Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Soft Starters > SMC™ Flex Smart Motor Controllers
SMC™ Flex Smart Motor Controllers
| Introduction | Standards Compliance and Certifications | Modes of Operation | Introduction | Cat. No. Explanation |
| Product Selection | Control Options (open and enclosed) | Accessories | Specifications | Approximate Dimensions and Shipping Weights |
| Functional Design Specifications | |||
| Standard Features | Installation | Power Wiring | Standard squirrel-cage induction motor or a Wye-Delta, six-lead motor. |
| Control Wiring | 2- and 3-wire control for a wide variety of applications. | ||
| Setup | Keypad | Front keypad and backlit LCD display. | |
| Software | Parameter values can be downloaded to the SMC-Flex Controller with DriveTools programming software and the Cat. No. 20-COMM… DPI communication module. | ||
| Communications | One DPI provided for connection to optional human interface and communication modules. | ||
| Starting and Stopping Modes | Soft Start Current Limit Start Dual Ramp Full Voltage Linear Speed Acceleration Preset Slow Speed Soft Stop |
||
| Protection and Diagnostics | Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. | ||
| Metering | Amps, volts, kW, kWH, MW, MWH, elapsed time, power factor, motor thermal capacity usage. | ||
| Alarm Contact | Overload, underload, undervoltage, overvoltage, unbalance, jam, stall, and ground fault | ||
| Status Indication | Stopped, starting, stopping, at speed, alarm, and fault. | ||
| Auxiliary Contacts | Four fully programmable contacts as normal/up-to-speed/fault/alarm/network (N.O./N.C.), or external bypass (N.O. only). | ||
| Optional Features | Pump Control | Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting time is adjustable from 0…30 s. Stopping time is adjustable from 0…120 s. | |
| Braking Control | SMB Smart Motor Braking |
Provides motor braking without additional equipment for applications that require the motor to stop quickly. Braking current is adjustable from 0…400% of the motors full-load current rating. | |
| Accu-Stop | Provides controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7% or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Braking current is programmable from 0…450% of full-load current. | ||
| Slow Speed with Braking | Used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop. | ||
Wiring Diagram — Line Controller
|
⋆ Customer supplied.
| Electrical Ratings | ||||
| Device Rating | UL/CSA/NEMA | IEC | ||
| Power Circuit | Rated Operation Voltage | 480V | 200…480V AC (15%, +10%) | 200…415V |
| 600V | 200…600V AC (15%, +10%) | 200…500V | ||
| 690V | 230…600V AC (15%, +10%) | 230…690V/Y (15%, +10%) | ||
| Rated Insulation Voltage | 480V | N/A | 500V | |
| 600V | 500V | |||
| 690V | 690V | |||
| Rated Impulse Voltage | 480V | N/A | 6000V | |
| 600V | ||||
| 690V | ||||
| Dielectric Withstand | 480V | 2200V AC | 2500V | |
| 600V | ||||
| 690V | ||||
| Repetitive Peak Inverse Voltage Rating | 480V | 1400V | 1400V | |
| 600V | 1600V | 1600V | ||
| 690V | 1800V | 1800V | ||
| Operating Frequency | All | 50/60 Hz | ||
| Utilization Category | 5…480 A | MG 1 | AC-53B:3.0-50:1750 | |
| 625…1250 A | MG 1 | AC-53B:3.0-50:3550 | ||
| Protection Against Electrical Shock | 5…85 A | N/A | IP20⋆ | |
| 108…480 A | IP2X (with terminal covers) | |||
| 625…1250 A | IP00 (open device) | |||
| DV/DT Protection | 480V & 600V | RC Snubber Network | ||
| 690V | None | |||
| Transient Protection | 480V & 600V | Metal Oxide Varistors: 220 Joules | ||
| 690V | None | |||
| Control Circuit | Rated Operational Voltage♣ | 5…480 A | 100…240V AC or 24V AC/DC | |
| 625…1250 A | 110/120V AC and 230/240V AC | |||
| Rated Insulation Voltage | All | N/A | 240V | |
| Rated Impulse Voltage | All | N/A | 3000V | |
| Dielectric Withstand | All | 1600V AC | 2000V | |
| Operating Frequency | All | 50/60 Hz | ||
| Input onstate voltage minimum | 85V AC, 19.2V DC / 20.4V AC | |||
| Input onstate current | 20 mA @120V AC / 40 mA @ 240V AC, 7.6 mA @ 24V AC/DC | |||
| Input offstate voltage maximum | 50V AC, 10V DC / 12V AC | |||
| Input offstate current @ input offstate voltage | <10 mA AC, <3 mA DC | |||
| ♣ 690V power is only available with 100…240V control. | ||||
| ⋆ IP20 when largest wire size is used. Rating is possible with smaller size wire by using an insulated ferrule or lug, which reduces the largest size wire to the size used in the application. | ||||
| IP2X when largest wire size is used with Cat. No. 150-TC terminal covers. When other wire sizes are used, Cat. No. 150-TC terminal covers provide dead front protection only. | ||||
| Electrical Ratings | ||||||||
| Short-Circuit Protection |
SCPD Performance 200…600V | Type 1♣ ∆ | ||||||
| SCCR List⋆ | Max. Standard Available Fault | Max. Standard Fuse [A] | Max. Standard Available Fault | Max. Circuit Breaker [A] | Max. High Fault | Max. Fuse [A] § | ||
| Line Device Operational Current Rating [A] | 5 | 5 kA | 20 | 5 kA | 20 | 70 kA | 10 | |
| 25 | 5 kA | 100 | 5 kA | 100 | 70 kA | 50 | ||
| 43 | 10 kA | 150 | 10 kA | 150 | 70 kA | 90 | ||
| 60 | 10 kA | 225 | 10 kA | 225 | 70 kA | 125 | ||
| 85 | 10 kA | 300 | 10 kA | 300 | 70 kA | 175 | ||
| 108 | 10 kA | 400 | 10 kA | 300 | 70 kA | 200 | ||
| 135 | 10 kA | 500 | 10 kA | 400 | 70 kA | 225 | ||
| 201 | 18 kA | 600 | 18 kA | 600 | 70 kA | 350 | ||
| 251 | 18 kA | 700 | 18 kA | 700 | 70 kA | 400 | ||
| 317 | 30 kA | 800 | 30 kA | 800 | 69 kA | 500 | ||
| 361 | 30 kA | 1000 | 30 kA | 1000 | 69 kA | 600 | ||
| 480 | 42 kA | 1200 | 42 kA | 1200 | 69 kA | 800 | ||
| 625 | 42 kA | 1600 | 42 kA | 1600 | 74 kA | 1600 | ||
| 780 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 970 | 85 kA | 2500 | 85 kA | 2500 | 85 kA | 2500 | ||
| 1250 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| Delta Device Operational Current Rating [A] | 8.7 | 5 kA | 35 | 5 kA | 35 | 70 kA | 17.5 | |
| 43 | 5 kA | 150 | 5 kA | 150 | 70 kA | 90 | ||
| 74 | 10 kA | 300 | 10 kA | 300 | 70 kA | 150 | ||
| 104 | 10 kA | 400 | 10 kA | 400 | 70 kA | 200 | ||
| 147 | 10 kA | 400 | 10 kA | 400 | 70 kA | 200 | ||
| 187 | 10 kA | 600 | 10 kA | 500 | 70 kA | 300 | ||
| 234 | 10 kA | 700 | 10 kA | 700 | 70 kA | 400 | ||
| 348 | 18 kA | 1000 | 18 kA | 1000 | 70 kA | 600 | ||
| 435 | 18 kA | 1200 | 18 kA | 1200 | 70 kA | 800 | ||
| 549 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1000 | ||
| 625 | 30 kA | 1600 | 30 kA | 1600 | 69 kA | 1200 | ||
| 831 | 42 kA | 1600 | 30 kA | 1600 | 69 kA | 1600 | ||
| 850 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 900 | 42 kA | 1600 | 42 kA | 2000 | 74 kA | 1600 | ||
| 1200 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| 1600 | 85 kA | 3000 | 85 kA | 3200 | 85 kA | 3000 | ||
| SCPD Performance 690V | Type 1♣ | |||||||
| SCCR List⋆ | Device Rating | Max. Standard Available Fault | Max. Ampere Tested — North American Style | Max. Ampere Tested — European Style | ||||
| Maximum FLC | 108 | 70 kA | A070URD33xxx500 | 6,9 gRB 73xxx400 6,6URD33xxx500 |
||||
| 135 | 70 kA | A070URD33xxx500 | 6,9 gRB 73xxx400 6,6URD33xxx500 |
|||||
| 201 | 70 kA | A070URD33xxx700 | 6,9 gRB 73xxx630 6,6URD33xxx700 |
|||||
| 251 | 70 kA | A070URD33xxx700 | 6,9 gRB 73xxx630 6,6URD33xxx700 |
|||||
| 317 | 70 kA | A070URD33xxx900 | 6,9 gRB 73xxx800 6,6URD33xxx900 |
|||||
| 361 | 70 kA | A070URD33xxx900 | 6,9 gRB 73xxx800 6,6URD33xxx900 |
|||||
| 480 | 70 kA | A070D33xxx1250 A100URD73xxx1250 |
9 URD 73xxx1250 6,6URD33xxx1250 |
|||||
| 625 | 70 kA | A070URD33xxx1400 | 6,6URD33xxx1400 | |||||
| 780 | 70 kA | A070URD33xxx1400 | 6,6URD33xxx1400 | |||||
| 970 | 85 kA | Two fuses in parallel A070URD33xxx1250 |
Two fuses in parallel 6,6URD33xxx1250 |
|||||
| 1250 | 85 kA | Two fuses in parallel A070URD33xxx1250 |
Two fuses in parallel 6,6URD33xxx1250 |
|||||
| ⋆ Consult local codes for proper sizing of short circuit protection. | ||||||||
| Non-time delay fuses (K5 — 5…480V (8.7…831 A) devices; Class L — 625…1250V (850…1600 A) devices). | ||||||||
| § High capacity fault rating when used with time delay class CC, J, or L fuses. | ||||||||
| ♣ Type 1 performance/protection indicates that, under a short-circuit condition, the fused or circuit breaker-protected starter shall cause no danger to persons or installation but may not be suitable for further service without repair or replacement. | ||||||||
| ∆ For short-circuit current rating (SCCR) for enclosed panel with external bypass or isolation contactor, see the Industrial Controls catalog website: www.ab.com/catalogs. | ||||||||
| Electrical Ratings | |||||
| Power Requirements |
Control Module | 1…480 A | 120…240V AC | Transformer | 75 VA |
| 24V AC | Transformer | 130 VA | |||
| 24V DC | Inrush Current | 5 A | |||
| Inrush Time | 250 ms | ||||
| Transient Watts | 60 W | ||||
| Transient Time | 500 ms | ||||
| Steady State Watts | 24 W | ||||
| Minimum Allen-Bradley Power Supply | 1606-XLP50E | ||||
| 625…1250 A | 751 VA (recommended 800 VA) | ||||
| Heatsink Fan(s)∆ | 5…135 A, 20 VA | ||||
| 201…251 A, 40 VA | |||||
| 317…480 A, 60 VA | |||||
| 625…1250 A, 150 VA | |||||
| Steady State Heat Dissipation with Control and Fan Power (Watts) | Controller Rating [A] | 5 | 70 | ||
| 25 | 70 | ||||
| 43 | 81 | ||||
| 60 | 97 | ||||
| 85 | 129 | ||||
| 108 | 91 | ||||
| 135 | 104 | ||||
| 201 | 180 | ||||
| 251 | 198 | ||||
| 317 | 225 | ||||
| 361 | 245 | ||||
| 480 | 290 | ||||
| 625 | 446 | ||||
| 780 | 590 | ||||
| 970 | 812 | ||||
| 1250 | 1222 | ||||
| Auxiliary Contacts 19/20 (Aux #1) 29/30 (Aux #2) 31/32 (Aux #3) 33/34 (Aux #4) |
Type of Control Circuit | Electromagnetic relay | |||
| Number of Contacts | 1 | ||||
| Type of Contacts | programmable N.O./N.C. | ||||
| Type of Current | AC | ||||
| Rated Operational Current | 3 A @ 120V AC, 1.5 A @ 240V AC | ||||
| Conventional Thermal CurrentIth AC/DC | 5 A | ||||
| Make/Break VA | 3600/360 | ||||
| Utilization Category | AC-15/DC | ||||
| PTC Input Ratings | Response Resistance | 3400 W ±150 W | |||
| Reset Resistance | 1600 W ±100 W | ||||
| Short-Circuit Trip Resistance | 25 W ±10 W | ||||
| Max. Voltage at PTC Terminals (RPTC = 4 kW) | < 7.5V | ||||
| Max. Voltage at PTC Terminals (RPTC = open) | 30V | ||||
| Max. No. of Sensors. | 6 | ||||
| Max. Cold Resistance of PTC Sensor Chain | 1500 W | ||||
| Response Time | 800 ms | ||||
| Tach Input | 0…5V DC, 4.5V DC = 100% Speed | ||||
| ∆ Heatsink fans can be powered by either 110/120V AC or 220/240V AC. | |||||
| Environmental | |
| Operating Temperature Range | -5…+50 °C (23…+122 °F) (open) -5…+40 °C (23…+104 °F) (enclosed) |
| Storage and Transportation Temperature Range | -20…+75 °C (-4…167 °F) |
| Altitude | 2000 m (6560 ft) |
| Humidity | 5…95% (non-condensing) |
| Pollution Degree | 2 |
| Mechanical | ||||
| Resistance to Vibration | Operational | All | 1.0 G Peak, 0.15 mm (0.006 in.) displacement | |
| Non-Operational | 5…480 A | 2.5 G Peak, 0.38 mm (0.015 in.) displacement | ||
| 625…1250 A | 1.0 G Peak, 0.15 mm (0.006 in.) displacement | |||
| Resistance to Shock | Operational | 5…85 A | 15 G | |
| 108…480 A | 5.5 G | |||
| 625…1250 A | 4 G | |||
| Non-Operational | 5…85 A | 30 G | ||
| 108…480 A | 25 G | |||
| 625…1250 A | 12 G | |||
| Construction | Power Poles | 5…85 A | Heatsink thyristor modular design | |
| Power Poles | 108…1250 A | Heatsink hockey puck thyristor modular design | ||
| Control Modules | Thermoset and Thermoplastic Moldings | |||
| Metal Parts | Plated Brass, Copper, or Painted Steel | |||
| Terminals | Power Terminals | 5…85 A | Cable size — Line Upper — 2.5…95 mm2 (14…3/0 AWG) Line Lower — 0.8…2.5 mm2 (18…14 AWG) Load Upper — 2.5…50 mm2 (14…1 AWG) Load Lower — 0.8…2.5 mm2 (18…14 AWG) Tightening torque — 14.7 Nm (130 lb.-in.) Wire strip length — 18…20 mm (0.22…0.34 in.) |
|
| 108…135 A | One M10 x 1.5 diameter hole per power pole | |||
| 201…251 A | Two M10 x 1.5 diameter holes per power pole | |||
| 317…480 A | Two M12 x 1.75 diameter holes per power pole | |||
| 625…1250 A | Two 13.5 mm (0.53 in.) diameter holes per power pole | |||
| Power Terminal Markings | NEMA, CENELEC EN50 012 | |||
| Control Terminals | M3 screw clamp | Clamping yoke connection | ||
| Other | ||||
| EMC Emission Levels | Conducted Radio Frequency Emissions Radiated Emissions |
Class A Class A |
||
| EMC Immunity Levels | Electrostatic Discharge Radio Frequency Electromagnetic Field Fast Transient Surge Transient |
8 kV Air Discharge Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 |
||
| Overload Characteristics | Current Range [A] | Line | Delta | |
| 108 | 27…108 | 47…187 | ||
| 135 | 34…135 | 59…234 | ||
| 201 | 67…201 | 116…348 | ||
| 251 | 84…251 | 145…435 | ||
| 317 | 106…317 | 183…549 | ||
| 361 | 120…361 | 208…625 | ||
| 480 | 160…480 | 277…831 | ||
| 625 | 208…625 | 283…850 | ||
| 780 | 260…780 | 300…900 | ||
| 970 | 323…970 | 400…1200 | ||
| 1250 | 416…1250 | 533…1600 | ||
| Trip Classes Trip Current Rating Number of Poles |
10, 15, 20, and 30 117% of Motor FLC 3 |
|||
| Certifications | Open-Type Controllers | CE Marked Per Low Voltage Directive 73/23/EEC, 93/68/EEC UL Listed (File No. E96956) |
||