Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Soft Starters > SMC™ Flex Smart Motor Controllers
SMC™ Flex Smart Motor Controllers
| Introduction | Standards Compliance and Certifications | Modes of Operation | Introduction | Cat. No. Explanation |
| Product Selection | Control Options (open and enclosed) | Accessories | Specifications | Approximate Dimensions and Shipping Weights |
| Functional Design Specifications | |||
| Standard Features | Installation | Power Wiring | Standard squirrel-cage induction motor or a Wye-Delta, six-lead motor. |
| Control Wiring | 2- and 3-wire control for a wide variety of applications. | ||
| Setup | Keypad | Front keypad and backlit LCD display. | |
| Software | Parameter values can be downloaded to the SMC-Flex Controller with DriveTools programming software and the Cat. No. 20-COMM… DPI communication module. | ||
| Communications | One DPI provided for connection to optional human interface and communication modules. | ||
| Starting and Stopping Modes | Soft Start Current Limit Start Dual Ramp Full Voltage Linear Speed Acceleration Preset Slow Speed Soft Stop |
||
| Protection and Diagnostics | Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. | ||
| Metering | Amps, volts, kW, kWH, mW, mWH, elapsed time, power factor, motor thermal capacity usage. | ||
| Alarm Contact | Overload, underload, undervoltage, overvoltage, unbalance, jam, stall, and ground fault | ||
| Status Indication | Stopped, starting, stopping, at speed, alarm, and fault. | ||
| Auxiliary Contacts | Four fully programmable contacts as normal/up-to-speed/fault/alarm/network (N.O./N.C.), or external bypass (N.O. only). | ||
| Optional Features | Pump Control | Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting time is adjustable from 0…30 s. Stopping time is adjustable from 0…120 s. | |
| Braking Control | SMB Smart Motor Braking |
Provides motor braking without additional equipment for applications that require the motor to stop quickly. Braking current is adjustable from 0…400% of the motors full-load current rating. | |
| Accu-Stop | Provides controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7% or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Braking current is programmable from 0…450% of full-load current. | ||
| Slow Speed with Braking | Used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop. | ||
Wiring Diagram — Line Controller
|
¬ Customer supplied.
| Electrical Ratings | ||||
| Device Rating | UL/CSA/NEMA | IEC | ||
| Power Circuit | Rated Operation Voltage | 480V | 200…480V AC (15%, +10%) | 200…415V |
| 600V | 200…600V AC (15%, +10%) | 200…500V | ||
| 690V | 230…600V AC (15%, +10%) | 230…690V/Y (15%, +10%) | ||
| Rated Insulation Voltage | 480V | N/A | 500V | |
| 600V | 500V | |||
| 690V | 690V | |||
| Rated Impulse Voltage | 480V | N/A | 6000V | |
| 600V | ||||
| 690V | ||||
| Dielectric Withstand | 480V | 2200V AC | 2500V | |
| 600V | ||||
| 690V | ||||
| Repetitive Peak Inverse Voltage Rating | 480V | 1400V | 1400V | |
| 600V | 1600V | 1600V | ||
| 690V | 1800V | 1800V | ||
| Operating Frequency | All | 50/60 Hz | ||
| Utilization Category | 5…480 A | MG 1 | AC-53B:3.0-50:1750 | |
| 625…1250 A | MG 1 | AC-53B:3.0-50:3550 | ||
| Protection Against Electrical Shock | 5…85 A | N/A | IP20 | |
| 108…480 A | IP2X (with terminal covers) | |||
| 625…1250 A | IP00 (open device) | |||
| DV/DT Protection | 480V & 600V | RC Snubber Network | ||
| 690V | None | |||
| Transient Protection | 480V & 600V | Metal Oxide Varistors: 220 Joules | ||
| 690V | None | |||
| Control Circuit | Rated Operational Voltage§ | 5…480 A | 100…240V AC or 24V AC/DC | |
| 625…1250 A | 110/120V AC and 230/240V AC | |||
| Rated Insulation Voltage | All | N/A | 240V | |
| Rated Impulse Voltage | All | N/A | 3000V | |
| Dielectric Withstand | All | 1600V AC | 2000V | |
| Operating Frequency | All | 50/60 Hz | ||
| Input onstate voltage minimum | 85V AC, 19.2V DC / 20.4V AC | |||
| Input onstate current | 20 mA @120V AC / 40 mA @ 240V AC, 7.6 mA @ 24V AC/DC | |||
| Input offstate voltage maximum | 50V AC, 10V DC / 12V AC | |||
| Input offstate current @ input offstate voltage | <10 mA AC, <3 mA DC | |||
| § 690V power is only available with 100…240V control. | ||||
| Electrical Ratings | ||||||||
| Short-Circuit Protection |
SCPD Performance 200…600V | Type 1 | ||||||
| SCCR List¬ | Max. Standard Available Fault | Max. Standard Fuse (A)T | Max. Standard Available Fault | Max. Circuit Breaker (A) | Max. High Fault | Max. Fuse (A) | ||
| Line Device Operational Current Rating (A) | 5 | 5 kA | 20 | 5 kA | 20 | 70 kA | 10 | |
| 25 | 5 kA | 100 | 5 kA | 100 | 70 kA | 50 | ||
| 43 | 10 kA | 150 | 10 kA | 150 | 70 kA | 90 | ||
| 60 | 10 kA | 225 | 10 kA | 225 | 70 kA | 125 | ||
| 85 | 10 kA | 300 | 10 kA | 300 | 70 kA | 175 | ||
| 108 | 10 kA | 400 | 10 kA | 300 | 70 kA | 200 | ||
| 135 | 10 kA | 500 | 10 kA | 400 | 70 kA | 225 | ||
| 201 | 18 kA | 600 | 18 kA | 600 | 70 kA | 350 | ||
| 251 | 18 kA | 700 | 18 kA | 700 | 70 kA | 400 | ||
| 317 | 30 kA | 800 | 30 kA | 800 | 69 kA | 500 | ||
| 361 | 30 kA | 1000 | 30 kA | 1000 | 69 kA | 600 | ||
| 480 | 42 kA | 1200 | 42 kA | 1200 | 69 kA | 800 | ||
| 625 | 42 kA | 1600 | 42 kA | 1600 | 74 kA | 1600 | ||
| 780 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 970 | 85 kA | 2500 | 85 kA | 2500 | 85 kA | 2500 | ||
| 1250 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| Delta Device Operational Current Rating (A) | 8.7 | 5 kA | 35 | 5 kA | 35 | 70 kA | 17.5 | |
| 43 | 5 kA | 150 | 5 kA | 150 | 70 kA | 90 | ||
| 74 | 10 kA | 300 | 10 kA | 300 | 70 kA | 150 | ||
| 104 | 10 kA | 400 | 10 kA | 400 | 70 kA | 200 | ||
| 147 | 10 kA | 400 | 10 kA | 400 | 70 kA | 200 | ||
| 187 | 10 kA | 600 | 10 kA | 500 | 70 kA | 300 | ||
| 234 | 10 kA | 700 | 10 kA | 700 | 70 kA | 400 | ||
| 348 | 18 kA | 1000 | 18 kA | 1000 | 70 kA | 600 | ||
| 435 | 18 kA | 1200 | 18 kA | 1200 | 70 kA | 800 | ||
| 549 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1000 | ||
| 625 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1200 | ||
| 831 | 42 kA | 1600 | 30 kA | 1600 | 69 kA | 1600 | ||
| 850 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 900 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 1200 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| 1600 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| SCPD Performance 690V | Type 1 | |||||||
| SCCR List¬ | Device Rating | Max. Standard Available Fault | Max. Ampere Tested — North American Style | Max. Ampere Tested — European Style | ||||
| Maximum FLC | 108 | 70 kA | A070URD33xxx500 | 6,9 gRB 73xxx400 6,6URD33xxx500 |
||||
| 135 | 70 kA | A070URD33xxx500 | 6,9 gRB 73xxx400 6,6URD33xxx500 |
|||||
| 201 | 70 kA | A070URD33xxx700 | 6,9 gRB 73xxx630 6,6URD33xxx700 |
|||||
| 251 | 70 kA | A070URD33xxx700 | 6,9 gRB 73xxx630 6,6URD33xxx700 |
|||||
| 317 | 70 kA | A070URD33xxx900 | 6,9 gRB 73xxx800 6,6URD33xxx900 |
|||||
| 361 | 70 kA | A070URD33xxx900 | 6,9 gRB 73xxx800 6,6URD33xxx900 |
|||||
| 480 | 70 kA | A070D33xxx1250 A100URD73xxx1250 |
9 URD 73xxx1250 6,6URD33xxx1250 |
|||||
| 625 | 70 kA | A070URD33xxx1400 | 6,6URD33xxx1400 | |||||
| 780 | 70 kA | A070URD33xxx1400 | 6,6URD33xxx1400 | |||||
| 970 | 85 kA | Two fuses in parallel A070URD33xxx1250 |
Two fuses in parallel 6,6URD33xxx1250 |
|||||
| 1250 | 85 kA | Two fuses in parallel A070URD33xxx1250 |
Two fuses in parallel 6,6URD33xxx1250 |
|||||
| ¬ Consult local codes for proper sizing of short circuit protection. | ||||||||
| T Non-time delay fuses (K5 — 5…480V (8.7…831 A) devices; Class L — 625…1250V (850…1600 A) devices). | ||||||||
| High capacity fault rating when used with time delay class CC, J, or L fuses. | ||||||||
| Electrical Ratings | |||||
| Power Requirements |
Control Module | 1…480 A | 120…240V AC | Transformer | 75 VA |
| 24V AC | Transformer | 130 VA | |||
| 24V DC | Inrush Current | 5 A | |||
| Inrush Time | 250 ms | ||||
| Transient Watts | 60 W | ||||
| Transient Time | 500 ms | ||||
| Steady State Watts | 24 W | ||||
| Minimum Allen-Bradley Power Supply | 1606-XLP50E | ||||
| 625…1250 A | 751 VA (recommended 800 VA) | ||||
| Heatsink Fan(s) (A)§ | 5…135 A, 20 VA | ||||
| 201…251 A, 40 VA | |||||
| 317…480 A, 60 VA | |||||
| 625…1250 A, 150 VA | |||||
| Steady State Heat Dissipation with Control and Fan Power (Watts) | Controller Rating (A) | 5 | 70 | ||
| 25 | 70 | ||||
| 43 | 81 | ||||
| 60 | 97 | ||||
| 85 | 129 | ||||
| 108 | 91 | ||||
| 135 | 104 | ||||
| 201 | 180 | ||||
| 251 | 198 | ||||
| 317 | 225 | ||||
| 361 | 245 | ||||
| 480 | 290 | ||||
| 625 | 446 | ||||
| 780 | 590 | ||||
| 970 | 812 | ||||
| 1250 | 1222 | ||||
| Auxiliary Contacts 19/20 (Aux #1) 29/30 (Aux #2) 31/32 (Aux #3) 33/34 (Aux #4) |
Type of Control Circuit | Electromagnetic relay | |||
| Number of Contacts | 1 | ||||
| Type of Contacts | programmable N.O./N.C. | ||||
| Type of Current | AC | ||||
| Rated Operational Current | 3 A @ 120V AC, 1.5 A @ 240V AC | ||||
| Conventional Thermal Current Ith AC/DC | 5 A | ||||
| Make/Break VA | 3600/360 | ||||
| Utilization Category | AC-15/DC | ||||
| PTC Input Ratings | Response Resistance | 3400 W ±150 W | |||
| Reset Resistance | 1600 W ±100 W | ||||
| Short-Circuit Trip Resistance | 25 W ±10 W | ||||
| Max. Voltage at PTC Terminals (RPTC = 4 kW) | < 7.5V | ||||
| Max. Voltage at PTC Terminals (RPTC = open) | 30V | ||||
| Max. No. of Sensors. | 6 | ||||
| Max. Cold Resistance of PTC Sensor Chain | 1500 W | ||||
| Response Time | 800 ms | ||||
| Tach Input | 0…5V DC, 4.5V DC = 100% Speed | ||||
| § Heatsink fans can be powered by either 110/120V AC or 220/240V AC. | |||||
| Environmental | |
| Operating Temperature Range | -5…+50 °C (23…+122 °F) (open) -5…+40 °C (23…+104 °F) (enclosed) |
| Storage and Transportation Temperature Range | 20…+75 °C |
| Altitude | 2000 m (6560 ft) |
| Humidity | 5…95% (non-condensing) |
| Pollution Degree | 2 |
| Mechanical | ||||
| Resistance to Vibration | Operational | All | 1.0 G Peak, 0.15 mm (0.006 in.) displacement | |
| Non-Operational | 5…480 A | 2.5 G Peak, 0.38 mm (0.015 in.) displacement | ||
| 625…1250 A | 1.0 G Peak, 0.15 mm (0.006 in.) displacement | |||
| Resistance to Shock | Operational | 5…85 A | 15 G | |
| 108…480 A | 5.5 G | |||
| 625…1250 A | 4 G | |||
| Non-Operational | 5…85 A | 30 G | ||
| 108…480 A | 25 G | |||
| 625…1250 A | 12 G | |||
| Construction | Power Poles | 5…85 A | Heatsink thyristor modular design | |
| Power Poles | 108…1250 A | Heatsink hockey puck thyristor modular design | ||
| Control Modules | Thermoset and Thermoplastic Moldings | |||
| Metal Parts | Plated Brass, Copper, or Painted Steel | |||
| Terminals | Power Terminals | 5…85 A | Cable size — Line Upper — 2.5…95 mm2 (14…3/0 AWG) Line Lower — 0.8…2.5 mm2 (18…14 AWG) Load Upper — 2.5…50 mm2 (14…1 AWG) Load Lower — 0.8…2.5 mm2 (18…14 AWG) Tightening torque — 14.7 Nm (130 lb.-in.) Wire strip length — 18…20 mm (0.22…0.34 in.) |
|
| 108…135 A | One M10 x 1.5 diameter hole per power pole | |||
| 201…251 A | Two M10 x 1.5 diameter holes per power pole | |||
| 317…480 A | Two M12 x 1.75 diameter holes per power pole | |||
| 625…1250 A | Two 13.5 mm (0.53 in.) diameter holes per power pole | |||
| Power Terminal Markings | NEMA, CENELEC EN50 012 | |||
| Control Terminals | M3 screw clamp | Clamping yoke connection | ||
| Other | ||||
| EMC Emission Levels | Conducted Radio Frequency Emissions Radiated Emissions |
Class A Class A |
||
| EMC Immunity Levels | Electrostatic Discharge Radio Frequency Electromagnetic Field Fast Transient Surge Transient |
8 kV Air Discharge Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 |
||
| Overload Characteristics | Current Range | Line | Delta | |
| 108 | 27…108 | 47…187 | ||
| 135 | 34…135 | 59…234 | ||
| 201 | 67…201 | 116…348 | ||
| 251 | 84…251 | 145…435 | ||
| 317 | 106…317 | 183…549 | ||
| 361 | 120…361 | 208…625 | ||
| 480 | 160…480 | 277…831 | ||
| 625 | 208…625 | 283…850 | ||
| 780 | 260…780 | 300…900 | ||
| 970 | 323…970 | 400…1200 | ||
| 1250 | 416…1250 | 533…1600 | ||
| Trip Classes Trip Current Rating Number of Poles |
10, 15, 20, and 30 117% of Motor FLC 3 |
|||
| Certifications | Open-Type Controllers | CE Marked Per Low Voltage Directive 73/23/EEC, 93/68/EEC UL Listed (File No. E96956) |
||