Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Soft Starters > SMC™-3 Smart Motor Controllers
SMC™-3 Smart Motor Controllers
| Introduction | Standards Compliance and Certifications | Modes of Operation | Description of Features | Cat. No. Explanation | Product Selection |
| Typical Wiring Diagrams | Specifications | Approximate Dimensions | Enclosed Options | Accessories |
| Standard Features | ||||||||
| Selectable Start Times | 2, 5, 10, 15, 20, 25, or 30 s | |||||||
| Selectable Initial Torque | 0%, 25%, 35%, and 65% of locked rotor torque | |||||||
| Selectable Current Limit | 150%, 250%, 350%, and 450% of full load current | |||||||
| Selectable Kick Start — 450% FLA | 0, 0.5, 1.0, or 1.5 s | |||||||
| Selectable Soft Stop | Off, 100%, 200%, or 300% of the start time setting when wired | |||||||
| Electrical Ratings | ||||||||
| UL/CSA/NEMA | IEC | |||||||
| Power Circuit | Rated Operation Voltage | 200…480V AC 200…600V AC |
200…480V~ — 400V~ 500V~ — 500V~ |
|||||
| Rated Insulation Voltage | 600V AC | 500V~ | ||||||
| Dielectric Withstand | 2200V AC | 2500V~ | ||||||
| Repetitive Peak | 200…480V AC: 1400V 200…600V AC: 1600V |
200…480V~: 1400V 500V~: 1600V |
||||||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||||||
| Utilization Category | 1…37 A | — | AC-53b: 3.5-15:3585 | |||||
| 43…60 A | — | AC-53b: 4.5-30:1770 | ||||||
| 85 A | — | AC-53b: 4.5-30:3570 | ||||||
| 108 A | — | AC-53b: 4.5-30:1770 | ||||||
| 135 A | — | AC-53b: 3.5-30: 1770 | ||||||
| 201…251 A | — | AC-53b: 3.5-30: 1770 | ||||||
| 317…480 A | — | AC-53b: 3.5-30: 1770 | ||||||
| Number of Poles | Equipment designed for 3-phase only | |||||||
| Rated Impulse Voltage | 6 kV | |||||||
| DV/DT Protection | 1000V/ms | |||||||
| Overvoltage Category | III | |||||||
| Short Circuit Protection |
SCPD Performance | Type 1 | ||||||
| Non-Time Delay | Thermal Magnetic Circuit Breaker | High Capacity Time Delay Class CC/J/L |
||||||
| SCPD List | Max. Standard Available Fault | Max. Standard Fuse (A)T | Max. Standard Available Fault | Max. Circuit Breaker (A) | Max. Standard Available Fault | Max. Fuse (A) | ||
| Line Device Operational Current Rating (A) | 3 | 5 kA | 12 | 5 kA | 15 | 70 kA | 6 | |
| 9 | 5 kA | 30 | 5 kA | 30 | 70 kA | 15 | ||
| 16 | 5 kA | 60 | 5 kA | 60 | 70 kA | 30 | ||
| 19 | 5 kA | 70 | 5 kA | 70 | 70 kA | 40 | ||
| 25 | 5 kA | 100 | 5 kA | 100 | 70 kA | 50 | ||
| 30 | 10 kA | 110 | 10 kA | 110 | 70 kA | 60 | ||
| 37 | 10 kA | 125 | 10 kA | 125 | 70 kA | 60 | ||
| 43 | 10 kA | 150 | 10 kA | 150 | 70 kA | 90 | ||
| 60 | 10 kA | 225 | 10 kA | 225 | 70 kA | 125 | ||
| 85 | 10 kA | 300 | 10 kA | 300 | 70 kA | 175 | ||
| 108 | 10 kA | 400 | 10 kA | 300 | 70 kA | 200 | ||
| 135 | 10 kA | 500 | 10 kA | 400 | 70 kA | 250 | ||
| 201 | 18 kA | 600 | 18 kA | 600 | 70 kA | 350 | ||
| 251 | 18 kA | 700 | 18 kA | 700 | 70 kA | 400 | ||
| 317 | 30 kA | 800 | 30 kA | 800 | 69 kA | 500 | ||
| 361 | 30 kA | 1000 | 30 kA | 1000 | 69 kA | 600 | ||
| 480 | 42 kA | 1200 | 42 kA | 1200 | 69 kA | 800 | ||
| Delta Device Operational Current Rating (A) | 5.1 | 5 kA | 15 | 5 kA | 15 | 70 kA | 10 | |
| 16 | 5 kA | 60 | 5 kA | 60 | 70 kA | 30 | ||
| 27.6 | 5 kA | 70 | 5 kA | 70 | 70 kA | 60 | ||
| 32.8 | 5 kA | 125 | 5 kA | 125 | 70 kA | 70 | ||
| 43 | 5 kA | 150 | 5 kA | 150 | 70 kA | 90 | ||
| 52 | 10 kA | 200 | 10 kA | 200 | 70 kA | 100 | ||
| 64 | 10 kA | 250 | 10 kA | 250 | 70 kA | 100 | ||
| 74 | 10 kA | 250 | 10 kA | 250 | 70 kA | 150 | ||
| 104 | 10 kA | 400 | 10 kA | 300 | 70 kA | 225 | ||
| 147 | 10 kA | 400 | 10 kA | 400 | 70 kA | 300 | ||
| 187 | 10 kA | 600 | 10 kA | 500 | 70 kA | 400 | ||
| 234 | 10 kA | 700 | 10 kA | 700 | 70 kA | 400 | ||
| 348 | 18 kA | 1000 | 18 kA | 1000 | 70 kA | 600 | ||
| 435 | 18 kA | 1200 | 18 kA | 1200 | 69 kA | 800 | ||
| 549 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1000 | ||
| 625 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1200 | ||
| 831 | 42 kA | 1600 | 30 kA | 1600 | 69 kA | 1600 | ||
| 831 | 42 kA | 1600 | 42 kA | 1200 | 69 kA | 1600 | ||
| T Non-time delay fuses (K5). | ||||||||
| Consult local codes for proper sizing of short-circuit protection. | ||||||||
| Electrical Ratings | |||||
| UL/CSA/NEMA | IEC | ||||
| Control Circuit | Rated Operational Voltage (+10%, 15%) | 100…240V AC, 24V AC/DC | 100…240V~, 24V AC/DC | ||
| Rated Insulation Voltage | 250V | 250V~ | |||
| Rated Impulse Voltage | 2.5 kV | 4 kV | |||
| Dielectric Withstand | 1500V AC | 2000V~ | |||
| Overvoltage Category | II | III¬ | |||
| Operating Frequency | 50/60 Hz | 50/60 Hz | |||
| Input onstate voltage minimum, during start (IN1, IN2) | 85V AC, 19.2V DC / 19.2V AC | ||||
| Input onstate current (IN1, IN2) | 9.8 mA @120V AC/19.6 mA @ 240V AC, 7.3 mA @ 24V AC/DC | ||||
| Input offstate voltage maximum (IN1, IN2) | 40V AC, 17V DC / 12V AC | ||||
| Input offstate current @ input offstate voltage (IN1, IN2) | <10 mA, <12 mA | ||||
| Control Power with Fan, during start | 3…37 A | 215 mA @ 120V AC / 180 mA @ 240V AC, 800 mA @ 24V DC / 660 mA @ 24V AC | |||
| 43…85 A | 200 mA @ 120V AC / 100 mA @ 240V AC, 700 mA @ 24V AC/DC | ||||
| Fan Power | Control Power | ||||
| 108…135 A | 20VA | 200 mA @ 120V AC / 120 mA @ 240V AC, 600 mA @ 24V AC/DC | |||
| 201…251 A | 40VA | ||||
| 317…480 A | 60VA | ||||
| Control Power without Fan, during start | 3…37 A | 205 mA @ 120V AC / 145 mA @ 240V AC, 705 mA @ 24V DC / 580 mA @ 24V AC | |||
| Steady State Heat Dissipation and Overload Current Range | Controller Rating (A) | Steady State Heat Dissipation (W) | Overload Current Range (A) | ||
| 3 | 11 | 1…3 | |||
| 9 | 12 | 3…9 | |||
| 16 | 14 | 5.3…16 | |||
| 19 | 15 | 6.3…19 | |||
| 25 | 17 | 9.2…27.7 | |||
| 30 | 19 | 10…30 | |||
| 37 | 24 | 12.3…37 | |||
| 43 | 34 | 14.3…43 | |||
| 60 | 50 | 20…60 | |||
| 85 | 82 | 28.3…85 | |||
| 108 | 62 | 27…108 | |||
| 135 | 75 | 34…135 | |||
| 201 | 129 | 67…201 | |||
| 251 | 147 | 84…251 | |||
| 317 | 174 | 106…317 | |||
| 361 | 194 | 120…361 | |||
| 480 | 239 | 160…480 | |||
| Auxiliary Contacts | |||
| UL/CSA/NEMA | IEC | ||
| Rated Operational Voltage | 250V AC/30V DC | 250V~/30V DC | |
| Rated Insulation Voltage | 250V | 250V~ | |
| Rated Impulse Voltage | 2.5 kV | 4 kV | |
| Dielectric Withstand | 1500V AC | 2000V~ | |
| Overvoltage Category | II | III¬ | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| Utilization Category | D300/D300 | AC-15/DC | |
| TB-97, -98 (OVLD/Fault) |
Type of Control Circuit | Electromagnetic relay | |
| Number of Contacts | 1 | ||
| Type of Contacts | Normally Open (N.O.) | ||
| Type of Current | AC/DC | ||
| Rated Operational Current (max.) | 0.6 A @ 120V~ and 0.3 A @ 240V~ | ||
| Conventional Thermal Current Ith | 1 A | ||
| Make/Break VA | 432/72 | ||
| TB-13, -14 (Normal/Up-to-Speed) |
Type of Control Circuit | Electromagnetic relay | |
| Number of Contacts | 1 | ||
| Type of Contacts | Normally Open (N.O.) | ||
| Type of Current | AC/DC | ||
| Rated Operational Current (max.) | 0.6 A @ 120V~ and 0.3 A @ 240V~ | ||
| Conventional Thermal Current Ith | 1 A | ||
| Make/Break VA | 432/72 | ||
| ¬ Overvoltage category II, when either control or auxiliary circuit is wired to a SELV or PELV circuit. | |||
| Electrical Ratings | |||
| Side-Mount Auxiliary Contacts | |||
| UL/CSA/NEMA | IEC | ||
| Rated Operational Voltage | 250V AC/30V DC | 250V AC/30V DC | |
| Rated Insulation Voltage | 250V | 250V AC | |
| Rated Impulse Voltage | 2.5 kV | 4 kV | |
| Dielectric Withstand | 1500V AC | 2000V AC | |
| Overvoltage Category | II | III¬ | |
| Operating Frequency | 50/60 Hz | 50/60 Hz | |
| TB-23, -24 (Normal/Up-to-Speed) TB-33, -34 (Normal/Up-to-Speed) |
Utilization Category | C300/R150 | AC-15/DC-13 |
| Type of Control Circuit | Electromagnetic relay | ||
| Number of Contacts | 1 | ||
| Type of Contacts | Normally Open (N.O.) | ||
| Type of Current | AC/DC | ||
| Rated Operational Current (max.) | 1.5 A @ 120V AC, 0.75A @ 240V AC, 1.17 A @ 24V DC | ||
| Conventional Thermal Current Ith | 2.5 A | ||
| Make/Break VA | 1800/180V AC, 28V DC (resistive) | ||
| TB-11, -12 (Normal/Up-to-Speed) |
Type of Control Circuit | B300/R300 | AC-15/DC-13 |
| Type of Control Circuit | Electromagnetic relay | ||
| Number of Contacts | 1 | ||
| Type of Contacts | Normally Open (N.O.) | ||
| Type of Current | AC/DC | ||
| Rated Operational Current (max.) | 3 A @ 120V AC, 1.5A @ 240V AC, 1.17 A @ 24V DC | ||
| Conventional Thermal Current Ith | 5 A | ||
| Make/Break VA | 3600/360V AC, 28V DC (resistive) | ||
| ¬ Overvoltage category II, when either control or auxiliary circuit is wired to a SELV or PELV circuit. | |||
| Environmental | |
| Operating Temperature Range | -5…+50 °C (23…122 °F) (open) -5…+40 °C (23…104 °F) (enclosed) |
| Storage and Transportation Temperature Range | -25…+85 °C (-13…+185 °F) |
| Altitude | 2000 m (6560 ft) |
| Humidity | 5…95% (non-condensing) |
| Pollution Degree | 2 |
| Type of Protection | IP2X |
| Mechanical Ratings | ||||
| Resistance to Vibration | Operational | 1.0 G Peak, 0.15 mm (0.006 in.) displacement | ||
| Non-Operational | 2.5 G Peak, 0.38 mm (0.015 in.) displacement | |||
| Resistance to Shock | Operational | 15 G | ||
| Non-Operational | 30 G | |||
| Line Power Terminals | Cable Size Tightening Torque |
3…37 A | 2.5…25 mm2 (14…4 AWG) 2.3…2.8 Nm (20…25 in-lbs) |
|
| 43…85 A | 2.5…95 mm2 (14…3/0 AWG) 11.3…12.4 Nm (100…110 in-lbs) |
|||
| 108…135 A | 23 Nm (200 in-lbs) | |||
| 201…251 A | Two M10 x 1.5 diameter holes per power pole | |||
| 317…480 A | Two M12 x 1.75 diameter holes per power pole | |||
| Load Power Terminals | Cable Size Tightening Torque |
3…37 A | 2.5…16 mm2 (14…6 AWG) 2.3…2.5 Nm (20…22.5 in-lbs) |
|
| 43…85 A | 2.5…50 mm2 (14…1 AWG) 11.3…12.4 Nm (100…110 in-lbs) |
|||
| 108…135 A | 23 Nm (200 in-lbs) | |||
| 201…251 A | Two M10 x 1.5 diameter holes per power pole | |||
| 317…480 A | Two M12 x 1.75 diameter holes per power pole | |||
| Control Terminals | Cable Size Tightening Torque |
All | 0.2…2.5 mm2 (24…14 AWG) 0.5…0.9 Nm (4.4…8.0 in-lbs) |
|
| Other | ||||
| UL/CSA/NEMA | IEC | |||
| EMC Emission Levels | Conducted Radio Frequency Emissions | — | Class A | |
| Radiated Emissions | — | Class A | ||
| EMC Immunity Levels | Electrostatic Discharge | 4 kV Contact and 8 kV Air Discharge | 8 kV Air Discharge | |
| Radio Frequency Electromagnetic Field | — | Per EN/IEC 60947-4-2 | ||
| Fast Transient | — | Per EN/IEC 60947-4-2 | ||
| Surge Transient | — | Per EN/IEC 60947-4-2 | ||
SMC-3 Overload Trip Curves
Trip Class 10
|
Trip Class 15
|
Trip Class 20
|
Starts per Hour Curves
|
|
|
|
|