100…240V AC, 50/60 Hz 150-C25NBD 150-C25NBR
24V AC/DC 150-C25NBR
10…30 15 7.5…20 100…240V AC, 50/60 Hz 150-C30NBD 150-C30FBD
24V AC/DC 150-C30NBR
12.3…37 18.5 10…25 100…240V AC, 50/60 Hz 150-C37NBD 150-C37FBD
24V AC/DC 150-C37NBR
14.3…43 22 10…30 100…240V AC, 50/60 Hz 150-C43NBD 150-C43FBD
24V AC/DC 150-C43NBR
20…60 30 15…40 100…240V AC, 50/60 Hz 150-C60NBD 150-C60FBD
24V AC/DC 150-C60NBR
28.3…85 45 25…60 100…240V AC, 50/60 Hz 150-C85NBD 150-C85FBD
24V AC/DC 150-C85NBR
27…108 55 50…75 100…240V AC, 50/60 Hz 150-C108NBD 150-C108FBD
24V AC/DC∆  150-C108NBR
34…135 75 60…100 100…240V AC, 50/60 Hz 150-C135NBD 150-C135FBD
24V AC/DC∆  150-C135NBR
67…201 95…110 75…150 100…240V AC, 50/60 Hz 150-C201NBD 150-C201FBD
24V AC/DC∆  150-C201NBR
84…251 95…132 100…200 100…240V AC, 50/60 Hz 150-C251NBD 150-C251FBD
24V AC/DC∆  150-C251NBR
106…317 95…160 125…250 100…240V AC, 50/60 Hz 150-C317NBD 150-C317FBD
24V AC/DC∆  150-C317NBR
120…361 110…200 250…300 100…240V AC, 50/60 Hz 150-C361NBD 150-C361FBD
24V AC/DC∆  150-C361NBR
160…480 160…250 300…400 100…240V AC, 50/60 Hz 150-C480NBD 150-C480FBD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
♣ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type — Line-Connected Motors IP65 (Type 4/12) Enclosed
Non-Combination Controllers♣ 
Cat. No. Cat. No.
500/575 1…3 1.5 0.75…2 100…240V AC, 50/60 Hz 150-C3NCD 150-C3FCD
24V AC/DC 150-C3NCR
3…9 5.5 3…7.5 100…240V AC, 50/60 Hz 150-C9NCD 150-C9FCD
24V AC/DC 150-C9NCR
5.3…16 7.5 5…10 100…240V AC, 50/60 Hz 150-C16NCD 150-C16FCD
24V AC/DC 150-C16NCR
6.3…19 11 7.5…15 100…240V AC, 50/60 Hz 150-C19NCD 150-C25FCD
24V AC/DC 150-C19NCR
9.2…25 15 7.5…20 100…240V AC, 50/60 Hz 150-C25NCD 150-C25FCD
24V AC/DC 150-C25NCR
10…30 18.5 10…25 100…240V AC, 50/60 Hz 150-C30NCD 150-C30FCD
24V AC/DC 150-C30NCR
12.3…37 22 15…30 100…240V AC, 50/60 Hz 150-C37NCD 150-C37FCD
24V AC/DC 150-C37NCR
14.3…43 22 15…40 100…240V AC, 50/60 Hz 150-C43NCD 150-C43FCD
24V AC/DC 150-C43NCR
20…60 37 20…50 100…240V AC, 50/60 Hz 150-C60NCD 150-C60FCD
24V AC/DC 150-C60NCR
28.3…85 55 30…75 100…240V AC, 50/60 Hz 150-C85NCD 150-C85FCD
24V AC/DC 150-C85NCR
27…108 75 60…100 100…240V AC, 50/60 Hz 150-C108NCD 150-C108FCD
24V AC/DC∆  150-C108NCR
34…135 90 75…125 100…240V AC, 50/60 Hz 150-C135NCD 150-C135FCD
24V AC/DC∆  150-C135NCR
67…201 75…132 100…200 100…240V AC, 50/60 Hz 150-C201NCD 150-C201FCD
24V AC/DC∆  150-C201NCR
84…251 90…160 125…250 100…240V AC, 50/60 Hz 150-C251NCD 150-C251FCD
24V AC/DC∆  150-C251NCR
106…317 100…200 200…300 100…240V AC, 50/60 Hz 150-C317NCD 150-C317FCD
24V AC/DC∆  150-C317NCR
120…361 132…250 200…350 100…240V AC, 50/60 Hz 150-C361NCD 150-C361FCD
24V AC/DC∆  150-C361NCR
160…480 200…315 250…500 100…240V AC, 50/60 Hz 150-C480NCD 150-C480FCD
24V AC/DC∆  150-C480NCR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
♣ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
∆ Separate 120V or 240V single phase is required for fan operation.

Open Type Controllers — For use with Delta-Connected Motors

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type
Cat. No.
200/208 1.7…5.1 1 100…240V AC, 50/60 Hz 150-C3NBD
24V AC/DC 150-C3NBR
5.1…16 1.5…3 100…240V AC, 50/60 Hz 150-C9NBD
24V AC/DC 150-C9NBR
9.1…27.6 3…7.5 100…240V AC, 50/60 Hz 150-C16NBD
24V AC/DC 150-C16NBR
10.9…32.8 3…10 100…240V AC, 50/60 Hz 150-C19NBD
24V AC/DC 150-C19NBR
14.3…43 3…10 100…240V AC, 50/60 Hz 150-C25NBD
24V AC/DC 150-C25NBR
17.3…52 5…10 100…240V AC, 50/60 Hz 150-C30NBD
24V AC/DC 150-C30NBR
21…64 7.5…20 100…240V AC, 50/60 Hz 150-C37NBD
24V AC/DC 150-C37NBR
25…74 7.5…20 100…240V AC, 50/60 Hz 150-C43NBD
24V AC/DC 150-C43NBR
34.6…104 15…30 100…240V AC, 50/60 Hz 150-C60NBD
24V AC/DC 150-C60NBR
50…147 15…40 100…240V AC, 50/60 Hz 150-C85NBD
24V AC/DC 150-C85NBR
47…187 20…60 100…240V AC, 50/60 Hz 150-C108NBD
24V AC/DC∆  150-C108NBR
59…234 20…75 100…240V AC, 50/60 Hz 150-C135NBD
24V AC/DC∆  150-C135NBR
116…348 75…100 100…240V AC, 50/60 Hz 150-C201NBD
24V AC/DC∆  150-C201NBR
145…435 100…150 100…240V AC, 50/60 Hz 150-C251NBD
24V AC/DC∆  150-C251NBR
183…549 100…200 100…240V AC, 50/60 Hz 150-C317NBD
24V AC/DC∆  150-C317NBR
208…625 125…200 100…240V AC, 50/60 Hz 150-C361NBD
24V AC/DC∆  150-C361NBR
277…831 200…300 100…240V AC, 50/60 Hz 150-C480NBD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type
Cat. No.
230 1.7…5.1 0.25…1.1 1 100…240V AC, 50/60 Hz 150-C3NBD
24V AC/DC 150-C3NBR
5.1…16 1.1…4 1…5 100…240V AC, 50/60 Hz 150-C9NBD
24V AC/DC 150-C9NBR
9.1…27.6 2.2…7.5 3…7.5 100…240V AC, 50/60 Hz 150-C16NBD
24V AC/DC 150-C16NBR
10.9…32.8 2.2…7.5 3…10 100…240V AC, 50/60 Hz 150-C19NBD
24V AC/DC 150-C19NBR
14.3…43 4…11 3…15 100…240V AC, 50/60 Hz 150-C25NBD
24V AC/DC 150-C25NBR
17.3…52 4…15 5…15 100…240V AC, 50/60 Hz 150-C30NBD
24V AC/DC 150-C30NBR
21…64 5.5…18.5 7.5…20 100…240V AC, 50/60 Hz 150-C37NBD
24V AC/DC 150-C37NBR
25…74 5.5…22 7.5…25 100…240V AC, 50/60 Hz 150-C43NBD
24V AC/DC 150-C43NBR
34.6…104 7.5…30 15…40 100…240V AC, 50/60 Hz 150-C60NBD
24V AC/DC 150-C60NBR
50…147 15…45 20…50 100…240V AC, 50/60 Hz 150-C85NBD
24V AC/DC 150-C85NBR
47…187 55 20…60 100…240V AC, 50/60 Hz 150-C108NBD
24V AC/DC∆  150-C108NBR
59…234 75 25…75 100…240V AC, 50/60 Hz 150-C135NBD
24V AC/DC∆  150-C135NBR
116…348 110 75…125 100…240V AC, 50/60 Hz 150-C201NBD
24V AC/DC∆  150-C201NBR
145…435 132 100…150 100…240V AC, 50/60 Hz 150-C251NBD
24V AC/DC∆  150-C251NBR
183…549 160 125…200 100…240V AC, 50/60 Hz 150-C317NBD
24V AC/DC∆  150-C317NBR
208…625 200 150…250 100…240V AC, 50/60 Hz 150-C361NBD
24V AC/DC∆  150-C361NBR
277…831 250 200…300 100…240V AC, 50/60 Hz 150-C480NBD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type
Cat. No.
380/400/415/460 1.7…5.1 0.55…2.2 0.5…2 100…240V AC, 50/60 Hz 150-C3NBD
24V AC/DC 150-C3NBR
5.1…16 2.2…7.5 2…7.5 100…240V AC, 50/60 Hz 150-C9NBD
24V AC/DC 150-C9NBR
9.1…27.6 4…11 5…15 100…240V AC, 50/60 Hz 150-C16NBD
24V AC/DC 150-C16NBR
10.9…32.8 4…15 5…15 100…240V AC, 50/60 Hz 150-C19NBD
24V AC/DC 150-C19NBR
14.3…43 5.5…22 7.5…20 100…240V AC, 50/60 Hz 150-C25NBD
24V AC/DC 150-C25NBR
17.3…52 7.5…22 7.5…30 100…240V AC, 50/60 Hz 150-C30NBD
24V AC/DC 150-C30NBR
21…64 7.5…30 10…40 100…240V AC, 50/60 Hz 150-C37NBD
24V AC/DC 150-C37NBR
25…74 11…37 10…50 100…240V AC, 50/60 Hz 150-C43NBD
24V AC/DC 150-C43NBR
34.6…104 15…55 20…75 100…240V AC, 50/60 Hz 150-C60NBD
24V AC/DC 150-C60NBR
50…147 22…75 25…100 100…240V AC, 50/60 Hz 150-C85NBD
24V AC/DC 150-C85NBR
47…187 90 40…150 100…240V AC, 50/60 Hz 150-C108NBD
24V AC/DC∆  150-C108NBR
59…234 132 50…150 100…240V AC, 50/60 Hz 150-C135NBD
24V AC/DC∆  150-C135NBR
116…348 160 150…250 100…240V AC, 50/60 Hz 150-C201NBD
24V AC/DC∆  150-C201NBR
145…435 250 200…350 100…240V AC, 50/60 Hz 150-C251NBD
24V AC/DC∆  150-C251NBR
183…549 315 250…450 100…240V AC, 50/60 Hz 150-C317NBD
24V AC/DC∆  150-C317NBR
208…625 355 300…500 100…240V AC, 50/60 Hz 150-C361NBD
24V AC/DC∆  150-C361NBR
277…831 450 350…700 100…240V AC, 50/60 Hz 150-C480NBD
24V AC/DC∆  150-C480NBR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
∆ Separate 120V or 240V single phase is required for fan operation.

Rated Voltage
[V AC]
Motor Current [A]‡  Max. kW, 50 Hz Max. Hp, 60 Hz Control Power Open Type
Cat. No.
500/575 1.7…5.1 0.75…3 1…3 100…240V AC, 50/60 Hz 150-C3NCD
24V AC/DC 150-C3NCR
5.1…16 3…7.5 3…10 100…240V AC, 50/60 Hz 150-C9NCD
24V AC/DC 150-C9NCR
9.1…27.6 5.5…15 7.5…20 100…240V AC, 50/60 Hz 150-C16NCD
24V AC/DC 150-C16NCR
10.9…32.8 5.5…22 7.5…30 100…240V AC, 50/60 Hz 150-C19NCD
24V AC/DC 150-C19NCR
14.3…43 7.5…22 10…40 100…240V AC, 50/60 Hz 150-C25NCD
24V AC/DC 150-C25NCR
17.3…52 11…30 15…50 100…240V AC, 50/60 Hz 150-C30NCD
24V AC/DC 150-C30NCR
21…64 11…37 15…60 100…240V AC, 50/60 Hz 150-C37NCD
24V AC/DC 150-C37NCR
25…74 15…45 20…60 100…240V AC, 50/60 Hz 150-C43NCD
24V AC/DC 150-C43NCR
34.6…104 22…55 30…100 100…240V AC, 50/60 Hz 150-C60NCD
24V AC/DC 150-C60NCR
50…147 30…90 40…150 100…240V AC, 50/60 Hz 150-C85NCD
24V AC/DC 150-C85NCR
47…187 132 50…150 100…240V AC, 50/60 Hz 150-C108NCD
24V AC/DC∆  150-C108NCR
59…234 160 60…200 100…240V AC, 50/60 Hz 150-C135NCD
24V AC/DC∆  150-C135NCR
116…348 250 250…300 100…240V AC, 50/60 Hz 150-C201NCD
24V AC/DC∆  150-C201NCR
145…435 315 250…400 100…240V AC, 50/60 Hz 150-C251NCD
24V AC/DC∆  150-C251NCR
183…549 400 300…500 100…240V AC, 50/60 Hz 150-C317NCD
24V AC/DC∆  150-C317NCR
208…625 450 350…600 100…240V AC, 50/60 Hz 150-C361NCD
24V AC/DC∆  150-C361NCR
277…831 560 400…900 100…240V AC, 50/60 Hz 150-C480NCD
24V AC/DC∆  150-C480NCR
  
‡ Motor FLA rating should fall within specified current range for unit to operate properly.
∆ Separate 120V or 240V single phase is required for fan operation.

Combination Enclosed (IP65, NEMA 4/12) Controllers with Fusible Disconnect or Circuit Breaker

Build a Catalog Number


Rated Voltage
[V AC]
Current
Rating [A]
kW Hp IP65 (Type 4/12) Enclosed Combination Controllers with Fusible Disconnect ‡  IP65 (Type 4/12) Enclosed Combination Controllers with Circuit Breaker ‡ 
Cat. No. Cat. No.
200/208 3 0.5 152H-C3FHD-33 153H-C3FHD-33
9 0.75 152H-C9FHD-34 153H-C9FHD-34
9 1 152H-C9FHD-35 153H-C9FHD-35
9 1.5 152H-C9FHD-36 153H-C9FHD-36
16 2 152H-C16FHD-37 153H-C16FHD-37
16 3 152H-C16FHD-38 153H-C16FHD-38
25 5 152H-C25FHD-39 153H-C25FHD-39
37 7.5 152H-C37FHD-40 153H-C37FHD-40
43 10 152H-C43FHD-41 153H-C43FHD-41
60 15 152H-C60FHD-42 153H-C60FHD-42
85 20 152H-C85FHD-43 153H-C85FHD-43
85 25 152H-C85FHD-44 153H-C85FHD-44
108 30 152H-C108FHD-45 153H-C108FHD-45
135 40 152H-C135FHD-46 153H-C135FHD-46
201 60 152H-C201FHD-48 153H-C201FHD-48
251 75 152H-C251FHD-49 153H-C251FHD-49
317 100 152H-C317FHD-50 153H-C317FHD-50
361 125 152H-C361FHD-51 153H-C361FHD-51
480 150 152H-C480FHD-52 153H-C480FHD-52
230 3 0.37 0.5 152H-C3FAD-33 153H-C3FAD-33
9 0.55 0.75 152H-C9FAD-34 153H-C9FAD-34
9 0.75 1 152H-C9FAD-35 153H-C9FAD-35
9 1.1 1.5 152H-C9FAD-36 153H-C9FAD-36
9 1.5 2 152H-C9FAD-37 153H-C9FAD-37
16 2.2 3 152H-C16FAD-38 153H-C16FAD-38
25 3.7 5 152H-C25FAD-39 153H-C25FAD-39
30 5.5 7.5 152H-C30FAD-40 153H-C30FAD-40
37 7.5 10 152H-C37FAD-41 153H-C37FAD-41
43 11 15 152H-C43FAD-42 153H-C43FAD-42
60 15 20 152H-C60FAD-43 153H-C60FAD-43
85 18.5 25 152H-C85FAD-44 153H-C85FAD-44
85 22 30 152H-C85FAD-45 153H-C85FAD-45
108 30 40 152H-C108FAD-46 153H-C108FAD-46
135 37 50 152H-C135FAD-47 153H-C135FAD-47
201 55 75 152H-C201FAD-49 153H-C201FAD-49
251 75 100 152H-C251FAD-50 153H-C251FAD-50
317 90 125 152H-C317FAD-51 153H-C317FAD-51
361 110 150 152H-C361FAD-52 153H-C361FAD-52
480 147 200 ♣  152H-C480JAD-54 153H-C480FAD-54
  
‡ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
♣ Available in IP54 (Type 12) enclosure only.

Rated Voltage
[V AC]
Current
Rating [A]
kW Hp IP65 (Type 4/12) Enclosed Combination Controllers with Fusible Disconnect ‡  IP65 (Type 4/12) Enclosed Combination Controllers with Circuit Breaker ‡ 
Cat. No. Cat. No.
460 3 0.37 0.5 152H-C3FBD-33 153H-C3FBD-33
3 0.55 0.75 152H-C3FBD-34 153H-C3FBD-34
3 0.75 1 152H-C3FBD-35 153H-C3FBD-35
9 1.1 1.5 152H-C9FBD-36 153H-C9FBD-36
9 1.5 2 152H-C9FBD-37 153H-C9FBD-37
9 2.2 3 152H-C9FBD-38 153H-C9FBD-38
16 3.7 5 152H-C16FBD-39 153H-C16FBD-39
16 5.5 7.5 152H-C16FBD-40 153H-C16FBD-40
25 7.5 10 152H-C25FBD-41 153H-C25FBD-41
30 11 15 152H-C30FBD-42 153H-C30FBD-42
37 15 20 152H-C37FBD-43 153H-C37FBD-43
43 18.5 25 152H-C43FBD-44 153H-C43FBD-44
43 22 30 152H-C43FBD-45 153H-C43FBD-45
60 30 40 152H-C60FBD-46 153H-C60FBD-46
85 37 50 152H-C85FBD-47 153H-C85FBD-47
85 45 60 152H-C85FBD-48 153H-C85FBD-48
108 55 75 152H-C108FBD-49 153H-C108FBD-49
135 75 100 152H-C135FBD-50 153H-C135FBD-50
201 110 150 152H-C201FBD-52 153H-C201FBD-52
251 132 200 152H-C251FBD-54 153H-C251FBD-54
317 160 250 152H-C317FBD-56 153H-C317FBD-56
361 200 300 152H-C361FBD-57 153H-C361FBD-57
480 250 400 ♣  152H-C480JBD-59 153H-C480FBD-59
500/575 3 0.55 0.75 152H-C3FCD-34 153H-C3FCD-34
3 0.75 1 152H-C3FCD-35 153H-C3FCD-35
9 1.1 1.5 152H-C9FCD-36 153H-C9FCD-36
9 1.5 2 152H-C9FCD-37 153H-C9FCD-37
9 2.2 3 152H-C9FCD-38 153H-C9FCD-38
9 3.7 5 152H-C9FCD-39 153H-C9FCD-39
16 5.5 7.5 152H-C16FCD-40 153H-C16FCD-40
16 7.5 10 152H-C16FCD-41 153H-C16FCD-41
25 11 15 152H-C25FCD-42 153H-C25FCD-42
30 15 20 152H-C30FCD-43 153H-C30FCD-43
37 18.5 25 152H-C37FCD-44 153H-C37FCD-44
43 22 30 152H-C43FCD-45 153H-C43FCD-45
43 30 40 152H-C43FCD-46 153H-C43FCD-46
60 37 50 152H-C60FCD-47 153H-C60FCD-47
85 45 60 152H-C85FCD-48 153H-C85FCD-48
85 55 75 152H-C85FCD-49 153H-C85FCD-49
108 75 100 152H-C108FCD-50 153H-C108FCD-50
135 90 125 152H-C135FCD-51 153H-C135FCD-51
201 132 200 152H-C201FCD-54 153H-C201FCD-54
251 160 250 152H-C251FCD-56 153H-C251FCD-56
317 200 300 152H-C317FCD-57 153H-C317FCD-57
361 250 350 152H-C361FCD-58 153H-C361FCD-58
480 315 500 ♣  152H-C480JCD-61 153H-C480FCD-61
  
‡ These controllers require a separate 100…240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
♣ Available in IP54 (Type 12) enclosure only.

Option Description Cat. No.
Modification
Push Buttons Start-Stop Push Button -1
Selector Switch Hand-Off-Auto Selector Switch -3
Pilot Light Transformer Pilot Light - Red Run Indicator -4R
Control Circuit Transformer Control Circuit Transformer (fused primary and secondary) -6P
Protective Module 480V Line Side Protective Module 3…480 A -8L
600V Line Side Protective Module 3…480 A
480V Load Side Protective Module 43…480 A -8M
600V Load Side Protective Module 43…480 A
480V Both Line and Load Side Protective Module 43…480 A -8B
600V Both Line and Load Side Protective Module 43…480 A
Auxiliary Contacts 1 N.O. auxiliary contact for 3…480 A units -90
2 N.O. auxiliary contacts for 3…480 A units -900
1 N.O. and 1 N.C. auxiliary contacts for 3…480 A units -901
Disconnect Auxiliary N.O. disconnect auxiliary mounted on the operating mechanism -98
N.C. disconnect auxiliary mounted on the operating mechanism -99
NEMA Bypass Contactor and Overload Relay 5…43 A§  -NB
60…85 A§ 
108…135 A§ 
201…251 A
317…361 A
480 A
MCS Bypass Contactor and Overload Relay 5…43 A§  -BP
60…85 A§ 
108…135 A§ 
201…251 A
317…361 A
480 A
  
§ Available only as a modified standard.

Auxiliary Contact Blocks

Description N.O. N.C. Connection Diagram Cat. No.
Click to enlarge - 150-CA_R Auxiliary Contact Blocks for side mounting with sequence terminal designations
1- and 2-pole
Quick and easy mounting without tools
One block per device only
1 0 Click to enlarge - 150-7_66-2 Click to enlarge - 150-7_66-3 Click to enlarge - 150-7_66-4 Click to enlarge - 150-7_66-5 150-CA10
2 0 150-CA20
0 1 150-CA01
1 1 150-CA11
(Form C)
  

Fans

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-CF64_L Fan
Field installed
Optional 150-C3…37 1 150-CF64
Replacement 150-C43…85 150-CF147
150-C108, 150-C135 41391-801-03
150-C201, 150-C251 41391-801-01
150-C317…C480 41391-801-02
  

Connecting Modules

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-7-66-7 Connecting modules to 140-M
Electrical interconnection between SMC-3 and 140-M.
Motor protector and SMC must be mounted separately.
Connects 140-M-C to
150-C3…25
1 150-CC25
Connects 140-M-D to
150-C3…25
1 150-CD25
Connects 140-M-F to
150-C3…37
1 150-CF45
Click to enlarge - 150-7-66-8 Connecting modules to 100-C
Electrical interconnection between SMC-3 and 100-C.
Contactor and SMC must be mounted separately.
Connects 100-C09…23 to
150-C3…19
1 150-CI23
Connects 100-C30…37 to
150-C3…37
1 150-CI37
  

Protective Modules

Protective modules must not be placed on the load side of a device when using an inside-the-delta connection.

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-C84 480V Protective Module 150-C3…37NB 1 150-C84
150-C43…85NB (line and/or load) 1 150-C84P
150-C108…480NB (line and/or load) 1 150-F84L
600V Protective Module 150-C3…37NC 1 150-C86
150-C43…85NC (line and/or load) 1 150-C86P
150-C108…480NC (line and/or load) 1 150-F86L
  

IEC Terminal Covers

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-7-76-3 Terminal Cover
IEC line or load terminal covers for 108…480 A devices.
Dead front protection
150-C108…-C135 1 150-TC1
150-C201…-C251 1 150-TC2
150-C317…-C480 1 150-TC3
  

Terminal Lug Kits (108…480 A)

Click to enlarge - 150-7_23-2 Current
Rating [A] ‡ 
Wire Size Total No. of Line Controller
Terminal Lugs
Possible Each Side
Pkg. Qty. Cat. No.
Line Side Load Side
108…135∆  #6…250 MCM AWG
16 mm2…120 mm2
3 3 3 199-LF1
201…251∆  6 6
317…480∆  #4…500 MCM AWG
25 mm2…240 mm2
6 6 199-LG1
  
Line and Load terminals are provided as standard on enclosed SMCs.
‡  1…85 A units have box lugs standard. No additional lugs are required.
∆ When a multi-conductor lug is required, refer to the Instruction Sheet for appropriate lug catalog number.

Marking Tags and Covers

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-7_66-10 Marking Tag Sheet
160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
150-C, 150-D 10 100-FMP
Transparent Cover
To be used with marking tag sheets
150-C, 150-D 100 100-FMC
  

Remote Reset Solenoid

Description For Use With Pkg. Qty. Cat. No.
Click to enlarge - 150-7_66-11 Remote Reset Solenoid for remote reset of electronic overload 193-T all, 150-C 1 193-ER1Ä
  

Ä Voltage Suffix Code

Available Coil Voltages 12…600V 50 Hz/12…600V 60 Hz
Standard Coil Voltages


Voltage 24 48 110 115 120 220 240
50 Hz J D A
60 Hz J D A
DC Z24 Z48 Z01
  
Surcharge for special voltages up to 20 pcs. (no surcharge for quantities greater than 20 pcs.)

Two-Wire Configuration

IEC

Click to enlarge - 150-7_59-1


NEMA

Click to enlarge - 150-7_59-2


Three-Wire Configuration

IEC

Click to enlarge - 150-7_59-3


NEMA

Click to enlarge - 150-7_59-4


Isolation Contactor Configuration

IEC

Click to enlarge - 150-7_60-1


NEMA

Click to enlarge - 150-7_60-2


Reversing Configuration

Note:Minimum Off time equals 1.0 s.

IEC

Click to enlarge - 150-7_60-3


NEMA

Click to enlarge - 150-7_60-4

Standard Features
Selectable Start Times 2, 5, 10, 15, 20, 25, or 30 s
Selectable Initial Torque 0%, 25%, 35%, and 65% of locked rotor torque
Selectable Current Limit 150%, 250%, 350%, and 450% of full load current
Selectable Kick Start — 450% FLA 0, 0.5, 1.0, or 1.5 s
Selectable Soft Stop Off, 100%, 200%, or 300% of the start time setting when wired
Electrical Ratings
  UL/CSA/NEMA IEC
Power Circuit Rated Operation Voltage 200…480V AC
200…600V AC
200…480V~ — 400V~
500V~ — 500V~
Rated Insulation Voltage 600V AC 500V~
Dielectric Withstand 2200V AC 2500V~
Repetitive Peak 200…480V AC: 1400V
200…600V AC: 1600V
200…480V~: 1400V
500V~: 1600V
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category 1…37 A AC-53b: 3.5-15:3585
43…60 A AC-53b: 4.5-30:1770
85 A AC-53b: 4.5-30:3570
108 A AC-53b: 4.5-30:1770
135 A AC-53b: 3.5-30: 1770
201…251 A AC-53b: 3.5-30: 1770
317…480 A AC-53b: 3.5-30: 1770
Number of Poles Equipment designed for 3-phase only
Rated Impulse Voltage 6 kV
DV/DT Protection 1000V/ms
Overvoltage Category III
Short Circuit
Protection
SCPD Performance Type 1♣ ∆ 
Non-Time Delay Thermal Magnetic Circuit Breaker High Capacity Time Delay
Class CC/J/L
SCPD List§  Max. Standard Available Fault Max. Standard Fuse [A]‡  Max. Standard Available Fault Max. Circuit Breaker [A] Max. Standard Available Fault Max. Fuse [A]
Line Device Operational Current Rating [A] 3 5 kA 12 5 kA 15 70 kA 6
9 5 kA 30 5 kA 30 70 kA 15
16 5 kA 60 5 kA 60 70 kA 30
19 5 kA 70 5 kA 70 70 kA 40
25 5 kA 100 5 kA 100 70 kA 50
30 10 kA 110 10 kA 110 70 kA 60
37 10 kA 125 10 kA 125 70 kA 60
43 10 kA 150 10 kA 150 70 kA 90
60 10 kA 225 10 kA 225 70 kA 125
85 10 kA 300 10 kA 300 70 kA 175
108 10 kA 400 10 kA 300 70 kA 200
135 10 kA 500 10 kA 400 70 kA 250
201 18 kA 600 18 kA 600 70 kA 350
251 18 kA 700 18 kA 700 70 kA 400
317 30 kA 800 30 kA 800 69 kA 500
361 30 kA 1000 30 kA 1000 69 kA 600
480 42 kA 1200 42 kA 1200 69 kA 800
Delta Device Operational Current Rating [A] 5.1 5 kA 15 5 kA 15 70 kA 10
16 5 kA 60 5 kA 60 70 kA 30
27.6 5 kA 70 5 kA 70 70 kA 60
32.8 5 kA 125 5 kA 125 70 kA 70
43 5 kA 150 5 kA 150 70 kA 90
52 10 kA 200 10 kA 200 70 kA 100
64 10 kA 250 10 kA 250 70 kA 100
74 10 kA 250 10 kA 250 70 kA 150
104 10 kA 400 10 kA 300 70 kA 225
147 10 kA 400 10 kA 400 70 kA 300
187 10 kA 600 10 kA 500 70 kA 400
234 10 kA 700 10 kA 700 70 kA 400
348 18 kA 1000 18 kA 1000 70 kA 600
435 18 kA 1200 18 kA 1200 69 kA 800
549 30 kA 1600 30 kA 1600 69 kA 1000
625 30 kA 1600 30 kA 1600 69 kA 1200
831 42 kA 1600 30 kA 1600 69 kA 1600
831 42 kA 1600 42 kA 1200 69 kA 1600
  
‡ Non-time delay fuses (K5).
§ Consult local codes for proper sizing of short-circuit protection.
♣ Type 1 performance/protection indicates that, under a short-circuit condition, the fused or circuit breaker-protected starter shall cause no danger to persons or installation but may not be suitable for further service without repair or replacement.
∆ For short-circuit current rating (SCCR) for enclosed panel with external bypass or isolation contactor, see the Industrial Controls catalog website: www.ab.com/catalogs.

Electrical Ratings
  UL/CSA/NEMA IEC
Control Circuit Rated Operational Voltage (+10%, –15%) 100…240V AC, 24V AC/DC 100…240V~, 24V AC/DC
Rated Insulation Voltage 250V 250V~
Rated Impulse Voltage 2.5 kV 4 kV
Dielectric Withstand 1500V AC 2000V~
Overvoltage Category II III⋆ 
Operating Frequency 50/60 Hz 50/60 Hz
Input onstate voltage minimum, during start (IN1, IN2) 85V AC, 19.2V DC / 19.2V AC
Input onstate current (IN1, IN2) 9.8 mA @120V AC/19.6 mA @ 240V AC, 7.3 mA @ 24V AC/DC
Input offstate voltage maximum (IN1, IN2) 40V AC, 17V DC / 12V AC
Input offstate current @ input offstate voltage (IN1, IN2) <10 mA, <12 mA
Control Power with Fan, during start 3…37 A 215 mA @ 120V AC / 180 mA @ 240V AC, 800 mA @ 24V DC / 660 mA @ 24V AC
43…85 A 200 mA @ 120V AC / 100 mA @ 240V AC, 700 mA @ 24V AC/DC
  Fan Power Control Power
108…135 A 20VA 200 mA @ 120V AC / 120 mA @ 240V AC, 600 mA @ 24V AC/DC
201…251 A 40VA
317…480 A 60VA
Control Power without Fan, during start 3…37 A 205 mA @ 120V AC / 145 mA @ 240V AC, 705 mA @ 24V DC / 580 mA @ 24V AC
Steady State Heat Dissipation and Overload Current Range Controller Rating [A] Steady State Heat Dissipation [W] Overload Current Range [A]
3 11 1…3
9 12 3…9
16 14 5.3…16
19 15 6.3…19
25 17 9.2…27.7
30 19 10…30
37 24 12.3…37
43 34 14.3…43
60 50 20…60
85 82 28.3…85
108 62 27…108
135 75 34…135
201 129 67…201
251 147 84…251
317 174 106…317
361 194 120…361
480 239 160…480
  

Auxiliary Contacts
  UL/CSA/NEMA IEC
Rated Operational Voltage 250V AC/30V DC 250V~/30V DC
Rated Insulation Voltage 250V 250V~
Rated Impulse Voltage 2.5 kV 4 kV
Dielectric Withstand 1500V AC 2000V~
Overvoltage Category II III⋆ 
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category D300/D300 AC-15/DC
TB-97, -98
(OVLD/Fault)
Type of Control Circuit Electromagnetic relay
Number of Contacts 1
Type of Contacts Normally Open (N.O.)
Type of Current AC/DC
Rated Operational Current (max.) 0.6 A @ 120V~ and 0.3 A @ 240V~
Conventional Thermal Current Ith 1 A
Make/Break VA 432/72
TB-13, -14 Aux 1
(Normal/Up-to-Speed)
Type of Control Circuit Electromagnetic relay
Number of Contacts 1
Type of Contacts Normally Open (N.O.)
Type of Current AC/DC
Rated Operational Current (max.) 0.6 A @ 120V~ and 0.3 A @ 240V~
Conventional Thermal Current Ith 1 A
Make/Break VA 432/72
  
⋆ Overvoltage category II, when either control or auxiliary circuit is wired to a SELV or PELV circuit.

Electrical Ratings
Side-Mount Auxiliary Contacts
  UL/CSA/NEMA IEC
Rated Operational Voltage 250V AC/30V DC 250V AC/30V DC
Rated Insulation Voltage 250V 250V AC
Rated Impulse Voltage 2.5 kV 4 kV
Dielectric Withstand 1500V AC 2000V AC
Overvoltage Category II III⋆ 
Operating Frequency 50/60 Hz 50/60 Hz
TB-23, -24
(Normal/Up-to-Speed)
TB-33, -34
(Normal/Up-to-Speed)
Utilization Category C300/R150 AC-15/DC-13
Type of Control Circuit Electromagnetic relay
Number of Contacts 1
Type of Contacts Normally Open (N.O.)
Type of Current AC/DC
Rated Operational Current (max.) 1.5 A @ 120V AC, 0.75A @ 240V AC, 1.17 A @ 24V DC
Conventional Thermal Current Ith 2.5 A
Make/Break VA 1800/180V AC, 28V DC (resistive)
TB-11, -12
(Normal/Up-to-Speed)
Type of Control Circuit B300/R300 AC-15/DC-13
Type of Control Circuit Electromagnetic relay
Number of Contacts 1
Type of Contacts Normally Closed (N.C.)
Type of Current AC/DC
Rated Operational Current (max.) 3 A @ 120V AC, 1.5A @ 240V AC, 1.17 A @ 24V DC
Conventional Thermal Current Ith 5 A
Make/Break VA 3600/360VA, 28VA (DC resistive)
  
⋆ Overvoltage category II, when either control or auxiliary circuit is wired to a SELV or PELV circuit.

Environmental
Operating Temperature Range -5…+50 °C (23…122 °F) (open)
-5…+40 °C (23…104 °F) (enclosed)
Storage and Transportation Temperature Range -25…+85 °C (-13…+185 °F)
Altitude 2000 m (6560 ft)
Humidity 5…95% (non-condensing)
Pollution Degree 2
Type of Protection IP2X
  

Mechanical Ratings
Resistance to Vibration Operational 1.0 G Peak, 0.15 mm (0.006 in.) displacement
Non-Operational 2.5 G Peak, 0.38 mm (0.015 in.) displacement
Resistance to Shock Operational 15 G
Non-Operational 30 G
Line Power Terminals Cable Size
Tightening Torque
3…37 A 2.5…25 mm2 (14…4 AWG)
2.3…2.8 N•m (20…25 in•lbs)
43…85 A 2.5…95 mm2 (14…3/0 AWG)
11.3…12.4 N•m (100…110 in•lbs)
108…135 A 23 N•m (200 in•lbs)
201…251 A Two M10 x 1.5 diameter holes per power pole
317…480 A Two M12 x 1.75 diameter holes per power pole
Load Power Terminals Cable Size
Tightening Torque
3…37 A 2.5…16 mm2 (14…6 AWG)
2.3…2.5 N•m (20…22.5 in•lbs)
43…85 A 2.5…50 mm2 (14…1 AWG)
11.3…12.4 N•m (100…110 in•lbs)
108…135 A 23 N•m (200 in•lbs)
201…251 A Two M10 x 1.5 diameter holes per power pole
317…480 A Two M12 x 1.75 diameter holes per power pole
Control Terminals Cable Size
Tightening Torque
All 0.2…2.5 mm2 (24…14 AWG)
0.5…0.9 N•m (4.4…8.0 in•lbs)
Other
  UL/CSA/NEMA IEC
EMC Emission Levels Conducted Radio Frequency Emissions Class A
Radiated Emissions Class A
EMC Immunity Levels Electrostatic Discharge 4 kV Contact and 8 kV Air Discharge 8 kV Air Discharge
Radio Frequency Electromagnetic Field Per EN/IEC 60947-4-2
Fast Transient Per EN/IEC 60947-4-2
Surge Transient Per EN/IEC 60947-4-2
  

SMC-3 Overload Trip Curves

Trip Class 10

Click to enlarge - 150-7-54-1


Trip Class 15

Click to enlarge - 150-7-54-2


Trip Class 20

Click to enlarge - 150-7-54-3


Starts per Hour Curves

Click to enlarge - start_curve3


Click to enlarge - start_curve4


Click to enlarge - SMC-3_Std Fan


Click to enlarge - smc3startsperhr108_135


Click to enlarge - smc3startsperhr201_480

Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. All dimensions are subject to change.

Open Type

Click to enlarge - dims_delta


Controller
Rating [A]
A B C D E F G Mounting
Hole Size
Weight
kg (lbs)
1…37 44.8 (1-49/64) 139.7 (5-1/2) 100 (4-21/64) 35 (1-3/8) 132 (5-13/64) 46.4 (1.81) 2 (1/16) 4.6 (0.18) 0.86 (1.9)
43…85 72 (2.83) 206 (8.11) 130 (5.12) 55 (2.17) 198 (7.8) 102 (4.02) 2 (1/16) 5.3 (0.21) 2.25 (5.0)
108…135 196.4 (7.74) 443.7 (17.47) 205.2 (8.08) 166.6 (6.56) 367 (14.45) 7.5 (0.295) 15 (33)
201…251 225 (8.86) 560 (22.05) 265.3 (10.45) 150 (5.91) 504.1 (19.85) 11.5 (0.45) 30.4 (67)
317…480 290 (11.42) 600 (23.62) 298 (11.73) 200 (7.87) 539.2 (21.23) 11.5 (0.45) 45.8 (101)
  

Minimum Enclosure Size

Click to enlarge - 150-7_55-2


Controller
Rating [A]
B Height A Width C Depth Fan Requirements
1…37 A 305 (12) 224 (9) 152 (6) none
43…85 A 406 (16) 305 (12) 203 (8) none
108…135 A 762 (30) 610 (24) 305 (12) none
201…251 A 965 (38) 762 (30) 356 (14) none
317…480 A 1295 (51) 914 (36) 356 (14) none
  

Enclosed Type Line-Connected Controllers

Click to enlarge - SMC dimension _1
Figure 1 — Wall-Mount


Click to enlarge - SMC dimension _2
Figure 2 — Wall-Mount


Click to enlarge - SMC dimension _3
Figure 3 — Floor-Mount


Click to enlarge - SMC dimension _4
Figure 4 — Floor-Mount


Controller Rating [A] Bulletin With Option Dimension Figure No. Dimensions in inches (mm)
A (Width) B (Height) C (Depth) D (Mtg. Dim.) E (Mtg. Dim.) F (Mtg. Dim.)
SMC-3 Combination Controller
3…37 152H,153H Any 1 16 (406) 14 (356) 8 (203) 4.38 (111) 12.40 (315) 7.0 (178)
43 152H Any 1 16 (406) 14 (356) 8 (203) 4.38 (111) 12.40 (315) 7.0 (178)
153H Any 1 16 (406) 24 (610) 10 (254) 0.75 (19) 22.5 (572) 14.5 (368)
60 152H, 153H Any 1 16 (406) 24 (610) 9 (229) 0.75 (19) 22.5 (572) 14.5 (368)
152H Any 1 24 (610) 30 (762) 12 (305) 0.75 (19) 28.5 (724) 22.5 (572)
85 152H Any 1⋆  16 (406) 24 (610) 9 (229) 0.75 (19) 22.5 (572) 14.5 (368)
Any 1‡  24 (610) 30 (762) 12 (305) 0.75 (19) 28.5 (724) 22.5 (572)
153H Any 1 16 (406) 24 (610) 9 (229) 0.75 (19) 22.5 (572) 14.5 (368)
108 152H,153H Any 1 30 (762) 38 (965) 14 (356) 0.75 (19) 36.5 (927) 28.5 (724)
135 152H,153H Any 1 30 (762) 38 (965) 14 (356) 0.75 (19) 36.5 (927) 28.5 (724)
201 152H,153H 1 30 (762) 38 (965) 14 (356) 0.75 (19) 36.5 (927) 28.5 (724)
152H,152B,153H,153B Any 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
251 152H,153H 1 30 (762) 38 (965) 14 (356) 0.75 (19) 36.5 (927) 28.5 (724)
152H,152B,153H,153B Any 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
317 153H 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
BP,NB 1 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)
153B 1 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)
152H,152B 2 38 (965) 60 (1524) 17 (431) 33.88 (861) 1.75 (45) 61.69 (1567)
152H BP 2 38 (965) 60 (1524) 17 (431) 33.88 (861) 1.75 (45) 61.69 (1567)
152H,152B,153H,153B NB,NI 3 40 (1016) 84 (2134) 18 (457)
361 153H 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
BP,NB 1 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)
153B 1 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)
152H,152B 2 38 (965) 60 (1524) 17 (431) 33.88 (861) 1.75 (45) 61.69 (1567)
152H BP 2 38 (965) 60 (1524) 17 (431) 33.88 (861) 1.75 (45) 61.69 (1567)
152H,152B,153H,153B NB,NI 3 40 (1016) 84 (2134) 18 (457)
480 153H 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
BP 3♣  40 (1016) 84 (2134) 18 (457)
152H,153B Any 3 40 (1016) 84 (2134) 18 (457)
152H 4♣  20 (508) 91.5 (2324) 20 (508)
152H,152B BP,NB 4♣  35 (889) 91.5 (2324) 20 (508)
  
⋆ Rating 20 Hp @208V, 25 Hp @240V, 50 Hp @ 480V, 60 Hp @ 600V
‡ Rating 25 Hp @208V, 30 Hp @240V, 60 Hp @ 480V, 75 Hp @ 600V
♣ 200 Hp @ 240V AC, 400 Hp @480V, 500 Hp @ 600V

Controller Rating [A] Bulletin With Option Dimension Figure No. Dimensions in inches (mm)
A (Width) B (Height) C (Depth) D (Mtg. Dim.) E (Mtg. Dim.) F (Mtg. Dim.)
SMC-3 Non-Combination Controller
3…37 150 1 8 (203) 12 (305) 6 (152) 2.44 (62) 10.43 (265) 3.0 (76)
6P 12 (305) 12 (305) 6 (152) 2.41 (61) 10.43 (265) 7.0 (178)
43…85 150 1 8 (203) 14 (356) 8 (203) 2.44 (62) 12.40 (315) 3.0 (76)
6P 16 (406) 14 (356) 8 (203) 4.38 (111) 12.40 (315) 7.0 (178)
108…135 150 Any 1 24 (610) 30 (762) 12 (305) 0.75 (19) 28.5 (724) 22.5 (572)
201…251 150 1 30 (762) 38 (965) 14 (356) 0.75 (19) 36.5 (927) 28.5 (724)
150, 150B BP,NB,NI,6P 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
317…361 150 Any 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
150B 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
NI, 6P 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
BP,NI, 6P 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)
480 150 1 36 (914) 51 (1295) 14 (356) 0.75 (19) 49.5 (1257) 34.5 (876)
150, 150B BP,NB,NI,6P 36 (914) 60 (1524) 14 (356) 0.75 (19) 58.5 (1486) 34.5 (876)