SMC™ Dialog Plus Smart Motor Controller

Product Overview


Click to enlarge - 150-7_28-1 Click to enlarge - 150-7_28-2
Click to enlarge - 150-7_28-3 Click to enlarge - 150-7_28-6
Click to enlarge - 150-7_28-5

Bulletin 150 — SMC™ Dialog Plus Smart Motor Controller

The SMC Dialog Plus™ controller provides microprocessor controlled starting for standard three-phase squirrel-cage induction motors. Four standard modes of operation are available within a single controller:


Options include:


Features include:


The SMC Dialog Plus™ controller is available for motors rated 1…1000 A; 200…480V AC, or 200…600V AC, 50 and 60 Hz. In addition to motors, the SMC Dialog Plus™ controller can be used to control resistive loads.

Standards Compliance and Certifications

Standards Compliance

UL 508
CSA C22.2 No.14
EN/IEC 60947-1
EN/IEC 60947-4-2


Certifications

cULus Listed (Open Type) (File No. E96956, Guides NMFT, NMFT7)
CSA Certified (File No. LR 1234)
CE Marked (Open Type) per EMC and Low Voltage Directive
CCC Certified


Modes of Operation

Modes of Operation

The SMC Dialog Plus controller provides the following modes of operation: Soft Start with selectable Kickstart, Current Limit Start, Dual Ramp Start, and Full Voltage Start.

Soft Start

This method has the most general application. The motor is raised to an initial torque value which is programmable from 0…90% of locked rotor torque. The motor voltage is gradually increased during the acceleration ramp time, which can be programmed from 0…30 seconds.

Soft Start with Selectable Kickstart

A kickstart, or boost, at the beginning of the voltage ramp is intended to provide a current pulse of 550% of full load current. The kickstart time is adjustable from 0.0…2.0 seconds. This allows the motor to develop additional torque at start for loads which may need a boost to get started.

Current Limit Start

This starting mode is used when it is necessary to limit the maximum starting current. The current limit can be programmed for 50…600% of full load current.

Dual Ramp Start

This starting mode is useful on applications that have varying loads and therefore varying starting torque requirements. The Dual Ramp Start offers the user the option to select between two separate Soft Start profiles with separately adjustable ramp times and initial torque settings.

The acceleration ramp times can be programmed from 0…30 seconds. The initial torque values can be programmed from 0…90% of locked rotor torque. Note: Dual Ramp is only available with the standard controller.

Full Voltage Start

This mode is used for applications requiring across-the-line starting. The ramp time is less than 1/4 second.

Click to enlarge - 150-7_29-1


Click to enlarge - 150-7_29-2


Click to enlarge - 150-7_29-3


Click to enlarge - 150-7_29-4


Click to enlarge - 150-7_29-5


Description of Starting and Stopping Options

The following options are available in the SMC Dialog Plus controller. Only one option may be added to the standard unit.

Soft Stop¬ 

This option can be used on applications that require an extended coast to rest. It is designed for frictional loads that tend to stop suddenly when voltage is removed from the motor.

The voltage ramp down time can be programmed from 0…60 seconds. The load will stop when the motor voltage drops to a point where the load torque is greater than the motor torque.

Pump Control¬ 

This option is used to reduce surges during the starting and stopping of a centrifugal pump by smoothly accelerating and decelerating the motor. The microprocessor analyzes the motor variables and generates commands which control the motor and reduce the possibility of surges occurring in the system.

The starting time is programmable from 0…30 seconds and the stopping time is programmable from 0…120 seconds.

Preset Slow Speed

This option can be used on applications that require a slow speed (for example, moving material into position).

The preset slow speed can be programmed for either 7% of base speed (low) or 15% of base speed (high) in the forward direction. It can also be set for 10% of base speed (low) or 20% of base speed (high) in the reverse direction without a reversing contactor.

SMB Smart Motor Braking¬ 

This option provides motor braking for applications that require the motor to stop faster than a coast to rest. Braking control, with automatic zero speed shut off, is fully integrated into the compact design of the SMC Dialog Plus controller. This design facilitates a clean, straightforward installation and eliminates the requirement for additional hardware such as braking contactors, resistors, timers, and speed sensors.
The microprocessor based braking system applies braking current to a standard squirrel cage induction motor. The strength of the braking current is programmable from 150…400% of full load current.


Accu-Stop¬ 

This option is used in applications requiring controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7 or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed.
Braking current is programmable from 0…400% of full load current. Slow Speed Current is programmable from 0…450% of full load current. Slow speed can be programmed for either 7% (low) or 15% (high).


Accu-Stop with Slow Speed at Start¬ 

The Accu-Stop option can also allow the motor to operate at a preset slow speed when Slow Speed Start is selected. This minimizes the jogging required to position a load. The start command will ramp the voltage from the preset slow speed to full speed. The operation of Accu-Stop is the same as explained previously.

Slow Speed with Braking¬ 

Slow Speed with Braking is used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop.

Slow speed adjustments are 7% (low) or 15% (high) of rated speed. Slow speed acceleration current is adjustable from 0…450%. Slow speed running current is adjustable from 0…450% of full load current. Braking current is adjustable from 0…400%.

¬ Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirements.


The following options are available in the SMC Dialog Plus controller. Only one option may be added to the standard unit.

Click to enlarge - 150-7_30-1


Click to enlarge - 150-7_30-2


Click to enlarge - 150-7_30-3


Click to enlarge - 150-7_30-4


Click to enlarge - 150-7_30-5


Click to enlarge - 150-7_30-6


Click to enlarge - 150-7_30-7


Description of Features

Electronic Motor Overload Protection

The SMC Dialog Plus controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm.
When coordinated with the proper short circuit protection, overload protection is intended to protect the motor, motor controller, and power wiring against overheating caused by excessive overcurrent. The SMC Dialog Plus controller meets applicable requirements as a motor overload protective device.
The controller’s overload protection is programmable, providing the user with flexibility. The overload trip class can be selected for class 10, 15, 20, or 30 protection. The trip current is programmed by entering the motor full-load current rating.
Thermal memory is included to accurately model motor operating temperature. Ambient insensitivity is inherent in the electronic design of the overload.
Note: The current sensing capability of the SMC Dialog Plus controller is disabled during bypass operation. The Bulletin 825 Converter Module and 150-NFS fanning strip are required for providing current feedback in these applications. Note: To achieve calibration, 70% motor load or greater is required at the motor shaft for 2 s. Calibration is required when a Bulletin 825 Converter Module is not used.


Stall Protection and Jam Detection

Motors can experience locked rotor currents and develop high torque levels in the event of a stall or a jam. These conditions can result in winding insulation breakdown or mechanical damage to the connected load. The SMC Dialog Plus controller provides both stall protection and jam detection for enhanced motor and system protection. Stall protection allows the user to program a maximum stall protection delay time from 0…10 s. The stall protection delay time is in addition to the programmed start time and begins only after the start time has timed out. If the controller senses that the motor is stalled, it will shut down after the delay period has expired.
Jam detection allows the user to determine the motor jam detection level as a percentage of the motor’s full load current rating. To prevent nuisance tripping, a jam detection delay time, from 0.0…10.0 s, can be programmed. This allows the user to select the time delay required before the SMC Dialog Plus controller will trip on a motor jam condition. The motor current must remain above the jam detection level during the delay time. Jam detection is active only after the motor has reached full speed.


Energy Saver

This is a standard feature with the SMC Dialog Plus controller. It is used to save energy on applications where the motor is lightly loaded or unloaded for long periods of time. The Energy Saver is a built-in feature of the controller. It does not require additional panel space or external wiring. It also does not require a complicated setup procedure.

Phase Rebalance

The SMC Dialog Plus controller incorporates, as standard, a dynamic Phase Rebalance feature. The controller compensates for voltage unbalance by automatically adjusting the voltage output to balance the 3-phase currents drawn by the motor. When phase rebalance is achieved, motor life may be extended and production can continue without interruption. Phase Rebalance is a built-in feature of the controller and does not require a complicated setup procedure.
Note: Phase Rebalance requires the use of the Bulletin 825 Converter Module and the Cat. No. 150-NFS fanning strip.
Note: The performance of the Phase Rebalance feature is dependent on the motor’s loading and characteristics. Severe imbalances cannot be corrected.


Underload Protection

Utilizing the underload protection of the SMC Dialog Plus controller, motor operation can be halted if a drop in current is sensed.
The SMC Dialog Plus controller provides an adjustable underload trip setting from 0…99% of the programmed motor full load current rating with an adjustable trip delay time of 0…99 s.


Undervoltage Protection

The SMC Dialog Plus controller’s undervoltage protection will halt motor operation if a drop in the incoming line voltage is detected.
The undervoltage trip level is adjustable as a percentage of the programmed line voltage, from 0…99%. To eliminate nuisance trips, a programmable undervoltage trip delay time of 0…99 s can also be programmed. The line voltage must remain below the undervoltage trip level during the programmed delay time.


Overvoltage Protection

If a rise in the incoming line voltage is detected, the SMC Dialog Plus controller’s overvoltage protection will halt motor operation.
The overvoltage trip level is adjustable as a percentage of the programmed line voltage, from 0…99%. To eliminate nuisance trips, a programmable overvoltage trip delay time of 0…99 s can also be programmed. The line voltage must remain above the overvoltage trip level during the programmed delay time.


Voltage Unbalance Protection

Voltage unbalance is detected by monitoring the 3-phase supply voltage magnitudes in conjunction with the rotational relationship of the three phases. The controller will halt motor operation when the calculated voltage unbalance reaches the user-programmed trip level.
The voltage unbalance trip level is programmable from 0…25% unbalance.


Excessive Starts Per Hour

The SMC Dialog Plus controller allows the user to program the allowed number of starts per hour (up to 99). This helps eliminate motor stress caused by repeated starting during a short time period.

Metering

Power monitoring parameters include:


Note: The motor thermal capacity usage allows the user to monitor the amount of overload thermal capacity usage before the SMC Dialog Plus controller’s built-in electronic overload trips.
Note: In bypass configurations, the current sensing and power factor measurement capability of the SMC Dialog Plus controller is disabled. Three-phase current measurement, kW, kWH, and motor thermal capacity usage can still be maintained with the use of the Bulletin 825 Converter Module.
Note: The usage of an SMC Controller on a generator and line power requires the use of a Bulletin 825 Converter Module.


Built-in SCANport™ Communication

A serial interface port is provided as standard, which allows connection to a Bulletin 1201 Human Interface Module or a variety of Bulletin 1203 Communication Modules. This includes Allen-Bradley Remote I/O, DeviceNet network and RS-232/422/485-DF1.

LCD Display

The SMC Dialog Plus controller’s two-line 16-character backlit LCD display provides parameter identification using clear, informative text. Controller set up can be performed quickly and easily without the use of a reference manual. Parameters are arranged in an organized four-level menu structure for ease of programming and fast access to parameters.

Keypad Programming

Programming of parameters is accomplished through a five-button keypad on the front of the SMC Dialog Plus controller. The five buttons include up and down arrows, an Enter button, a Select button, and an Escape button. The user needs only to enter the correct sequence of keystrokes for programming the SMC Dialog Plus controller.

Auxiliary Contacts

Three hard contacts are furnished as standard with the SMC Dialog Plus controller. The first two contacts are programmable for Normal/Up-to-speed. The third is programmable for Normal/Fault.

Cat. No. Explanation

Open and Non-Combination

150 B180    N    B    D    A 8L
a    b    c    d    e    f    g

a
Bulletin Number
Code Description
150 Solid-State Controller
150B Solid-State Controller and Isolation Contactor (enclosed only)

b
Controller Ratings
Code Description
B24 24 A, 1…15 Hp @ 460V AC
B35 35 A, 1…25 Hp @ 460V AC
B54 54 A, 1…40 Hp @ 460V AC
B97 97 A, 5…75 Hp @ 460V AC
B135 135 A, 5…100 Hp @ 460V AC
B180 180 A, 5…150 Hp @ 460V AC
B240 240 A, 5…200 Hp @ 460V AC
B360 360 A, 5…300 Hp @ 460V AC
B500 500 A, 4…400 Hp @ 460V AC
B650 650 A, 5…500 Hp @ 460V AC
B720 720 A, 5…600 Hp @ 460V AC
B850 850 A, 10…700 Hp @ 460V AC
B1000 1000 A, 10…800 Hp @ 460V AC

c
Enclosure Type
Code Description
N Open
A NEMA Type 1 (IP30)
F NEMA Type 4 (IP65)
J NEMA Type 12 (IP54)
H NEMA Type 3R

d
Input Line Voltage
Open Type
Code Description
B 200…460V AC, 3-phase, 50 and 60 Hz
C 200…575V AC, 3-phase, 50 and 60 Hz
Non-Combination Enclosed Only
H 200…208V AC, 3-phase, 50 and 60 Hz
A 230V AC, 3-phase, 50 and 60 Hz
B 200…460V AC, 3-phase, 50 and 60 Hz
C 200…575V AC, 3-phase, 50 and 60 Hz

e
Control Voltage
Code Description
D 100…240V AC
R 24V AC/DC

f
Control Options (see Enclosed Options for a full listing.)
Note: Select Only One
Code Description
Blank Standard
B Pump Control
C Preset Slow Speed
D SMB Smart Motor Braking
E Accu-Stop
F Slow Speed with Braking

g
Options
Code Description
8L Line-Mounted Protective Module
8M Load-Mounted Protective Module
8B Line- and Load-Mounted Protective Modules

Combination

152H B240    A    BD    B 52 8B
a    b    c    d    e    f    g

a
Bulletin Number
Code Description
152B Solid-State Controller with Fusible Disconnect and Isolating Contactor
152H Solid-State Controller with
Fusible Disconnect
153B Solid-State Controller with Circuit Breaker and Isolating Contactor
153H Solid-State Controller with Circuit Breaker

b
Controller Ratings
Code Description
B24 24 A, 1…15 Hp @ 460V AC
B35 35 A, 1…25 Hp @ 460V AC
B54 54 A, 1…40 Hp @ 460V AC
B97 97 A, 5…75 Hp @ 460V AC
B135 135 A, 5…100 Hp @ 460V AC
B180 180 A, 5…150 Hp @ 460V AC
B240 240 A, 5…200 Hp @ 460V AC
B360 360 A, 5…300 Hp @ 460V AC
B500 500 A, 4…400 Hp @ 460V AC
B650 650 A, 5…500 Hp @ 460V AC
B720 720 A, 5…600 Hp @ 460V AC
B850 850 A, 10…700 Hp @ 460V AC
B1000 1000 A, 10…800 Hp @ 460V AC

c
Enclosure Type
Code Description
A NEMA Type 1 (IP30)
J NEMA Type 12 (IP54)
F NEMA Type 4 (IP65)
H NEMA 3R

d
Line Voltage
Code Description
HD 200…208V AC, 3-phase, 50 and 60 Hz
AD 230V AC, 3-phase, 50 and 60 Hz
BD 400…460V AC, 3-phase, 50 and 60 Hz
CD 500…575V AC, 3-phase, 50 and 60 Hz

e
Control Options
Code Description
Blank Standard
B Pump Control
C Preset Slow Speed
D SMB Smart Motor Braking
E Accu-Stop
F Slow Speed with Braking

f
Horsepower
Code Hp Rating Code Hp Rating
39 5 52 150
40 7-1/2 54 200
41 10 56 250
42 15 57 300
43 20 58 350
44 25 59 400
45 30 60 450
46 40 61 500
47 50 62 600
48 60 63 700
49 75 65 800
50 100 67 1000
51 125

g
Options (see Enclosed Options for a full listing.)
Code Description
8L Line-Mounted Protective Module
8M Load-Mounted Protective Module
8B Line- and Load-Mounted Protective Modules

Product Selection

Open Type Controllers

Build a Catalog Number


Up to 460V AC

Current¬ 
Rating
(A)
kWT  Hp‡  100…240V AC
50/60 Hz Control
Cat. No.
24V AC/DC Control
Cat. No.
230V AC
50 Hz
400V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
24 5.5 11 1…5 1…7.5 1…15 150-B24NBD 150-B24NBR
35 10 18.5 1…10 1…10 1…25 150-B35NBD 150-B35NBR
54 15 22 1…15 1…20 1…40 150-B54NBD 150-B54NBR
97 25 45 5…30 5…30 5…75 150-B97NBD §  150-B97NBR
135 37 75 5…40 5…50 5…100 150-B135NBD §  150-B135NBR
180 51 90 5…60 5…60 5…150 150-B180NBD §  150-B180NBR
240 75 132 5…75 5…75 5…200 150-B240NBD §  150-B240NBR
360 110 200 5…125 5…150 5…300 150-B360NBD §  150-B360NBR
500 150 257 5…150 5…200 5…400 150-B500NBD §  150-B500NBR
650 200 355 5…200 5…250 5…500 150-B650NBD §  150-B650NBR
720 220 400 5…250 5…300 5…600 150-B720NBD §  150-B720NBR
850 257 475 10…300 10…350 10…700 150-B850NBD §  150-B850NBR
1000 315 530 10…350 10…400 10…800 150-B1000NBD §  150-B1000NBR
  
¬ Controllers rated 97…360 A are not equipped with line and load terminal lugs. See Accessories for terminal lug kits.
T The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices rated 850 A and greater.
‡ Hp ratings at motor terminal voltages for 208, 480, and 600 line volts, respectively.
§ 120V AC control is required for heatsink fan operation.

Up to 575V AC

Current¬ 
Rating
(A)
kWT  Hp‡  100…240V AC
50/60 Hz Control
Cat. No.
24V AC/DC Control
Cat. No.
230V AC
50 Hz
400V AC
50 Hz
500V AC
50 Hz
200V AC
60 Hz
230V AC
60 Hz
460V AC
60 Hz
575V AC
60 Hz
24 5.5 11 15 1…5 1…7.5 1…15 1…20 150-B24NCD 150-B24NCR
35 10 18.5 22 1…10 1…10 1…25 1…30 150-B35NCD 150-B35NCR
54 15 22 37 1…15 1…20 1…40 1…50 150-B54NCD 150-B54NCR
97 25 45 63 5…30 5…30 5…75 5…75 150-B97NCD §  150-B97NCR
135 37 75 90 5…40 5…50 5…100 5…125 150-B135NCD §  150-B135NCR
180 51 90 132 5…60 5…60 5…150 5…150 150-B180NCD §  150-B180NCR
240 75 132 160 5…75 5…75 5…200 5…250 150-B240NCD §  150-B240NCR
360 110 200 250 5…125 5…150 5…300 5…350 150-B360NCD §  150-B360NCR
500 150 257 355 5…150 5…200 5…400 5…500 150-B500NCD §  150-B500NCR
650 200 355 475 5…200 5…250 5…500 5…600 150-B650NCD §  150-B650NCR
720 220 400 500 5…250 5…300 5…600 5…700 150-B720NCD §  150-B720NCR
850 257 475 600 10…300 10…350 10…700 10…800 150-B850NCD §  150-B850NCR
1000 315 530 710 10…350 10…400 10…800 10…1000 150-B1000NCD §  150-B1000NCR
  
¬ Controllers rated 97…360 A are not equipped with line and load terminal lugs. See Accessories for terminal lug kits.
T The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices rated 850 A and greater.
‡ Hp ratings at motor terminal voltages for 208, 480, and 600 line volts, respectively.
§ 120V AC control is required for heatsink fan operation.

Non-Combination Controllers — IP30 (Type 1) Vented Enclosed, IP65 (Type 4) Enclosed, and IP54 (Type 12) Enclosed

Build a Catalog Number


Require a separate 100…240V, 50/60 Hz single-phase control source. Line and load terminations are provided as standard. The IP65 (Type 4) Enclosed Non-Combination, and IP54 (Type 12) Enclosed Non-Combination 97…1000 A controllers include a bypass contactor and a Bulletin 825 converter module. Enclosures other than those listed are available; consult your local Rockwell Automation sales office or Allen-Bradley distributor.

208V AC

Current Rating Hp IP30 (Type 1) Vented Enclosed
Non-Combination Controllers
IP65 (Type 4) Enclosed
Non-Combination Controllers
IP54 (Type 12) Enclosed
Non-Combination Controllers
200V AC 60 Hz Cat. No. Cat. No. Cat. No.
24 1…5 §  150-B24AHD Ø  150-B24FHD Ø  150-B24JHD
35 1…10 §  150-B35AHD Ø  150-B35FHD Ø  150-B35JHD
54 1…15 §  150-B54AHD Ø  150-B54FHD Ø  150-B54JHD
97 5…30 150-B97AHD 150-B97FHD 150-B97JHD
135 5…40 150-B135AHD 150-B135FHD 150-B135JHD
180 5…60 150-B180AHD 150-B180FHD 150-B180JHD
240 5…75 150-B240AHD 150-B240FHD 150-B240JHD
360 5…125 150-B360AHD 150-B360FHD 150-B360JHD
500 5…150 150-B500AHD 150-B500FHD 150-B500JHD
650 5…200 150-B650AHD 150-B650FHD 150-B650JHD
720 5…250 150-B720AHD 150-B720FHD 150-B720JHD
850 10…300 150-B850AHD 150-B850FHD 150-B850JHD
1000 10…350 150-B1000AHD 150-B1000FHD 150-B1000JHD
  
§ Includes internal circulating fan rather than enclosure ventilation.
Ø Includes an internal circulating fan instead of a bypass contactor.

230V AC

Current Rating kWT  Hp IP30 (Type 1) Vented Enclosed
Non-Combination Controllers
IP65 (Type 4) Enclosed
Non-Combination Controllers
IP54 (Type 12) Enclosed
Non-Combination Controllers
230V AC 50 Hz 230V AC 60 Hz Cat. No. Cat. No. Cat. No.
24 5.5 1…5 §  150-B24AAD Ø  150-B24FAD Ø  150-B24JAD
35 10 1…10 §  150-B35AAD Ø  150-B35FAD Ø  150-B35JAD
54 15 1…15 §  150-B54AAD Ø  150-B54FAD Ø  150-B54JAD
97 25 5…30 150-B97AAD 150-B97FAD 150-B97JAD
135 37 5…40 150-B135AAD 150-B135FAD 150-B135JAD
180 51 5…60 150-B180AAD 150-B180FAD 150-B180JAD
240 75 5…75 150-B240AAD 150-B240FAD 150-B240JAD
360 110 5…125 150-B360AAD 150-B360FAD 150-B360JAD
500 150 5…150 150-B500AAD 150-B500FAD 150-B500JAD
650 200 5…200 150-B650AAD 150-B650FAD 150-B650JAD
720 220 5…250 150-B720AAD 150-B720FAD 150-B720JAD
850 257 10…300 150-B850AAD 150-B850FAD 150-B850JAD
1000 315 10…350 150-B1000AAD 150-B1000FAD 150-B1000JAD
  
T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater.
§ Includes internal circulating fan rather than enclosure ventilation.
Ø Includes an internal circulating fan instead of a bypass contactor.

460V AC

Current Rating kWT  Hp IP30 (Type 1) Vented Enclosed
Non-Combination Controllers
IP65 (Type 4) Enclosed
Non-Combination Controllers
IP54 (Type 12) Enclosed
Non-Combination Controllers
400V AC 50 Hz 460V AC 60 Hz Cat. No. Cat. No. Cat. No.
24 11 1…15 §  150-B24ABD Ø  150-B24FBD Ø  150-B24JBD
35 18.5 1…25 §  150-B35ABD Ø  150-B35FBD Ø  150-B35JBD
54 22 1…40 §  150-B54ABD Ø  150-B54FBD Ø  150-B54JBD
97 45 5…75 150-B97ABD 150-B97FBD 150-B97JBD
135 75 5…100 150-B135ABD 150-B135FBD 150-B135JBD
180 90 5…150 150-B180ABD 150-B180FBD 150-B180JBD
240 132 5…200 150-B240ABD 150-B240FBD 150-B240JBD
360 200 5…300 150-B360ABD 150-B360FBD 150-B360JBD
500 257 5…400 150-B500ABD 150-B500FBD 150-B500JBD
650 355 5…500 150-B650ABD 150-B650FBD 150-B650JBD
720 400 5…600 150-B720ABD 150-B720FBD 150-B720JBD
850 475 10…700 150-B850ABD 150-B850FBD 150-B850JBD
1000 530 10…800 150-B1000ABD 150-B1000FBD 150-B1000JBD
  
T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater.
§ Includes internal circulating fan rather than enclosure ventilation.
Ø Includes an internal circulating fan instead of a bypass contactor.

575V AC

Current Rating
(A)
kWT  Hp IP30 (Type 1) Vented Enclosed
Non-Combination Controllers
IP65 (Type 4) Enclosed
Non-Combination Controllers
IP54 (Type 12) Enclosed
Non-Combination Controllers
500V AC 50 Hz 575V AC 60 Hz Cat. No. Cat. No. Cat. No.
24 15 1…20 §  150-B24ACD Ø  150-B24FCD Ø  150-B24JCD
35 22 1…30 §  150-B35ACD Ø  150-B35FCD Ø  150-B35JCD
54 37 1…50 §  150-B54ACD Ø  150-B54FCD Ø  150-B54JCD
97 63 5…75 150-B97ACD 150-B97FCD 150-B97JCD
135 90 5…125 150-B135ACD 150-B135FCD 150-B135JCD
180 132 5…150 150-B180ACD 150-B180FCD 150-B180JCD
240 160 5…250 150-B240ACD 150-B240FCD 150-B240JCD
360 250 5…350 150-B360ACD 150-B360FCD 150-B360JCD
500 355 5…500 150-B500ACD 150-B500FCD 150-B500JCD
650 475 5…600 150-B650ACD 150-B650FCD 150-B650JCD
720 500 5…700 150-B720ACD 150-B720FCD 150-B720JCD
850 600 10…800 150-B850ACD 150-B850FCD 150-B850JCD
1000 710 10…1000 150-B1000ACD 150-B1000FCD 150-B1000JCD
  
T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater.
§ Includes internal circulating fan rather than enclosure ventilation.
Ø Includes an internal circulating fan instead of a bypass contactor.

Combination Controllers — IP30 (Type 1) Vented Enclosed with Fusible Disconnect, IP54 (Type 12) Enclosed with Fusible Disconnect, IP30 (Type 1) Vented Enclosed with Circuit Breaker, IP54 (Type 12) Enclosed with Circuit Breaker

Build a Catalog Number


Includes a 120V control transformer and line and load terminations. The IP54 (Type 12) Enclosed Combination with Fusible Disconnect and IP54 (Type 12) Enclosed Combination with Circuit Breaker 97…1000 A controllers include a bypass contactor and a Bulletin 825 converter module. Enclosures other than those listed are available; consult your local Rockwell Automation sales office or Allen-Bradley distributor.
All Bulletin 153 numbers are supplied with thermal magnetic circuit breakers.


208V AC, 60 Hz

Hp
Range
Controller Current
Rating (A)z 
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Fusible
Disconnect
IP54 (Type 12) Enclosed
Combination Controllers
with Fusible Disconnect
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Circuit
Breaker
IP54 (Type 12) Enclosed
Combination Controllers
with Circuit Breaker
Cat. No. Cat. No. Cat. No. Cat. No.
1…5 24 §  152H-B24AHD-39 ª  152H-B24JHD-39 §  153H-B24AHD-39 ª  153H-B24JHD-39
7-1/2 35 §  152H-B35AHD-40 ª  152H-B35JHD-40 §  153H-B35AHD-40 ª  153H-B35JHD-40
10 35 §  152H-B35AHD-41 ª  152H-B35JHD-41 §  153H-B35AHD-41 ª  153H-B35JHD-41
15 54 §  152H-B54AHD-42 ª  152H-B54JHD-42 §  153H-B54AHD-42 ª  153H-B54JHD-42
20 97 152H-B97AHD-43 152H-B97JHD-43 153H-B97AHD-43 153H-B97JHD-43
25 97 152H-B97AHD-44 152H-B97JHD-44 153H-B97AHD-44 153H-B97JHD-44
30 97 152H-B97AHD-45 152H-B97JHD-45 153H-B97AHD-45 153H-B97JHD-45
40 135 152H-B135AHD-46 152H-B135JHD-46 153H-B135AHD-46 153H-B135JHD-46
50 180 152H-B180AHD-47 152H-B180JHD-47 153H-B180AHD-47 153H-B180JHD-47
60 180 152H-B180AHD-48 152H-B180JHD-48 153H-B180AHD-48 153H-B180JHD-48
75 240 152H-B240AHD-49 152H-B240JHD-49 153H-B240AHD-49 153H-B240JHD-49
100 360 152H-B360AHD-50 152H-B360JHD-50 153H-B360AHD-50 153H-B360JHD-50
125 360 152H-B360AHD-51 152H-B360JHD-51 153H-B360AHD-51 153H-B360JHD-51
150 500 152H-B500AHD-52 152H-B500JHD-52 153H-B500AHD-52 153H-B500JHD-52
200 650 152H-B650AHD-54 152H-B650JHD-54 153H-B650AHD-54 153H-B650JHD-54
250 720 152H-B720AHD-56 152H-B720JHD-56 153H-B720AHD-56 153H-B720JHD-56
300 850 152H-B850AHD-57 152H-B850JHD-57 153H-B850AHD-57 153H-B850JHD-57
350 1000 152H-B1000AHD-58 152H-B1000JHD-58 153H-B1000AHD-58 153H-B1000JHD-58
  
z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
§ Includes internal circulating fan rather than enclosure ventilation.
ª Supplied without bypass contactor or converter module.

230V AC, 60 Hz

Hp
Range
Controller
Current
Rating (A)z 
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Fusible
Disconnect
IP54 (Type 12) Enclosed
Combination Controllers
with Fusible Disconnect
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Circuit
Breaker
IP54 (Type 12) Enclosed
Combination Controllers
with Circuit Breaker
Cat. No. Cat. No. Cat. No. Cat. No.
1…7-1/2 24 §  152H-B24AAD-40 ª  152H-B24JAD-40 §  153H-B24AAD-40 ª  153H-B24JAD-40
10 35 §  152H-B35AAD-41 ª  152H-B35JAD-41 §  153H-B35AAD-41 ª  153H-B35JAD-41
15 54 §  152H-B54AAD-42 ª  152H-B54JAD-42 §  153H-B54AAD-42 ª  153H-B54JAD-42
20 54 §  152H-B54AAD-43 ª  152H-B54JAD-43 §  153H-B54AAD-43 ª  153H-B54JAD-43
25 97 152H-B97AAD-44 152H-B97JAD-44 153H-B97AAD-44 153H-B97JAD-44
30 97 152H-B97AAD-45 152H-B97JAD-45 153H-B97AAD-45 153H-B97JAD-45
40 135 152H-B135AAD-46 152H-B135JAD-46 153H-B135AAD-46 153H-B135JAD-46
50 135 152H-B135AAD-47 152H-B135JAD-47 153H-B135AAD-47 153H-B135JAD-47
60 180 152H-B180AAD-48 152H-B180JAD-48 153H-B180AAD-48 153H-B180JAD-48
75 240 152H-B240AAD-49 152H-B240JAD-49 153H-B240AAD-49 153H-B240JAD-49
100 360 152H-B360AAD-50 152H-B360JAD-50 153H-B360AAD-50 153H-B360JAD-50
125 360 152H-B360AAD-51 152H-B360JAD-51 153H-B360AAD-51 153H-B360JAD-51
150 360 152H-B360AAD-52 152H-B360JAD-52 153H-B360AAD-52 153H-B360JAD-52
200 500 152H-B500AAD-54 152H-B500JAD-54 153H-B500AAD-54 153H-B500JAD-54
250 650 152H-B650AAD-56 152H-B650JAD-56 153H-B650AAD-56 153H-B650JAD-56
300 720 152H-B720AAD-57 152H-B720JAD-57 153H-B720AAD-57 153H-B720JAD-57
350 850 152H-B850AAD-58 152H-B850JAD-58 153H-B850AAD-58 153H-B850JAD-58
400 1000 152H-B1000AAD-59 152H-B1000JAD-59 153H-B1000AAD-59 153H-B1000JAD-59
  
z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
§ Includes internal circulating fan rather than enclosure ventilation.
ª Supplied without bypass contactor or converter module.

460V AC, 60 Hz

Hp
Range
Controller Current
Rating (A)z 
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Fusible
Disconnect
IP54 (Type 12) Enclosed
Combination Controllers with
Fusible Disconnect
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Circuit
Breaker
IP54 (Type 12) Enclosed
Combination Controllers
with Circuit Breaker
Cat. No. Cat. No. Cat. No. Cat. No.
1…15 24 §  152H-B24ABD-42 ª  152H-B24JBD-42 §  153H-B24ABD-42 ª  153H-B24JBD-42
20 35 §  152H-B35ABD-43 ª  152H-B35JBD-43 §  153H-B35ABD-43 ª  153H-B35JBD-43
25 35 §  152H-B35ABD-44 ª  152H-B35JBD-44 §  153H-B35ABD-44 ª  153H-B35JBD-44
30 54 §  152H-B54ABD-45 ª  152H-B54JBD-45 §  153H-B54ABD-45 ª  153H-B54JBD-45
40 54 §  152H-B54ABD-46 ª  152H-B54JBD-46 §  153H-B54ABD-46 ª  153H-B54JBD-46
50 97 152H-B97ABD-47 152H-B97JBD-47 153H-B97ABD-47 153H-B97JBD-47
60 97 152H-B97ABD-48 152H-B97JBD-48 153H-B97ABD-48 153H-B97JBD-48
75 97 152H-B97ABD-49 152H-B97JBD-49 153H-B97ABD-49 153H-B97JBD-49
100 135 152H-B135ABD-50 152H-B135JBD-50 153H-B135ABD-50 153H-B135JBD-50
125 180 152H-B180ABD-51 152H-B180JBD-51 153H-B180ABD-51 153H-B180JBD-51
150 180 152H-B180ABD-52 152H-B180JBD-52 153H-B180ABD-52 153H-B180JBD-52
200 240 152H-B240ABD-54 152H-B240JBD-54 153H-B240ABD-54 153H-B240JBD-54
250 360 152H-B360ABD-56 152H-B360JBD-56 153H-B360ABD-56 153H-B360JBD-56
300 360 152H-B360ABD-57 152H-B360JBD-57 153H-B360ABD-57 153H-B360JBD-57
350 500 152H-B500ABD-58 152H-B500JBD-58 153H-B500ABD-58 153H-B500JBD-58
400 500 152H-B500ABD-59 152H-B500JBD-59 153H-B500ABD-59 153H-B500JBD-59
450 650 152H-B650ABD-60 152H-B650JBD-60 153H-B650ABD-60 153H-B650JBD-60
500 650 152H-B650ABD-61 152H-B650JBD-61 153H-B650ABD-61 153H-B650JBD-61
600 720 152H-B720ABD-62 152H-B720JBD-62 153H-B720ABD-62 153H-B720JBD-62
700 850 152H-B850ABD-63 152H-B850JBD-63 153H-B850ABD-63 153H-B850JBD-63
800 1000 152H-B1000ABD-65 152H-B1000JBD-65 153H-B1000ABD-65 153H-B1000JBD-65
  
z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Allen-Bradley distributor.
§ Includes internal circulating fan rather than enclosure ventilation.
ª Supplied without bypass contactor or converter module.

575V AC, 60 Hz

Hp
Range
Controller Current
Rating (A)z 
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Fusible
Disconnect
IP54 (Type 12) Enclosed
Combination Controllers
with Fusible Disconnect
IP30 (Type 1) Vented
Enclosed Combination
Controllers with Circuit
Breaker
IP54 (Type 12) Enclosed
Combination Controllers with
Circuit Breaker
Cat. No. Cat. No. Cat. No. Cat. No.
1…20 24 §  152H-B24ACD-43 ª  152H-B24JCD-43 §  153H-B24ACD-43 ª  153H-B24JCD-43
25 35 §  152H-B35ACD-44 ª  152H-B35JCD-44 §  153H-B35ACD-44 ª  153H-B35JCD-44
30 35 §  152H-B35ACD-45 ª  152H-B35JCD-45 §  153H-B35ACD-45 ª  153H-B35JCD-45
40 54 §  152H-B54ACD-46 ª  152H-B54JCD-46 §  153H-B54ACD-46 ª  153H-B54JCD-46
50 54 §  152H-B54ACD-47 ª  152H-B54JCD-47 153H-B54ACD-47 ª  153H-B54JCD-47
60 97 152H-B97ACD-48 152H-B97JCD-48 153H-B97ACD-48 153H-B97JCD-48
75 97 152H-B97ACD-49 152H-B97JCD-49 153H-B97ACD-49 153H-B97JCD-49
100 135 152H-B135ACD-50 152H-B135JCD-50 153H-B135ACD-50 153H-B135JCD-50
125 135 152H-B135ACD-51 152H-B135JCD-51 153H-B135ACD-51 153H-B135JCD-51
150 180 152H-B180ACD-52 152H-B180JCD-52 153H-B180ACD-52 153H-B180JCD-52
200 240 152H-B240ACD-54 152H-B240JCD-54 153H-B240ACD-54 153H-B240JCD-54
250 240 152H-B240ACD-56 152H-B240JCD-56 153H-B240ACD-56 153H-B240JCD-56
300 360 152H-B360ACD-57 152H-B360JCD-57 153H-B360ACD-57 153H-B360JCD-57
350 360 152H-B360ACD-58 152H-B360JCD-58 153H-B360ACD-58 153H-B360JCD-58
400 500 152H-B500ACD-59 152H-B500JCD-59 153H-B500ACD-59 153H-B500JCD-59
450 500 152H-B500ACD-60 152H-B500JCD-60 153H-B500ACD-60 153H-B500JCD-60
500 500 152H-B500ACD-61 152H-B500JCD-61 153H-B500ACD-61 153H-B500JCD-61
600 650 152H-B650ACD-62 152H-B650JCD-62 153H-B650ACD-62 153H-B650JCD-62
700 720 152H-B720ACD-63 152H-B720JCD-63 153H-B720ACD-63 153H-B720JCD-63
800 850 152H-B850ACD-65 152H-B850JCD-65 153H-B850ACD-65 153H-B850JCD-65
1000 1000 152H-B1000ACD-67 152H-B1000JCD-67 153H-B1000ACD-67 153H-B1000JCD-67
  
z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
§ Includes internal circulating fan rather than enclosure ventilation.
ª Supplied without bypass contactor or converter module.

Options

Open Type Options (only one selection allowed)

Option Description Cat. No.
Modification
Soft Stop Provides a ramp down time of 0…60 s for applications which require an extended coast-to-rest. A§ 
Pump Control Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s, and stopping time is adjustable from 0…120 s. B§ 
Preset Slow Speed Provides preset slow speeds for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load motor current. C§ 
SMB Smart Motor Braking Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of the motor’s full-load current rating. D§ 
Accu-Stop Provides stopping control for general positioning or to minimize jogging to stop. A 3-phase braking current is applied to the motor (adjustable from 0…400% of full-load current) until it reaches a preset slow speed (either 7% or 15% of rated motor speed). The motor is held at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Slow speed current is adjustable from 0…450% of full-load current. E§ 
Slow Speed with Braking Provides a preset slow speed for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load current.
Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of full-load motor current.
F§ 
  

§ Add the designated letter to the end of the cat. no. Example: To add the Pump Control option: Cat. No. 150-B24NBDB.


Enclosed Options

Option Description Cat. No.
Modification
Soft Stop Provides a ramp down time of 0…60 s for applications that require an extended coast-to-rest. -A¬ 
Pump Control Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s and stopping time is adjustable from 0…120 s. -B¬ 
24 A
35 A
54 A
97 A
135 A
180 A
240 A
360 A
500 A
650 A
720 A
850 A
1000 A
Push Buttons Start-Stop Push Button -1
Start-Stop Push Button with H-O-A Selector Switch -1F
Soft Stop Push ButtonT  -1XA
Pump Stop Push ButtonT  -1XB
Brake Push ButtonT  -1XD
Selector Switch Hand-Off-Auto Selector Switch -3
SMC-Off-Bypass Selector Switch -3B
Pilot Light Transformer Pilot Light‡  (Red or Green Lens) -4_
Push-To-Test Pilot Light‡  (Red Lens) -5_
Control Circuit Transformer Control Circuit Transformer (fused primary and secondary) -6P
SCR Fusing Fast Acting Current Limiting SCR Fusing for 24 A unit -SCR
Fast Acting Current Limiting SCR Fusing for 35 A unit
Fast Acting Current Limiting SCR Fusing for 54 A unit
Fast Acting Current Limiting SCR Fusing for 97…135 A unit
Fast Acting Current Limiting SCR Fusing for 180 A unit
Fast Acting Current Limiting SCR Fusing for 240 A unit
Fast Acting Current Limiting SCR Fusing for 360 A unit
Fast Acting Current Limiting SCR Fusing for 500 A unit
Fast Acting Current Limiting SCR Fusing for 650…720 A unit
Fast Acting Current Limiting SCR Fusing for 850 A unit
Fast Acting Current Limiting SCR Fusing for 1000 A unit
Door-Mounted Human
Interface Module
Programmer Only (Type 1) -HAP
Programmer Only (Type 4/12) -HJP
Digital Contral Panel (Type 1) -HA2
Digital Control Panel (Type 4/12) -HJ2
Communication Module Remote I/O -GD1
RS-232/422/485, DH485 -GD2
DeviceNet™ Network -GK5
Enhanced DeviceNet -GU6
ControlNet -CN1
  
¬ Add the designated letter to the end of the Cat. No. For example, to add the pump control option Cat. No. 152H-B180JBDB-51 .
T Option push buttons are available only when the corresponding option module is selected. For example, Cat. No. 150-A24JBDA-1XA.
‡ Specify pilot light lens color. Options: Red, Green.

Option Description Cat. No.
Modification
Protective Module¬  480V Line Side Protective Module 24…54 A -8L
480V Line Side Protective Module 97…360 A
600V Line Side Protective Module 24…54 A
600V Line Side Protective Module 97…360 A
480V Load Side Protective Module 24…54 A -8M
480V Load Side Protective Module 97…360 A
600V Load Side Protective Module 24…54 A
600V Load Side Protective Module 97…360 A
480V Both Line and Load Side Protective Module 24…54 A -8B
480V Both Line and Load Side Protective Module 97…360 A
600V Both Line and Load Side Protective Module 24…54 A
600V Both Line and Load Side Protective Module 97…360 A
Auxiliary ContactsT  N.O. auxiliary contacts for 24…240 A -90
N.O. auxiliary contacts for 360…1000 A
N.C. auxiliary contacts for 24…240 A -91
N.C. auxiliary contacts for 360…1000 A
1 N.O and 1 N.C. auxiliary contacts for 24…240 A -901
1 N.O. and 1 N.C. auxiliary contacts for 360…1000 A
Unwired Control RelaysØ  Bulletin 700CF 4-pole relay – 2 N.O. and 2 N.C. -89F22
Bulletin 700CF 4-pole relay – 3 N.O. and 1 N.C. -89F31
Bulletin 700CF 4-pole relay – 4 N.O. -89F40
Disconnect Auxiliaryz  N.O. disconnect auxiliary mounted on operating mechanism -98
N.C. disconnect auxiliary mounted on operating mechanism -99
Circuit Breaker Disconnect
Auxilaryª 
Internal N.O. circuit breaker auxiliary -98X
Internal N.C. circuit breaker auxiiary -99X
Service Entrance Label Service Entrance Label 24…650 A -SEL
720…1000 A
UL Label UL Label -UL
NEMA Bypass Contactor§  NEMA Bypass for 24…97 A unit -NB
NEMA Bypass for 135…180 A unit
NEMA Bypass for 240 A unit
NEMA Bypass for 360 A unit
NEMA Bypass for 500 A unit
NEMA Isolation Contactor§  NEMA Isolation for 24…97 A unit -NI
NEMA Isolation for 135…180 A unit
NEMA Isolation for 240 A unit
NEMA Isolation for 360 A unit
NEMA Isolation for 500 A unit
¬ Line and Load Side Protective Modules are standard on 500…1000 A units.
T Available only with enclosed Bulletin 150, 152 and 153 devices with bypass contactor. Maximum of four (4) auxiliary contacts.
§ Thermal overload for Bulletin 150 enclosed controllers only. Overload is standard on Bulletins 152 and 153.
Ø Instantaneous auxiliary contacts on Bulletin 700CF relays are non-convertible.
z Available only with Bulletin 152 and 153 devices. Maximum of two (2) disconnect auxiliaries.
ª Available only with Bulletin 153 devices. Maximum of two (2) disconnect auxiliaries.
v Order to be released to manufacturing upon release of signed print approval drawings.
§ 650, 720, 850, and 1000 A units currently use a NEMA contactor.

Accessories

Protective Modules¬ § 

  Current Rating (A) Description Field Modification
Cat. No.
Click to enlarge - 150-7_23-1 24…54   

480 V Protective Module (Field Installed)  

150-N84
  

600 V Protective Module (Field Installed)  

150-N86
97…360   

480 V Protective Module (Field Installed)  

150-N84L
  

600 V Protective Module (Field Installed)  

150-N86L
  
¬ The same protective module mounts on the line or load side of the SMC Dialog Plus Controller. For applications requiring both line and load side protection, two protective modules must be ordered.
§ Surge protection is provided as standard on 500…1000 A units

Terminal Lug Kits (97…1000 A)

  Current
Rating (A)
Wire Size Total No. of
Terminal Lugs
Possible Each Side
Pkg. Quantity Cat. No.
Line Side Load Side
Click to enlarge - 150-7_23-2 97…135 #6…250 MCM AWG
16 mm2…120 mm2
  
3  
3 3 199-LF1
180…360   
6  
6
500‡  #4…500 MCM AWG
25 mm2…240 mm2
  
6  
6 199-LG1
650…720‡    
9  
9
850…1000‡  (2) 1/0…500 MCM AWG
50 mm2…240 mm2
  
6  
6 199-LJ1
  
‡ Lugs are supplied with SMC.

IEC Terminal Covers

  Description Field Modification
Cat. No.
Click to enlarge - 150-7_23-3   
IEC line- or load-side terminal covers for 97…135 A devices (includes line and load termination covers)  
150-NT1
  
IEC line- or load-side terminal covers for 180…360 A devices (includes line and load termination covers)  
150-NT2
  

Description Degree of Protection Cat. No.
Click to enlarge - 150-7_39-1 Human Interface Modulev  Door Mount Bezel Kit IP30 (Type 1) 1201-DMA
Cat. No. 1201-HAP Programmer Only IP30 (Type 1)ª  1201-HAP
Click to enlarge - 150-7_39-2 Programmer Only IP65 (Type 4/12) with Bezel 1201-HJP
Cat. No. 1201-HA1 Analog Control Panelz  IP30 (Type 1)ª  1201-HA1
Click to enlarge - 150-7_39-3 Digital Control Panelz  IP30 (Type 1)ª  1201-HA2
Cat. No. 1201-HA2 Digital Control Panelz  IP65 (Type 4/12) with Bezel 1201-HJ2
Description For Use With Cat. No.
Click to enlarge - 150-7_39-4 Communication Cable Male-Male 0.3 m Human Interface Module and Communication Modules 1202-C03
1 m 1202-C10
3 m 1202-C30
Communication Cable
Cat. No. 1202-C10
9 m 1202-C90
Click to enlarge - 150-7_39-5 Communication Modulev  Single Point Remote I/O Bulletin 150 SMC Dialog Plus 1203-GD1
RS-232/RS-422/RS-485/DF1, or DH485 (Series B) 1203-GD2
ControlNet 1203-CN1
DeviceNet Network 1203-GK5
Communication Module
Cat. No. 1203-GD1
Enhanced DeviceNet 1203-GU6
Click to enlarge - 150-7_39-6 Click to enlarge - 150-7_39-7 Flex I/O SCANport Module§ 
Flex I/O Terminal Base
Bulletin 150 SMC Dialog Plus 1203-FB1
Cat. No. 1203-FM1 Cat No. 1203-SM1 Flex I/O ModuleØ  1203-FM1
Communication Option Kits SLC Communication Module 1203-SM1
  
z Start, Stop, and Jog buttons are the only active controls when used with the SMC Dialog Plus Controller.
ª Requires Type 1 Door Mount Bezel Kit.
v Separately powered 120/240V AC.
§ Each Flex I/O SCANport Module requires (1) Cat. No. 1203-FB1 and (1) Cat. No. 1203-FM1.
Ø Requires a Communication Option Cable (Cat. No. 1202-C03/C10/C30/C90) to be functional. These units are not acceptable for NEMA Type 4 door mounting or UL Type 4X outdoor only.

Converter Modules¬ 

  Motor Full Load
Current Range [A]
Cat. No.
Click to enlarge - 150-7_40-1 2.5…20 A 825-MCM20
Cat. No. 825-MCM180 9…100 A 825-MCM180
Click to enlarge - 150-7_40-2 64…360 A 825-MCM630
Cat. No. 825-MCM630
Connection Cable (Replacement)
Bul. 825-P to Bul. 825-MCM connection
825-MCA
  

  Description Cat. No.
Click to enlarge - 150-7_40-3 Fanning Strip for Bulletin 825 Converter Modules 150-NFS
Cat. No. 150-NFS
Click to enlarge - 150-7_40-4 M8 connections
Set of three
4 x 16 x 102 mm (1/8 x 5/8 x 4-1/64 in.) (125 A max.)
Universally applicable
Weight: 230 g
825-MVM
  
¬ Must be used with fanning strip Cat. No. 150-NFS.

Specifications

Functional Design Specifications
Standard Features Installation Power Wiring The SMC Dialog Plus Controller can be wired with or without an isolation contactor. Bypass contactors can be employed after the controller has brought the motor to full speed.
Control Wiring 2- and 3-wire control for a wide variety of applications.
Setup Keypad The SMC Dialog Plus Controller is configured with the front keypad and backlit LCD display.
Software Parameter values can be downloaded to the SMC Dialog Plus Controller with DriveTools programming software and the Cat. No. 1203-GD2 communication module.
Communications One serial port provided for connection to optional human interface and communication modules.
Starting Modes Soft start with selectable kickstart, current limit, dual ramp, and full voltage in one unit.
Protection and Diagnostics Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault.
Metering Amps, volts, kW, kWH, elapsed time, power factor, motor thermal capacity usage.
Status Indication Stopped, ramping, stopping, at speed, and fault.
Auxiliary Contacts (1) Single-pole double-throw contact programmable as normal or up-to-speed; one programmable as normal or fault.
Optional Features Soft Stop Extended coast-to-rest to minimize load shifting. Ramp down time is adjustable from 0…60 s.
Pump Control Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting time is adjustable from 0…30 s. Stopping time is adjustable from 0…120 s.
Preset Slow Speed Enables the operator to position material. The preset slow speed can be set for low (7% of base speed), high (15% of base speed), reverse low (10% of base speed) or reverse high (20% of base speed).
SMB Smart Motor Braking Provides motor braking without additional equipment for applications that require the motor to stop quickly. Braking current is adjustable from 0…400% of the motor’s full-load current rating.
Accu-Stop/Slow Speed with
Braking
Combines Smart Motor Braking and Preset Slow Speed. Braking current is adjustable from 0…400% of
full-load current. Slow speed can be set for either Low (7% of base speed) or High (15% of base speed).
  

Electrical Ratings
  UL/CSA/NEMA IEC
Power Circuit Rated Operation Voltage 200…480V AC
200…600V AC (–15%, +10%)
200…415V
200…500V
Rated Insulation Voltage N/A 500V
Rated Impulse Voltage N/A 6000V
Dielectric Withstand 2200V AC 2500V
Repetitive Peak Inverse Voltage Rating 200…480V AC: 1400V
200…600V AC: 1600V
200…415V: 1400V
200…500V: 1600V
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category MG 1 AC-53a
Protection Against Electrical Shock N/A IP00 (open device)
DV/DT Protection RC Snubber Network
Transient Protection Metal Oxide Varistors:
220 Joules @ 24…360 A
220 Joules @ 480V, 500…1000 A
300 Joules @ 600V, 500…1000 A
Short-Circuit
Protection
SCPD Performance Type 1
SCPD List Maximum Fuse or Circuit Breaker (A):
Device Operational Current Rating (A) 24 80
35 125
54 200
97 350
135 500
180 600
240 700
360 1000
500 1200
650 1600
720 2000
850 2500
1000 3000
Control Circuit Rated Operational Voltage 100…240V AC
24V AC
24V DC
100…240V
24V
24V DC
Rated Insulation Voltage N/A 240V
Rated Impulse Voltage N/A 3000V
Dielectric Withstand 1600V AC 2000V
Operating Frequency 50/60 Hz 50/60 Hz
Protection Against Electric Shock N/A IP20
Power
Requirements
Control Module 40 VA
Heatsink Fan(s) (A)¬  24
35
54
97 45 VA
135 45 VA
180 45 VA
240 45 VA
360 45 VA
500 145 VA
650 320 VA
720 320 VA
850 320 VA
1000 320 VA
  
¬ For devices rated 24…500 A, heatsink fans can be powered by either 110/120V AC or 220/240V AC. For devices rated 650…1000 A, heatsink fans can only be powered by 110/120V AC.

Electrical Ratings, Continued
  UL/CSA/NEMA IEC
Maximum Heat
Dissipation
(Watts)
Controller
Rating (A)
24 110
35 150
54 200
97 285
135 490
180 660
240 935
360 1170
500 1400
650 2025
720 2250
850 2400
1000 2760
Auxiliary
Contacts
Rated Operation Voltage 240V AC 240V
Rated Insulation Voltage N/A 240V
Dielectric Withstand 1600V AC 2000V
Operating Frequency 50/60 Hz 50/60 Hz
Utilization Category B300 (terminals 18…19)
C300 (terminals 18…20)
C300 (terminals 29…30)
AC-15
SCPD Performance Type 2
SCPD List Class CC 8 A @ 1000 A Available Fault Current
Environmental
Operating Temperature Range 0…+50 °C (32…122 °F) (open)
0…+40 °C (32…104 °F) (enclosed)
Storage and Transportation Temperature Range –20…+75 °C
  2000 m (6560 ft)
Humidity 5…95% (non-condensing)
Pollution Degree 2
Mechanical
Resistance to
Vibration
Operational
Non-Operational
1.0 G Peak, 0.006 in. displacement
2.5 G, 0.015 in. displacement
Resistance to
Shock
Operational
Non-Operational
15 G
30 G
Construction Power
Poles
Thermoset Moldings
Heatsink hockey puck thyristor
24…135 A
180…1000 A
Control Modules Thermoset and Thermoplastic Moldings
Metal Parts Anodized Aluminum, Plated Brass, Copper, or Painted Steel
Terminals Power
Terminals
24…54 A 6.0 mm hole with clamp screw
97 and 135 A One 11.5 mm (0.453 in.) diameter hole each
180…360 A One 10.5 mm (0.413 in.) diameter hole each
500 A Two 13.5 mm (0.531 in.) diameter holes each
650 and 720 A Three 13.1 mm (0.515 in.) diameter holes each
850 and 1000 A Six 13.1 mm (0.515 in.) diameter holes each
Power Terminal Markings NEMA, CENELEC EN50 012
Control Terminals M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate
Other
EMC Emission
Levels
Conducted Radio Frequency Emissions
Radiated Emissions
Class A
Class A
EMC Immunity
Levels
Electrostatic Discharge 8 kV Air Discharge
Radio Frequency Electromagnetic Field Per IEC 947-4-2
Fast Transient Per IEC 947-4-2
Surge Transient Per IEC 947-4-2
Overload
Characteristics
Current Range 1.0…999.9 A
Trip Classes 10, 15, 20, and 30
Trip Current Rating 120% of Motor FLC
Number of Poles 3
  

Specifications, Continued

Fuse Clip Sizing and Type for Fusible Combination Controllers¬ T 

Horsepower @ 480V Fuse Clip Size/Type Fuse Size Range [A]
15 30 A/Class J 0…30
20 60 A/Class J 31…60
25 60 A/Class J 31…60
30 60 A/Class J 31…60
40 100 A/Class J 61…100
50 100 A/Class J 61…100
60 200 A/Class J 101…200
75 200 A/Class J 101…200
100 200 A/Class J 101…200
125 400 A/Class J 201…400
150 400 A/Class J 201…400
200 400 A/Class J 201…400
250 400 A/Class J 401…600
300 600 A/Class J 401…600
350 600 A/Class J 401…600
400 1200 A/Class L 601…1600
450 1200 A/Class L 601…1600
500 1200 A/Class L 601…1600
600 1200 A/Class L 601…1600
700 1200 A/Class L 601…1600
800 1200 A/Class L 601…1600
  
¬ Consult NEC Handbook for proper fuse sizing guidelines.
T Optional fuse clip sizes and types are available upon request. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Circuit Breaker Sizes and Rating Plug Sizes

Horsepower @ 480V Circuit Breaker Size [A]/
Rating Plug Size [A]
Interrupting Rating in
Symmetrical Amps @ 480V‡ 
15 150/50 14 000
20 150/50 14 000
25 150/60 14 000
30 150/70 14 000
40 150/100 14 000
50 150/125 14 000
60 250/150 25 000
75 250/175 25 000
100 250/225 25 000
125 250/250 25 000
150 400/300 35 000
200 400/400 35 000
250 600/500 35 000
300 600/600 35 000
350 800/800 35 000
400 800/800 50 000
450 1200/1000 50 000
500 1200/1200 50 000
600 1200/1200 50 000
700 2000/1600 65 000
800 2000/2000 65 000
  
‡ For higher interrupting ratings, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

Approximate Dimensions

Approximate Dimensions and Shipping Weights

Open Type Controllers

Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Controller
Rating [A]
Height Width Depth Weight
24 180
(7.09)
154
(6.06)
185
(7.29)
4.5 kg
(10 lbs)
35 240
(9.45)
214
(8.43)
195
(7.68)
6.8 kg
(15 lbs)
54 290
(11.42)
244
(9.61)
225
(8.86)
11.3 kg
(25 lbs)
97 336
(13.23)
248
(9.77)
256
(10.09)
10.4 kg
(23 lbs)
135 336
(13.23)
248
(9.77)
256
(10.09)
11.8 kg
(26 lbs)
180 560
(22.06)
273
(10.75)
294
(11.58)
25 kg
(55 lbs)
240 560
(22.06)
273
(10.75)
294
(11.58)
30 kg
(65 lbs)
360 560
(22.06)
273
(10.75)
294
(11.58)
30 kg
(65 lbs)
500 588
(23.17)
508
(20.00)
311
(12.23)
40.8 kg
(90 lbs)
650…1000 1524
(60.0)
813
(32.00)
402
(15.83)
167.8 kg
(370 lbs)
  

Enclosed Type Controllers

Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes. All dimensions are subject to change.
Factory-installed options may affect enclosure size requirements.
Exact dimensions can be obtained after order entry. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.


Click to enlarge - 150-7_18-2


Controller
Rating [A]
A J  
IP30 (Type 1) IP54 (Type 12) IP65 (Type 4)
B Height A Width C Depth B Height A Width C Depth B Height A Width C Depth
Non-Combination Controller
24 610 (24) 406 (16) 229 (9) 610 (24) 406 (16) 229 (9) 610 (24) 406 (16) 229 (9)
35 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
54 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
97 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
135 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
180 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
240 965 (38) 762 (30) 356 (14) 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14)
360 1295 (51) 914 (36) 356 (14) 1524 (60) 914 (36) 356 (14) 1524 (60) 914 (36) 356 (14)
500 1524 (60) 914 (36) 356 (14) 2286 (90) 889 (35) 508 (20) 2134 (90) 1016 (35) 457 (20)
650 2286 (90) 889 (35) 508 (20) 2286 (90) 1778 (60) 508 (20) 2286 (90) 1778 (60) 508 (20)
720 2286 (90) 889 (35) 508 (20) 2286 (90) 1778 (60) 508 (20) 2286 (90) 1778 (60) 508 (20)
850 2286 (90) 889 (35) 508 (20) 2286 (90) 1778 (60) 508 (20) 2286 (90) 1778 (60) 508 (20)
1000 2286 (90) 889 (35) 508 (20) 2286 (90) 1778 (60) 508 (20) 2286 (90) 1778 (60) 508 (20)
Combination Controllers with Fusible Disconnect
24 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
35 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
54 (60 A Disconnect) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
54 (100 A Disconnect) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
97 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
135 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
180 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14)
240 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14)
360 1524 (60) 965 (38) 356 (15) 1524 (60) 965 (38) 356 (15) 1524 (60) 965 (38) 356 (15)
500 (600 A Disconnect) 2134 (84) 1016 (40) 457 (18) 2134 (84) 1016 (40) 457 (18) 2134 (84) 1016 (40) 457 (18)
500 (1200 A Disconnect) 2286 (90) 1143 (55) 508 (20) 2286 (90) 1270 (55) 508 (20) 2286 (90) 1778 (55) 508 (20)
650 2286 (90) 1397 (55) 508 (20) 2286 (90) 1778 (55) 508 (20) 2286 (90) 1778 (55) 508 (20)
720 2286 (90) 1397 (55) 508 (20) 2286 (90) 1778 (55) 508 (20) 2286 (90) 1778 (55) 508 (20)
850 2286 (90) 1397 (55) 508 (20) 2286 (90) 2667 (95) 508 (20) 2286 (90) 2667 (95) 508 (20)
1000 2286 (90) 1397 (55) 508 (20) 2286 (90) 2667 (95) 508 (20) 2286 (90) 2667 (95) 508 (20)
Combination Controllers with Circuit Breaker
24 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
35 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
54 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12) 762 (30) 610 (24) 305 (12)
97 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
135 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14) 965 (38) 762 (30) 356 (14)
180 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14)
240 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14) 1295 (51) 914 (36) 356 (14)
360 1524 (60) 965 (38) 356 (14) 1524 (60) 965 (38) 356 (14) 1524 (60) 965 (38) 356 (14)
500 2134 (90) 1016 (35) 457 (20) 2134 (90) 1016 (35) 457 (20) 2134 (90) 1016 (35) 457 (20)
650 2286 (90) 1397 (55) 508 (20) 2286 (90) 1778 (50) 508 (20) 2286 (90) 1778 (50) 508 (20)
720 2286 (90) 1397 (55) 508 (20) 2286 (90) 1778 (50) 508 (20) 2286 (90) 1778 (50) 508 (20)
850 2286 (90) 1778 (55) 508 (20) 2286 (90) 2667 (65) 508 (20) 2286 (90) 2667 (65) 508 (20)
1000 2286 (90) 1778 (55) 508 (20) 2286 (90) 2667 (65) 508 (20) 2286 (90) 2667 (65) 508 (20)