SMC™ Dialog Plus Smart Motor Controller
| Product Overview |
|
|
|
|
|
Bulletin 150 — SMC™ Dialog Plus Smart Motor Controller
The SMC Dialog Plus™ controller provides microprocessor controlled starting for standard three-phase squirrel-cage induction motors. Four standard modes of operation are available within a single controller:
- Soft Start with Selectable Kickstart
- Dual Ramp Start
- Current Limit Start with Selectable Kickstart
- Full Voltage Start
Options include:
- Soft Stop
- SMB Smart Motor Braking
- Pump Control
- Accu-Stop
- Preset Slow Speed
- Slow Speed with Braking
Features include:
- Built-in electronic motor overload protection
- Metering
- SCANport communication
- Keypad programming
- Three programmable auxiliary contacts
- LCD display
The SMC Dialog Plus™ controller is available for motors rated 1…1000 A; 200…480V AC, or 200…600V AC, 50 and 60 Hz. In addition to motors, the SMC Dialog Plus™ controller can be used to control resistive loads.
Standards Compliance and Certifications
Standards Compliance
UL 508
CSA C22.2 No.14
EN/IEC 60947-1
EN/IEC 60947-4-2
Certifications
cULus Listed (Open Type) (File No. E96956, Guides NMFT, NMFT7)
CSA Certified (File No. LR 1234)
CE Marked (Open Type) per EMC and Low Voltage Directive
CCC Certified
Modes of Operation
Modes of Operation
The SMC Dialog Plus controller provides the following modes of operation: Soft Start with selectable Kickstart, Current Limit Start, Dual Ramp Start, and Full Voltage Start.
Soft Start
This method has the most general application. The motor is raised to an initial torque value which is programmable from 0…90% of locked rotor torque. The motor voltage is gradually increased during the acceleration ramp time, which can be programmed from 0…30 seconds.
Soft Start with Selectable Kickstart
A kickstart, or boost, at the beginning of the voltage ramp is intended to provide a current pulse of 550% of full load current. The kickstart time is adjustable from 0.0…2.0 seconds. This allows the motor to develop additional torque at start for loads which may need a boost to get started.
Current Limit Start
This starting mode is used when it is necessary to limit the maximum starting current. The current limit can be programmed for 50…600% of full load current.
Dual Ramp Start
This starting mode is useful on applications that have varying loads and therefore varying starting torque requirements. The Dual Ramp Start offers the user the option to select between two separate Soft Start profiles with separately adjustable ramp times and initial torque settings.
The acceleration ramp times can be programmed from 0…30 seconds. The initial torque values can be programmed from 0…90% of locked rotor torque. Note: Dual Ramp is only available with the standard controller.
Full Voltage Start
This mode is used for applications requiring across-the-line starting. The ramp time is less than 1/4 second.
|
|
|
|
|
Description of Starting and Stopping Options
The following options are available in the SMC Dialog Plus controller. Only one option may be added to the standard unit.
Soft Stop¬
This option can be used on applications that require an extended coast to rest. It is designed for frictional loads that tend to stop suddenly when voltage is removed from the motor.
The voltage ramp down time can be programmed from 0…60 seconds. The load will stop when the motor voltage drops to a point where the load torque is greater than the motor torque.
Pump Control¬
This option is used to reduce surges during the starting and stopping of a centrifugal pump by smoothly accelerating and decelerating the motor. The microprocessor analyzes the motor variables and generates commands which control the motor and reduce the possibility of surges occurring in the system.
The starting time is programmable from 0…30 seconds and the stopping time is programmable from 0…120 seconds.
Preset Slow Speed
This option can be used on applications that require a slow speed (for example, moving material into position).
The preset slow speed can be programmed for either 7% of base speed (low) or 15% of base speed (high) in the forward direction. It can also be set for 10% of base speed (low) or 20% of base speed (high) in the reverse direction without a reversing contactor.
SMB Smart Motor Braking¬
This option provides motor braking for applications that require the motor to stop faster than a coast to rest. Braking control, with automatic zero speed shut off, is fully integrated into the compact design of the SMC Dialog Plus controller. This design facilitates a clean, straightforward installation and eliminates the requirement for additional hardware such as braking contactors, resistors, timers, and speed sensors.
The microprocessor based braking system applies braking current to a standard squirrel cage induction motor. The strength of the braking current is programmable from 150…400% of full load current.
Accu-Stop¬
This option is used in applications requiring controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7 or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed.
Braking current is programmable from 0…400% of full load current. Slow Speed Current is programmable from 0…450% of full load current. Slow speed can be programmed for either 7% (low) or 15% (high).
Accu-Stop with Slow Speed at Start¬
The Accu-Stop option can also allow the motor to operate at a preset slow speed when Slow Speed Start is selected. This minimizes the jogging required to position a load. The start command will ramp the voltage from the preset slow speed to full speed. The operation of Accu-Stop is the same as explained previously.
Slow Speed with Braking¬
Slow Speed with Braking is used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop.
Slow speed adjustments are 7% (low) or 15% (high) of rated speed. Slow speed acceleration current is adjustable from 0…450%. Slow speed running current is adjustable from 0…450% of full load current. Braking current is adjustable from 0…400%.
¬ Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirements.
The following options are available in the SMC Dialog Plus controller. Only one option may be added to the standard unit.
|
|
|
|
|
|
|
Description of Features
Electronic Motor Overload Protection
The SMC Dialog Plus controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm.
When coordinated with the proper short circuit protection, overload protection is intended to protect the motor, motor controller, and power wiring against overheating caused by excessive overcurrent. The SMC Dialog Plus controller meets applicable requirements as a motor overload protective device.
The controllers overload protection is programmable, providing the user with flexibility. The overload trip class can be selected for class 10, 15, 20, or 30 protection. The trip current is programmed by entering the motor full-load current rating.
Thermal memory is included to accurately model motor operating temperature. Ambient insensitivity is inherent in the electronic design of the overload.
Note: The current sensing capability of the SMC Dialog Plus controller is disabled during bypass operation. The Bulletin 825 Converter Module and 150-NFS fanning strip are required for providing current feedback in these applications. Note: To achieve calibration, 70% motor load or greater is required at the motor shaft for 2 s. Calibration is required when a Bulletin 825 Converter Module is not used.
Stall Protection and Jam Detection
Motors can experience locked rotor currents and develop high torque levels in the event of a stall or a jam. These conditions can result in winding insulation breakdown or mechanical damage to the connected load. The SMC Dialog Plus controller provides both stall protection and jam detection for enhanced motor and system protection. Stall protection allows the user to program a maximum stall protection delay time from 0…10 s. The stall protection delay time is in addition to the programmed start time and begins only after the start time has timed out. If the controller senses that the motor is stalled, it will shut down after the delay period has expired.
Jam detection allows the user to determine the motor jam detection level as a percentage of the motors full load current rating. To prevent nuisance tripping, a jam detection delay time, from 0.0…10.0 s, can be programmed. This allows the user to select the time delay required before the SMC Dialog Plus controller will trip on a motor jam condition. The motor current must remain above the jam detection level during the delay time. Jam detection is active only after the motor has reached full speed.
Energy Saver
This is a standard feature with the SMC Dialog Plus controller. It is used to save energy on applications where the motor is lightly loaded or unloaded for long periods of time. The Energy Saver is a built-in feature of the controller. It does not require additional panel space or external wiring. It also does not require a complicated setup procedure.
Phase Rebalance
The SMC Dialog Plus controller incorporates, as standard, a dynamic Phase Rebalance feature. The controller compensates for voltage unbalance by automatically adjusting the voltage output to balance the 3-phase currents drawn by the motor. When phase rebalance is achieved, motor life may be extended and production can continue without interruption. Phase Rebalance is a built-in feature of the controller and does not require a complicated setup procedure.
Note: Phase Rebalance requires the use of the Bulletin 825 Converter Module and the Cat. No. 150-NFS fanning strip.
Note: The performance of the Phase Rebalance feature is dependent on the motors loading and characteristics. Severe imbalances cannot be corrected.
Underload Protection
Utilizing the underload protection of the SMC Dialog Plus controller, motor operation can be halted if a drop in current is sensed.
The SMC Dialog Plus controller provides an adjustable underload trip setting from 0…99% of the programmed motor full load current rating with an adjustable trip delay time of 0…99 s.
Undervoltage Protection
The SMC Dialog Plus controllers undervoltage protection will halt motor operation if a drop in the incoming line voltage is detected.
The undervoltage trip level is adjustable as a percentage of the programmed line voltage, from 0…99%. To eliminate nuisance trips, a programmable undervoltage trip delay time of 0…99 s can also be programmed. The line voltage must remain below the undervoltage trip level during the programmed delay time.
Overvoltage Protection
If a rise in the incoming line voltage is detected, the SMC Dialog Plus controllers overvoltage protection will halt motor operation.
The overvoltage trip level is adjustable as a percentage of the programmed line voltage, from 0…99%. To eliminate nuisance trips, a programmable overvoltage trip delay time of 0…99 s can also be programmed. The line voltage must remain above the overvoltage trip level during the programmed delay time.
Voltage Unbalance Protection
Voltage unbalance is detected by monitoring the 3-phase supply voltage magnitudes in conjunction with the rotational relationship of the three phases. The controller will halt motor operation when the calculated voltage unbalance reaches the user-programmed trip level.
The voltage unbalance trip level is programmable from 0…25% unbalance.
Excessive Starts Per Hour
The SMC Dialog Plus controller allows the user to program the allowed number of starts per hour (up to 99). This helps eliminate motor stress caused by repeated starting during a short time period.
Metering
Power monitoring parameters include:
- 3-phase current
- Power factor
- 3-phase voltage
- Motor thermal capacity usage
- Power in kW
- Elapsed time
- Power usage in kWH
-
Note: The motor thermal capacity usage allows the user to monitor the amount of overload thermal capacity usage before the SMC Dialog Plus controllers built-in electronic overload trips.
Note: In bypass configurations, the current sensing and power factor measurement capability of the SMC Dialog Plus controller is disabled. Three-phase current measurement, kW, kWH, and motor thermal capacity usage can still be maintained with the use of the Bulletin 825 Converter Module.
Note: The usage of an SMC Controller on a generator and line power requires the use of a Bulletin 825 Converter Module.
Built-in SCANport™ Communication
A serial interface port is provided as standard, which allows connection to a Bulletin 1201 Human Interface Module or a variety of Bulletin 1203 Communication Modules. This includes Allen-Bradley Remote I/O, DeviceNet network and RS-232/422/485-DF1.
LCD Display
The SMC Dialog Plus controllers two-line 16-character backlit LCD display provides parameter identification using clear, informative text. Controller set up can be performed quickly and easily without the use of a reference manual. Parameters are arranged in an organized four-level menu structure for ease of programming and fast access to parameters.
Keypad Programming
Programming of parameters is accomplished through a five-button keypad on the front of the SMC Dialog Plus controller. The five buttons include up and down arrows, an Enter button, a Select button, and an Escape button. The user needs only to enter the correct sequence of keystrokes for programming the SMC Dialog Plus controller.
Auxiliary Contacts
Three hard contacts are furnished as standard with the SMC Dialog Plus controller. The first two contacts are programmable for Normal/Up-to-speed. The third is programmable for Normal/Fault.
Cat. No. Explanation
Open and Non-Combination
| 150 | | B180 | N | B | D | A | | 8L | ||||
| a | b | c | d | e | f | g |
| a | |
| Bulletin Number | |
| Code | Description |
| 150 | Solid-State Controller |
| 150B | Solid-State Controller and Isolation Contactor (enclosed only) |
| b | |
| Controller Ratings | |
| Code | Description |
| B24 | 24 A, 1…15 Hp @ 460V AC |
| B35 | 35 A, 1…25 Hp @ 460V AC |
| B54 | 54 A, 1…40 Hp @ 460V AC |
| B97 | 97 A, 5…75 Hp @ 460V AC |
| B135 | 135 A, 5…100 Hp @ 460V AC |
| B180 | 180 A, 5…150 Hp @ 460V AC |
| B240 | 240 A, 5…200 Hp @ 460V AC |
| B360 | 360 A, 5…300 Hp @ 460V AC |
| B500 | 500 A, 4…400 Hp @ 460V AC |
| B650 | 650 A, 5…500 Hp @ 460V AC |
| B720 | 720 A, 5…600 Hp @ 460V AC |
| B850 | 850 A, 10…700 Hp @ 460V AC |
| B1000 | 1000 A, 10…800 Hp @ 460V AC |
| c | |
| Enclosure Type | |
| Code | Description |
| N | Open |
| A | NEMA Type 1 (IP30) |
| F | NEMA Type 4 (IP65) |
| J | NEMA Type 12 (IP54) |
| H | NEMA Type 3R |
| d | |
| Input Line Voltage | |
| Open Type | |
| Code | Description |
| B | 200…460V AC, 3-phase, 50 and 60 Hz |
| C | 200…575V AC, 3-phase, 50 and 60 Hz |
| Non-Combination Enclosed Only | |
| H | 200…208V AC, 3-phase, 50 and 60 Hz |
| A | 230V AC, 3-phase, 50 and 60 Hz |
| B | 200…460V AC, 3-phase, 50 and 60 Hz |
| C | 200…575V AC, 3-phase, 50 and 60 Hz |
| e | |
| Control Voltage | |
| Code | Description |
| D | 100…240V AC |
| R | 24V AC/DC |
| f | |
| Control Options (see Enclosed Options for a full listing.) | |
| Note: Select Only One | |
| Code | Description |
| Blank | Standard |
| B | Pump Control |
| C | Preset Slow Speed |
| D | SMB Smart Motor Braking |
| E | Accu-Stop |
| F | Slow Speed with Braking |
| g | |
| Options | |
| Code | Description |
| 8L | Line-Mounted Protective Module |
| 8M | Load-Mounted Protective Module |
| 8B | Line- and Load-Mounted Protective Modules |
Combination
| 152H | | B240 | A | BD | B | | 52 | | 8B | |||
| a | b | c | d | e | f | g |
| a | |
| Bulletin Number | |
| Code | Description |
| 152B | Solid-State Controller with Fusible Disconnect and Isolating Contactor |
| 152H | Solid-State Controller with Fusible Disconnect |
| 153B | Solid-State Controller with Circuit Breaker and Isolating Contactor |
| 153H | Solid-State Controller with Circuit Breaker |
| b | |
| Controller Ratings | |
| Code | Description |
| B24 | 24 A, 1…15 Hp @ 460V AC |
| B35 | 35 A, 1…25 Hp @ 460V AC |
| B54 | 54 A, 1…40 Hp @ 460V AC |
| B97 | 97 A, 5…75 Hp @ 460V AC |
| B135 | 135 A, 5…100 Hp @ 460V AC |
| B180 | 180 A, 5…150 Hp @ 460V AC |
| B240 | 240 A, 5…200 Hp @ 460V AC |
| B360 | 360 A, 5…300 Hp @ 460V AC |
| B500 | 500 A, 4…400 Hp @ 460V AC |
| B650 | 650 A, 5…500 Hp @ 460V AC |
| B720 | 720 A, 5…600 Hp @ 460V AC |
| B850 | 850 A, 10…700 Hp @ 460V AC |
| B1000 | 1000 A, 10…800 Hp @ 460V AC |
| c | |
| Enclosure Type | |
| Code | Description |
| A | NEMA Type 1 (IP30) |
| J | NEMA Type 12 (IP54) |
| F | NEMA Type 4 (IP65) |
| H | NEMA 3R |
| d | |
| Line Voltage | |
| Code | Description |
| HD | 200…208V AC, 3-phase, 50 and 60 Hz |
| AD | 230V AC, 3-phase, 50 and 60 Hz |
| BD | 400…460V AC, 3-phase, 50 and 60 Hz |
| CD | 500…575V AC, 3-phase, 50 and 60 Hz |
| e | |
| Control Options | |
| Code | Description |
| Blank | Standard |
| B | Pump Control |
| C | Preset Slow Speed |
| D | SMB Smart Motor Braking |
| E | Accu-Stop |
| F | Slow Speed with Braking |
| f | |||
| Horsepower | |||
| Code | Hp Rating | Code | Hp Rating |
| 39 | 5 | 52 | 150 |
| 40 | 7-1/2 | 54 | 200 |
| 41 | 10 | 56 | 250 |
| 42 | 15 | 57 | 300 |
| 43 | 20 | 58 | 350 |
| 44 | 25 | 59 | 400 |
| 45 | 30 | 60 | 450 |
| 46 | 40 | 61 | 500 |
| 47 | 50 | 62 | 600 |
| 48 | 60 | 63 | 700 |
| 49 | 75 | 65 | 800 |
| 50 | 100 | 67 | 1000 |
| 51 | 125 | — | — |
| g | |
| Options (see Enclosed Options for a full listing.) | |
| Code | Description |
| 8L | Line-Mounted Protective Module |
| 8M | Load-Mounted Protective Module |
| 8B | Line- and Load-Mounted Protective Modules |
Product Selection
Open Type Controllers
| Build a Catalog Number |
Up to 460V AC
| Current¬ Rating (A) |
kWT | Hp | 100…240V AC 50/60 Hz Control Cat. No. |
24V AC/DC Control Cat. No. |
||||
| 230V AC 50 Hz |
400V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
||||
| 24 | 5.5 | 11 | 1…5 | 1…7.5 | 1…15 | 150-B24NBD | 150-B24NBR | |
| 35 | 10 | 18.5 | 1…10 | 1…10 | 1…25 | 150-B35NBD | 150-B35NBR | |
| 54 | 15 | 22 | 1…15 | 1…20 | 1…40 | 150-B54NBD | 150-B54NBR | |
| 97 | 25 | 45 | 5…30 | 5…30 | 5…75 | 150-B97NBD | § | 150-B97NBR |
| 135 | 37 | 75 | 5…40 | 5…50 | 5…100 | 150-B135NBD | § | 150-B135NBR |
| 180 | 51 | 90 | 5…60 | 5…60 | 5…150 | 150-B180NBD | § | 150-B180NBR |
| 240 | 75 | 132 | 5…75 | 5…75 | 5…200 | 150-B240NBD | § | 150-B240NBR |
| 360 | 110 | 200 | 5…125 | 5…150 | 5…300 | 150-B360NBD | § | 150-B360NBR |
| 500 | 150 | 257 | 5…150 | 5…200 | 5…400 | 150-B500NBD | § | 150-B500NBR |
| 650 | 200 | 355 | 5…200 | 5…250 | 5…500 | 150-B650NBD | § | 150-B650NBR |
| 720 | 220 | 400 | 5…250 | 5…300 | 5…600 | 150-B720NBD | § | 150-B720NBR |
| 850 | 257 | 475 | 10…300 | 10…350 | 10…700 | 150-B850NBD | § | 150-B850NBR |
| 1000 | 315 | 530 | 10…350 | 10…400 | 10…800 | 150-B1000NBD | § | 150-B1000NBR |
| ¬ Controllers rated 97…360 A are not equipped with line and load terminal lugs. See Accessories for terminal lug kits. | ||||||||
| T The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices rated 850 A and greater. | ||||||||
| Hp ratings at motor terminal voltages for 208, 480, and 600 line volts, respectively. | ||||||||
| § 120V AC control is required for heatsink fan operation. | ||||||||
Up to 575V AC
| Current¬ Rating (A) |
kWT | Hp | 100…240V AC 50/60 Hz Control Cat. No. |
24V AC/DC Control Cat. No. |
||||||
| 230V AC 50 Hz |
400V AC 50 Hz |
500V AC 50 Hz |
200V AC 60 Hz |
230V AC 60 Hz |
460V AC 60 Hz |
575V AC 60 Hz |
||||
| 24 | 5.5 | 11 | 15 | 1…5 | 1…7.5 | 1…15 | 1…20 | 150-B24NCD | 150-B24NCR | |
| 35 | 10 | 18.5 | 22 | 1…10 | 1…10 | 1…25 | 1…30 | 150-B35NCD | 150-B35NCR | |
| 54 | 15 | 22 | 37 | 1…15 | 1…20 | 1…40 | 1…50 | 150-B54NCD | 150-B54NCR | |
| 97 | 25 | 45 | 63 | 5…30 | 5…30 | 5…75 | 5…75 | 150-B97NCD | § | 150-B97NCR |
| 135 | 37 | 75 | 90 | 5…40 | 5…50 | 5…100 | 5…125 | 150-B135NCD | § | 150-B135NCR |
| 180 | 51 | 90 | 132 | 5…60 | 5…60 | 5…150 | 5…150 | 150-B180NCD | § | 150-B180NCR |
| 240 | 75 | 132 | 160 | 5…75 | 5…75 | 5…200 | 5…250 | 150-B240NCD | § | 150-B240NCR |
| 360 | 110 | 200 | 250 | 5…125 | 5…150 | 5…300 | 5…350 | 150-B360NCD | § | 150-B360NCR |
| 500 | 150 | 257 | 355 | 5…150 | 5…200 | 5…400 | 5…500 | 150-B500NCD | § | 150-B500NCR |
| 650 | 200 | 355 | 475 | 5…200 | 5…250 | 5…500 | 5…600 | 150-B650NCD | § | 150-B650NCR |
| 720 | 220 | 400 | 500 | 5…250 | 5…300 | 5…600 | 5…700 | 150-B720NCD | § | 150-B720NCR |
| 850 | 257 | 475 | 600 | 10…300 | 10…350 | 10…700 | 10…800 | 150-B850NCD | § | 150-B850NCR |
| 1000 | 315 | 530 | 710 | 10…350 | 10…400 | 10…800 | 10…1000 | 150-B1000NCD | § | 150-B1000NCR |
| ¬ Controllers rated 97…360 A are not equipped with line and load terminal lugs. See Accessories for terminal lug kits. | ||||||||||
| T The minimum rating is: 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices rated 850 A and greater. | ||||||||||
| Hp ratings at motor terminal voltages for 208, 480, and 600 line volts, respectively. | ||||||||||
| § 120V AC control is required for heatsink fan operation. | ||||||||||
Non-Combination Controllers — IP30 (Type 1) Vented Enclosed, IP65 (Type 4) Enclosed, and IP54 (Type 12) Enclosed
| Build a Catalog Number |
Require a separate 100…240V, 50/60 Hz single-phase control source. Line and load terminations are provided as standard. The IP65 (Type 4) Enclosed Non-Combination, and IP54 (Type 12) Enclosed Non-Combination 97…1000 A controllers include a bypass contactor and a Bulletin 825 converter module. Enclosures other than those listed are available; consult your local Rockwell Automation sales office or Allen-Bradley distributor.
208V AC
| Current Rating | Hp | IP30 (Type 1) Vented Enclosed Non-Combination Controllers |
IP65 (Type 4) Enclosed Non-Combination Controllers |
IP54 (Type 12) Enclosed Non-Combination Controllers |
|||
| 200V AC 60 Hz | Cat. No. | Cat. No. | Cat. No. | ||||
| 24 | 1…5 | § | 150-B24AHD | Ø | 150-B24FHD | Ø | 150-B24JHD |
| 35 | 1…10 | § | 150-B35AHD | Ø | 150-B35FHD | Ø | 150-B35JHD |
| 54 | 1…15 | § | 150-B54AHD | Ø | 150-B54FHD | Ø | 150-B54JHD |
| 97 | 5…30 | 150-B97AHD | 150-B97FHD | 150-B97JHD | |||
| 135 | 5…40 | 150-B135AHD | 150-B135FHD | 150-B135JHD | |||
| 180 | 5…60 | 150-B180AHD | 150-B180FHD | 150-B180JHD | |||
| 240 | 5…75 | 150-B240AHD | 150-B240FHD | 150-B240JHD | |||
| 360 | 5…125 | 150-B360AHD | 150-B360FHD | 150-B360JHD | |||
| 500 | 5…150 | 150-B500AHD | 150-B500FHD | 150-B500JHD | |||
| 650 | 5…200 | 150-B650AHD | 150-B650FHD | 150-B650JHD | |||
| 720 | 5…250 | 150-B720AHD | 150-B720FHD | 150-B720JHD | |||
| 850 | 10…300 | 150-B850AHD | 150-B850FHD | 150-B850JHD | |||
| 1000 | 10…350 | 150-B1000AHD | 150-B1000FHD | 150-B1000JHD | |||
| § Includes internal circulating fan rather than enclosure ventilation. | |||||||
| Ø Includes an internal circulating fan instead of a bypass contactor. | |||||||
230V AC
| Current Rating | kWT | Hp | IP30 (Type 1) Vented Enclosed Non-Combination Controllers |
IP65 (Type 4) Enclosed Non-Combination Controllers |
IP54 (Type 12) Enclosed Non-Combination Controllers |
|||
| 230V AC 50 Hz | 230V AC 60 Hz | Cat. No. | Cat. No. | Cat. No. | ||||
| 24 | 5.5 | 1…5 | § | 150-B24AAD | Ø | 150-B24FAD | Ø | 150-B24JAD |
| 35 | 10 | 1…10 | § | 150-B35AAD | Ø | 150-B35FAD | Ø | 150-B35JAD |
| 54 | 15 | 1…15 | § | 150-B54AAD | Ø | 150-B54FAD | Ø | 150-B54JAD |
| 97 | 25 | 5…30 | 150-B97AAD | 150-B97FAD | 150-B97JAD | |||
| 135 | 37 | 5…40 | 150-B135AAD | 150-B135FAD | 150-B135JAD | |||
| 180 | 51 | 5…60 | 150-B180AAD | 150-B180FAD | 150-B180JAD | |||
| 240 | 75 | 5…75 | 150-B240AAD | 150-B240FAD | 150-B240JAD | |||
| 360 | 110 | 5…125 | 150-B360AAD | 150-B360FAD | 150-B360JAD | |||
| 500 | 150 | 5…150 | 150-B500AAD | 150-B500FAD | 150-B500JAD | |||
| 650 | 200 | 5…200 | 150-B650AAD | 150-B650FAD | 150-B650JAD | |||
| 720 | 220 | 5…250 | 150-B720AAD | 150-B720FAD | 150-B720JAD | |||
| 850 | 257 | 10…300 | 150-B850AAD | 150-B850FAD | 150-B850JAD | |||
| 1000 | 315 | 10…350 | 150-B1000AAD | 150-B1000FAD | 150-B1000JAD | |||
| T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater. | ||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | ||||||||
| Ø Includes an internal circulating fan instead of a bypass contactor. | ||||||||
460V AC
| Current Rating | kWT | Hp | IP30 (Type 1) Vented Enclosed Non-Combination Controllers |
IP65 (Type 4) Enclosed Non-Combination Controllers |
IP54 (Type 12) Enclosed Non-Combination Controllers |
|||
| 400V AC 50 Hz | 460V AC 60 Hz | Cat. No. | Cat. No. | Cat. No. | ||||
| 24 | 11 | 1…15 | § | 150-B24ABD | Ø | 150-B24FBD | Ø | 150-B24JBD |
| 35 | 18.5 | 1…25 | § | 150-B35ABD | Ø | 150-B35FBD | Ø | 150-B35JBD |
| 54 | 22 | 1…40 | § | 150-B54ABD | Ø | 150-B54FBD | Ø | 150-B54JBD |
| 97 | 45 | 5…75 | 150-B97ABD | 150-B97FBD | 150-B97JBD | |||
| 135 | 75 | 5…100 | 150-B135ABD | 150-B135FBD | 150-B135JBD | |||
| 180 | 90 | 5…150 | 150-B180ABD | 150-B180FBD | 150-B180JBD | |||
| 240 | 132 | 5…200 | 150-B240ABD | 150-B240FBD | 150-B240JBD | |||
| 360 | 200 | 5…300 | 150-B360ABD | 150-B360FBD | 150-B360JBD | |||
| 500 | 257 | 5…400 | 150-B500ABD | 150-B500FBD | 150-B500JBD | |||
| 650 | 355 | 5…500 | 150-B650ABD | 150-B650FBD | 150-B650JBD | |||
| 720 | 400 | 5…600 | 150-B720ABD | 150-B720FBD | 150-B720JBD | |||
| 850 | 475 | 10…700 | 150-B850ABD | 150-B850FBD | 150-B850JBD | |||
| 1000 | 530 | 10…800 | 150-B1000ABD | 150-B1000FBD | 150-B1000JBD | |||
| T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater. | ||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | ||||||||
| Ø Includes an internal circulating fan instead of a bypass contactor. | ||||||||
575V AC
| Current Rating (A) |
kWT | Hp | IP30 (Type 1) Vented Enclosed Non-Combination Controllers |
IP65 (Type 4) Enclosed Non-Combination Controllers |
IP54 (Type 12) Enclosed Non-Combination Controllers |
|||
| 500V AC 50 Hz | 575V AC 60 Hz | Cat. No. | Cat. No. | Cat. No. | ||||
| 24 | 15 | 1…20 | § | 150-B24ACD | Ø | 150-B24FCD | Ø | 150-B24JCD |
| 35 | 22 | 1…30 | § | 150-B35ACD | Ø | 150-B35FCD | Ø | 150-B35JCD |
| 54 | 37 | 1…50 | § | 150-B54ACD | Ø | 150-B54FCD | Ø | 150-B54JCD |
| 97 | 63 | 5…75 | 150-B97ACD | 150-B97FCD | 150-B97JCD | |||
| 135 | 90 | 5…125 | 150-B135ACD | 150-B135FCD | 150-B135JCD | |||
| 180 | 132 | 5…150 | 150-B180ACD | 150-B180FCD | 150-B180JCD | |||
| 240 | 160 | 5…250 | 150-B240ACD | 150-B240FCD | 150-B240JCD | |||
| 360 | 250 | 5…350 | 150-B360ACD | 150-B360FCD | 150-B360JCD | |||
| 500 | 355 | 5…500 | 150-B500ACD | 150-B500FCD | 150-B500JCD | |||
| 650 | 475 | 5…600 | 150-B650ACD | 150-B650FCD | 150-B650JCD | |||
| 720 | 500 | 5…700 | 150-B720ACD | 150-B720FCD | 150-B720JCD | |||
| 850 | 600 | 10…800 | 150-B850ACD | 150-B850FCD | 150-B850JCD | |||
| 1000 | 710 | 10…1000 | 150-B1000ACD | 150-B1000FCD | 150-B1000JCD | |||
| T The minimum rating is 0.7 kW for devices with current ratings of 54 A or less; 4 kW for devices rated 97…720 A; 7.5 kW for devices 850 A and greater. | ||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | ||||||||
| Ø Includes an internal circulating fan instead of a bypass contactor. | ||||||||
Combination Controllers — IP30 (Type 1) Vented Enclosed with Fusible Disconnect, IP54 (Type 12) Enclosed with Fusible Disconnect, IP30 (Type 1) Vented Enclosed with Circuit Breaker, IP54 (Type 12) Enclosed with Circuit Breaker
| Build a Catalog Number |
Includes a 120V control transformer and line and load terminations. The IP54 (Type 12) Enclosed Combination with Fusible Disconnect and IP54 (Type 12) Enclosed Combination with Circuit Breaker 97…1000 A controllers include a bypass contactor and a Bulletin 825 converter module. Enclosures other than those listed are available; consult your local Rockwell Automation sales office or Allen-Bradley distributor.
All Bulletin 153 numbers are supplied with thermal magnetic circuit breakers.
208V AC, 60 Hz
| Hp Range |
Controller Current Rating (A)z |
IP30 (Type 1) Vented Enclosed Combination Controllers with Fusible Disconnect |
IP54 (Type 12) Enclosed Combination Controllers with Fusible Disconnect |
IP30 (Type 1) Vented Enclosed Combination Controllers with Circuit Breaker |
IP54 (Type 12) Enclosed Combination Controllers with Circuit Breaker |
||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||||||
| 1…5 | 24 | § | 152H-B24AHD-39 | ª | 152H-B24JHD-39 | § | 153H-B24AHD-39 | ª | 153H-B24JHD-39 |
| 7-1/2 | 35 | § | 152H-B35AHD-40 | ª | 152H-B35JHD-40 | § | 153H-B35AHD-40 | ª | 153H-B35JHD-40 |
| 10 | 35 | § | 152H-B35AHD-41 | ª | 152H-B35JHD-41 | § | 153H-B35AHD-41 | ª | 153H-B35JHD-41 |
| 15 | 54 | § | 152H-B54AHD-42 | ª | 152H-B54JHD-42 | § | 153H-B54AHD-42 | ª | 153H-B54JHD-42 |
| 20 | 97 | 152H-B97AHD-43 | 152H-B97JHD-43 | 153H-B97AHD-43 | 153H-B97JHD-43 | ||||
| 25 | 97 | 152H-B97AHD-44 | 152H-B97JHD-44 | 153H-B97AHD-44 | 153H-B97JHD-44 | ||||
| 30 | 97 | 152H-B97AHD-45 | 152H-B97JHD-45 | 153H-B97AHD-45 | 153H-B97JHD-45 | ||||
| 40 | 135 | 152H-B135AHD-46 | 152H-B135JHD-46 | 153H-B135AHD-46 | 153H-B135JHD-46 | ||||
| 50 | 180 | 152H-B180AHD-47 | 152H-B180JHD-47 | 153H-B180AHD-47 | 153H-B180JHD-47 | ||||
| 60 | 180 | 152H-B180AHD-48 | 152H-B180JHD-48 | 153H-B180AHD-48 | 153H-B180JHD-48 | ||||
| 75 | 240 | 152H-B240AHD-49 | 152H-B240JHD-49 | 153H-B240AHD-49 | 153H-B240JHD-49 | ||||
| 100 | 360 | 152H-B360AHD-50 | 152H-B360JHD-50 | 153H-B360AHD-50 | 153H-B360JHD-50 | ||||
| 125 | 360 | 152H-B360AHD-51 | 152H-B360JHD-51 | 153H-B360AHD-51 | 153H-B360JHD-51 | ||||
| 150 | 500 | 152H-B500AHD-52 | 152H-B500JHD-52 | 153H-B500AHD-52 | 153H-B500JHD-52 | ||||
| 200 | 650 | 152H-B650AHD-54 | 152H-B650JHD-54 | 153H-B650AHD-54 | 153H-B650JHD-54 | ||||
| 250 | 720 | 152H-B720AHD-56 | 152H-B720JHD-56 | 153H-B720AHD-56 | 153H-B720JHD-56 | ||||
| 300 | 850 | 152H-B850AHD-57 | 152H-B850JHD-57 | 153H-B850AHD-57 | 153H-B850JHD-57 | ||||
| 350 | 1000 | 152H-B1000AHD-58 | 152H-B1000JHD-58 | 153H-B1000AHD-58 | 153H-B1000JHD-58 | ||||
| z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | |||||||||
| ª Supplied without bypass contactor or converter module. | |||||||||
230V AC, 60 Hz
| Hp Range |
Controller Current Rating (A)z |
IP30 (Type 1) Vented Enclosed Combination Controllers with Fusible Disconnect |
IP54 (Type 12) Enclosed Combination Controllers with Fusible Disconnect |
IP30 (Type 1) Vented Enclosed Combination Controllers with Circuit Breaker |
IP54 (Type 12) Enclosed Combination Controllers with Circuit Breaker |
||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||||||
| 1…7-1/2 | 24 | § | 152H-B24AAD-40 | ª | 152H-B24JAD-40 | § | 153H-B24AAD-40 | ª | 153H-B24JAD-40 |
| 10 | 35 | § | 152H-B35AAD-41 | ª | 152H-B35JAD-41 | § | 153H-B35AAD-41 | ª | 153H-B35JAD-41 |
| 15 | 54 | § | 152H-B54AAD-42 | ª | 152H-B54JAD-42 | § | 153H-B54AAD-42 | ª | 153H-B54JAD-42 |
| 20 | 54 | § | 152H-B54AAD-43 | ª | 152H-B54JAD-43 | § | 153H-B54AAD-43 | ª | 153H-B54JAD-43 |
| 25 | 97 | 152H-B97AAD-44 | 152H-B97JAD-44 | 153H-B97AAD-44 | 153H-B97JAD-44 | ||||
| 30 | 97 | 152H-B97AAD-45 | 152H-B97JAD-45 | 153H-B97AAD-45 | 153H-B97JAD-45 | ||||
| 40 | 135 | 152H-B135AAD-46 | 152H-B135JAD-46 | 153H-B135AAD-46 | 153H-B135JAD-46 | ||||
| 50 | 135 | 152H-B135AAD-47 | 152H-B135JAD-47 | 153H-B135AAD-47 | 153H-B135JAD-47 | ||||
| 60 | 180 | 152H-B180AAD-48 | 152H-B180JAD-48 | 153H-B180AAD-48 | 153H-B180JAD-48 | ||||
| 75 | 240 | 152H-B240AAD-49 | 152H-B240JAD-49 | 153H-B240AAD-49 | 153H-B240JAD-49 | ||||
| 100 | 360 | 152H-B360AAD-50 | 152H-B360JAD-50 | 153H-B360AAD-50 | 153H-B360JAD-50 | ||||
| 125 | 360 | 152H-B360AAD-51 | 152H-B360JAD-51 | 153H-B360AAD-51 | 153H-B360JAD-51 | ||||
| 150 | 360 | 152H-B360AAD-52 | 152H-B360JAD-52 | 153H-B360AAD-52 | 153H-B360JAD-52 | ||||
| 200 | 500 | 152H-B500AAD-54 | 152H-B500JAD-54 | 153H-B500AAD-54 | 153H-B500JAD-54 | ||||
| 250 | 650 | 152H-B650AAD-56 | 152H-B650JAD-56 | 153H-B650AAD-56 | 153H-B650JAD-56 | ||||
| 300 | 720 | 152H-B720AAD-57 | 152H-B720JAD-57 | 153H-B720AAD-57 | 153H-B720JAD-57 | ||||
| 350 | 850 | 152H-B850AAD-58 | 152H-B850JAD-58 | 153H-B850AAD-58 | 153H-B850JAD-58 | ||||
| 400 | 1000 | 152H-B1000AAD-59 | 152H-B1000JAD-59 | 153H-B1000AAD-59 | 153H-B1000JAD-59 | ||||
| z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | |||||||||
| ª Supplied without bypass contactor or converter module. | |||||||||
460V AC, 60 Hz
| Hp Range |
Controller Current Rating (A)z |
IP30 (Type 1) Vented Enclosed Combination Controllers with Fusible Disconnect |
IP54 (Type 12) Enclosed Combination Controllers with Fusible Disconnect |
IP30 (Type 1) Vented Enclosed Combination Controllers with Circuit Breaker |
IP54 (Type 12) Enclosed Combination Controllers with Circuit Breaker |
||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||||||
| 1…15 | 24 | § | 152H-B24ABD-42 | ª | 152H-B24JBD-42 | § | 153H-B24ABD-42 | ª | 153H-B24JBD-42 |
| 20 | 35 | § | 152H-B35ABD-43 | ª | 152H-B35JBD-43 | § | 153H-B35ABD-43 | ª | 153H-B35JBD-43 |
| 25 | 35 | § | 152H-B35ABD-44 | ª | 152H-B35JBD-44 | § | 153H-B35ABD-44 | ª | 153H-B35JBD-44 |
| 30 | 54 | § | 152H-B54ABD-45 | ª | 152H-B54JBD-45 | § | 153H-B54ABD-45 | ª | 153H-B54JBD-45 |
| 40 | 54 | § | 152H-B54ABD-46 | ª | 152H-B54JBD-46 | § | 153H-B54ABD-46 | ª | 153H-B54JBD-46 |
| 50 | 97 | 152H-B97ABD-47 | 152H-B97JBD-47 | 153H-B97ABD-47 | 153H-B97JBD-47 | ||||
| 60 | 97 | 152H-B97ABD-48 | 152H-B97JBD-48 | 153H-B97ABD-48 | 153H-B97JBD-48 | ||||
| 75 | 97 | 152H-B97ABD-49 | 152H-B97JBD-49 | 153H-B97ABD-49 | 153H-B97JBD-49 | ||||
| 100 | 135 | 152H-B135ABD-50 | 152H-B135JBD-50 | 153H-B135ABD-50 | 153H-B135JBD-50 | ||||
| 125 | 180 | 152H-B180ABD-51 | 152H-B180JBD-51 | 153H-B180ABD-51 | 153H-B180JBD-51 | ||||
| 150 | 180 | 152H-B180ABD-52 | 152H-B180JBD-52 | 153H-B180ABD-52 | 153H-B180JBD-52 | ||||
| 200 | 240 | 152H-B240ABD-54 | 152H-B240JBD-54 | 153H-B240ABD-54 | 153H-B240JBD-54 | ||||
| 250 | 360 | 152H-B360ABD-56 | 152H-B360JBD-56 | 153H-B360ABD-56 | 153H-B360JBD-56 | ||||
| 300 | 360 | 152H-B360ABD-57 | 152H-B360JBD-57 | 153H-B360ABD-57 | 153H-B360JBD-57 | ||||
| 350 | 500 | 152H-B500ABD-58 | 152H-B500JBD-58 | 153H-B500ABD-58 | 153H-B500JBD-58 | ||||
| 400 | 500 | 152H-B500ABD-59 | 152H-B500JBD-59 | 153H-B500ABD-59 | 153H-B500JBD-59 | ||||
| 450 | 650 | 152H-B650ABD-60 | 152H-B650JBD-60 | 153H-B650ABD-60 | 153H-B650JBD-60 | ||||
| 500 | 650 | 152H-B650ABD-61 | 152H-B650JBD-61 | 153H-B650ABD-61 | 153H-B650JBD-61 | ||||
| 600 | 720 | 152H-B720ABD-62 | 152H-B720JBD-62 | 153H-B720ABD-62 | 153H-B720JBD-62 | ||||
| 700 | 850 | 152H-B850ABD-63 | 152H-B850JBD-63 | 153H-B850ABD-63 | 153H-B850JBD-63 | ||||
| 800 | 1000 | 152H-B1000ABD-65 | 152H-B1000JBD-65 | 153H-B1000ABD-65 | 153H-B1000JBD-65 | ||||
| z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Allen-Bradley distributor. | |||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | |||||||||
| ª Supplied without bypass contactor or converter module. | |||||||||
575V AC, 60 Hz
| Hp Range |
Controller Current Rating (A)z |
IP30 (Type 1) Vented Enclosed Combination Controllers with Fusible Disconnect |
IP54 (Type 12) Enclosed Combination Controllers with Fusible Disconnect |
IP30 (Type 1) Vented Enclosed Combination Controllers with Circuit Breaker |
IP54 (Type 12) Enclosed Combination Controllers with Circuit Breaker |
||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | ||||||
| 1…20 | 24 | § | 152H-B24ACD-43 | ª | 152H-B24JCD-43 | § | 153H-B24ACD-43 | ª | 153H-B24JCD-43 |
| 25 | 35 | § | 152H-B35ACD-44 | ª | 152H-B35JCD-44 | § | 153H-B35ACD-44 | ª | 153H-B35JCD-44 |
| 30 | 35 | § | 152H-B35ACD-45 | ª | 152H-B35JCD-45 | § | 153H-B35ACD-45 | ª | 153H-B35JCD-45 |
| 40 | 54 | § | 152H-B54ACD-46 | ª | 152H-B54JCD-46 | § | 153H-B54ACD-46 | ª | 153H-B54JCD-46 |
| 50 | 54 | § | 152H-B54ACD-47 | ª | 152H-B54JCD-47 | 153H-B54ACD-47 | ª | 153H-B54JCD-47 | |
| 60 | 97 | 152H-B97ACD-48 | 152H-B97JCD-48 | 153H-B97ACD-48 | 153H-B97JCD-48 | ||||
| 75 | 97 | 152H-B97ACD-49 | 152H-B97JCD-49 | 153H-B97ACD-49 | 153H-B97JCD-49 | ||||
| 100 | 135 | 152H-B135ACD-50 | 152H-B135JCD-50 | 153H-B135ACD-50 | 153H-B135JCD-50 | ||||
| 125 | 135 | 152H-B135ACD-51 | 152H-B135JCD-51 | 153H-B135ACD-51 | 153H-B135JCD-51 | ||||
| 150 | 180 | 152H-B180ACD-52 | 152H-B180JCD-52 | 153H-B180ACD-52 | 153H-B180JCD-52 | ||||
| 200 | 240 | 152H-B240ACD-54 | 152H-B240JCD-54 | 153H-B240ACD-54 | 153H-B240JCD-54 | ||||
| 250 | 240 | 152H-B240ACD-56 | 152H-B240JCD-56 | 153H-B240ACD-56 | 153H-B240JCD-56 | ||||
| 300 | 360 | 152H-B360ACD-57 | 152H-B360JCD-57 | 153H-B360ACD-57 | 153H-B360JCD-57 | ||||
| 350 | 360 | 152H-B360ACD-58 | 152H-B360JCD-58 | 153H-B360ACD-58 | 153H-B360JCD-58 | ||||
| 400 | 500 | 152H-B500ACD-59 | 152H-B500JCD-59 | 153H-B500ACD-59 | 153H-B500JCD-59 | ||||
| 450 | 500 | 152H-B500ACD-60 | 152H-B500JCD-60 | 153H-B500ACD-60 | 153H-B500JCD-60 | ||||
| 500 | 500 | 152H-B500ACD-61 | 152H-B500JCD-61 | 153H-B500ACD-61 | 153H-B500JCD-61 | ||||
| 600 | 650 | 152H-B650ACD-62 | 152H-B650JCD-62 | 153H-B650ACD-62 | 153H-B650JCD-62 | ||||
| 700 | 720 | 152H-B720ACD-63 | 152H-B720JCD-63 | 153H-B720ACD-63 | 153H-B720JCD-63 | ||||
| 800 | 850 | 152H-B850ACD-65 | 152H-B850JCD-65 | 153H-B850ACD-65 | 153H-B850JCD-65 | ||||
| 1000 | 1000 | 152H-B1000ACD-67 | 152H-B1000JCD-67 | 153H-B1000ACD-67 | 153H-B1000JCD-67 | ||||
| z The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | |||||||||
| § Includes internal circulating fan rather than enclosure ventilation. | |||||||||
| ª Supplied without bypass contactor or converter module. | |||||||||
Options
Open Type Options (only one selection allowed)
| Option | Description | Cat. No. Modification |
| Soft Stop | Provides a ramp down time of 0…60 s for applications which require an extended coast-to-rest. | A§ |
| Pump Control | Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s, and stopping time is adjustable from 0…120 s. | B§ |
| Preset Slow Speed | Provides preset slow speeds for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load motor current. | C§ |
| SMB Smart Motor Braking | Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of the motors full-load current rating. | D§ |
| Accu-Stop | Provides stopping control for general positioning or to minimize jogging to stop. A 3-phase braking current is applied to the motor (adjustable from 0…400% of full-load current) until it reaches a preset slow speed (either 7% or 15% of rated motor speed). The motor is held at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Slow speed current is adjustable from 0…450% of full-load current. | E§ |
| Slow Speed with Braking | Provides a preset slow speed for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load current. Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of full-load motor current. |
F§ |
§ Add the designated letter to the end of the cat. no. Example: To add the Pump Control option: Cat. No. 150-B24NBDB.
Enclosed Options
| Option | Description | Cat. No. Modification |
|
| Soft Stop | Provides a ramp down time of 0…60 s for applications that require an extended coast-to-rest. | -A¬ | |
| Pump Control | Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s and stopping time is adjustable from 0…120 s. | -B¬ | |
| 24 A | |||
| 35 A | |||
| 54 A | |||
| 97 A | |||
| 135 A | |||
| 180 A | |||
| 240 A | |||
| 360 A | |||
| 500 A | |||
| 650 A | |||
| 720 A | |||
| 850 A | |||
| 1000 A | |||
| Push Buttons | Start-Stop Push Button | -1 | |
| Start-Stop Push Button with H-O-A Selector Switch | -1F | ||
| Soft Stop Push ButtonT | -1XA | ||
| Pump Stop Push ButtonT | -1XB | ||
| Brake Push ButtonT | -1XD | ||
| Selector Switch | Hand-Off-Auto Selector Switch | -3 | |
| SMC-Off-Bypass Selector Switch | -3B | ||
| Pilot Light | Transformer Pilot Light (Red or Green Lens) | -4_ | |
| Push-To-Test Pilot Light (Red Lens) | -5_ | ||
| Control Circuit Transformer | Control Circuit Transformer (fused primary and secondary) | -6P | |
| SCR Fusing | Fast Acting Current Limiting SCR Fusing | for 24 A unit | -SCR |
| Fast Acting Current Limiting SCR Fusing | for 35 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 54 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 97…135 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 180 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 240 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 360 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 500 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 650…720 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 850 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 1000 A unit | ||
| Door-Mounted Human Interface Module |
Programmer Only (Type 1) | -HAP | |
| Programmer Only (Type 4/12) | -HJP | ||
| Digital Contral Panel (Type 1) | -HA2 | ||
| Digital Control Panel (Type 4/12) | -HJ2 | ||
| Communication Module | Remote I/O | -GD1 | |
| RS-232/422/485, DH485 | -GD2 | ||
| DeviceNet™ Network | -GK5 | ||
| Enhanced DeviceNet | -GU6 | ||
| ControlNet | -CN1 | ||
| ¬ Add the designated letter to the end of the Cat. No. For example, to add the pump control option Cat. No. 152H-B180JBDB-51 . | |||
| T Option push buttons are available only when the corresponding option module is selected. For example, Cat. No. 150-A24JBDA-1XA. | |||
| Specify pilot light lens color. Options: Red, Green. | |||
| Option | Description | Cat. No. Modification |
|
| Protective Module¬ | 480V Line Side Protective Module | 24…54 A | -8L |
| 480V Line Side Protective Module | 97…360 A | ||
| 600V Line Side Protective Module | 24…54 A | ||
| 600V Line Side Protective Module | 97…360 A | ||
| 480V Load Side Protective Module | 24…54 A | -8M | |
| 480V Load Side Protective Module | 97…360 A | ||
| 600V Load Side Protective Module | 24…54 A | ||
| 600V Load Side Protective Module | 97…360 A | ||
| 480V Both Line and Load Side Protective Module | 24…54 A | -8B | |
| 480V Both Line and Load Side Protective Module | 97…360 A | ||
| 600V Both Line and Load Side Protective Module | 24…54 A | ||
| 600V Both Line and Load Side Protective Module | 97…360 A | ||
| Auxiliary ContactsT | N.O. auxiliary contacts | for 24…240 A | -90 |
| N.O. auxiliary contacts | for 360…1000 A | ||
| N.C. auxiliary contacts | for 24…240 A | -91 | |
| N.C. auxiliary contacts | for 360…1000 A | ||
| 1 N.O and 1 N.C. auxiliary contacts | for 24…240 A | -901 | |
| 1 N.O. and 1 N.C. auxiliary contacts | for 360…1000 A | ||
| Unwired Control RelaysØ | Bulletin 700CF 4-pole relay 2 N.O. and 2 N.C. | -89F22 | |
| Bulletin 700CF 4-pole relay 3 N.O. and 1 N.C. | -89F31 | ||
| Bulletin 700CF 4-pole relay 4 N.O. | -89F40 | ||
| Disconnect Auxiliaryz | N.O. disconnect auxiliary mounted on operating mechanism | -98 | |
| N.C. disconnect auxiliary mounted on operating mechanism | -99 | ||
| Circuit Breaker Disconnect Auxilaryª |
Internal N.O. circuit breaker auxiliary | -98X | |
| Internal N.C. circuit breaker auxiiary | -99X | ||
| Service Entrance Label | Service Entrance Label | 24…650 A | -SEL |
| 720…1000 A | |||
| UL Label | UL Label | -UL | |
| NEMA Bypass Contactor§ | NEMA Bypass | for 24…97 A unit | -NB |
| NEMA Bypass | for 135…180 A unit | ||
| NEMA Bypass | for 240 A unit | ||
| NEMA Bypass | for 360 A unit | ||
| NEMA Bypass | for 500 A unit | ||
| NEMA Isolation Contactor§ | NEMA Isolation | for 24…97 A unit | -NI |
| NEMA Isolation | for 135…180 A unit | ||
| NEMA Isolation | for 240 A unit | ||
| NEMA Isolation | for 360 A unit | ||
| NEMA Isolation | for 500 A unit | ||
| ¬ Line and Load Side Protective Modules are standard on 500…1000 A units. | |||
| T Available only with enclosed Bulletin 150, 152 and 153 devices with bypass contactor. Maximum of four (4) auxiliary contacts. | |||
| § Thermal overload for Bulletin 150 enclosed controllers only. Overload is standard on Bulletins 152 and 153. | |||
| Ø Instantaneous auxiliary contacts on Bulletin 700CF relays are non-convertible. | |||
| z Available only with Bulletin 152 and 153 devices. Maximum of two (2) disconnect auxiliaries. | |||
| ª Available only with Bulletin 153 devices. Maximum of two (2) disconnect auxiliaries. | |||
| v Order to be released to manufacturing upon release of signed print approval drawings. | |||
| § 650, 720, 850, and 1000 A units currently use a NEMA contactor. | |||
Accessories
Protective Modules¬ §
Terminal Lug Kits (97…1000 A)
IEC Terminal Covers
Converter Modules¬
Specifications
| Functional Design Specifications | |||
| Standard Features | Installation | Power Wiring | The SMC Dialog Plus Controller can be wired with or without an isolation contactor. Bypass contactors can be employed after the controller has brought the motor to full speed. |
| Control Wiring | 2- and 3-wire control for a wide variety of applications. | ||
| Setup | Keypad | The SMC Dialog Plus Controller is configured with the front keypad and backlit LCD display. | |
| Software | Parameter values can be downloaded to the SMC Dialog Plus Controller with DriveTools programming software and the Cat. No. 1203-GD2 communication module. | ||
| Communications | One serial port provided for connection to optional human interface and communication modules. | ||
| Starting Modes | Soft start with selectable kickstart, current limit, dual ramp, and full voltage in one unit. | ||
| Protection and Diagnostics | Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. | ||
| Metering | Amps, volts, kW, kWH, elapsed time, power factor, motor thermal capacity usage. | ||
| Status Indication | Stopped, ramping, stopping, at speed, and fault. | ||
| Auxiliary Contacts | (1) Single-pole double-throw contact programmable as normal or up-to-speed; one programmable as normal or fault. | ||
| Optional Features | Soft Stop | Extended coast-to-rest to minimize load shifting. Ramp down time is adjustable from 0…60 s. | |
| Pump Control | Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting time is adjustable from 0…30 s. Stopping time is adjustable from 0…120 s. | ||
| Preset Slow Speed | Enables the operator to position material. The preset slow speed can be set for low (7% of base speed), high (15% of base speed), reverse low (10% of base speed) or reverse high (20% of base speed). | ||
| SMB Smart Motor Braking | Provides motor braking without additional equipment for applications that require the motor to stop quickly. Braking current is adjustable from 0…400% of the motors full-load current rating. | ||
| Accu-Stop/Slow Speed with Braking |
Combines Smart Motor Braking and Preset Slow Speed. Braking current is adjustable from 0…400% of full-load current. Slow speed can be set for either Low (7% of base speed) or High (15% of base speed). |
||
| Electrical Ratings | ||||
| UL/CSA/NEMA | IEC | |||
| Power Circuit | Rated Operation Voltage | 200…480V AC 200…600V AC (15%, +10%) |
200…415V 200…500V |
|
| Rated Insulation Voltage | N/A | 500V | ||
| Rated Impulse Voltage | N/A | 6000V | ||
| Dielectric Withstand | 2200V AC | 2500V | ||
| Repetitive Peak Inverse Voltage Rating | 200…480V AC: 1400V 200…600V AC: 1600V |
200…415V: 1400V 200…500V: 1600V |
||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Utilization Category | MG 1 | AC-53a | ||
| Protection Against Electrical Shock | N/A | IP00 (open device) | ||
| DV/DT Protection | RC Snubber Network | |||
| Transient Protection | Metal Oxide Varistors: 220 Joules @ 24…360 A 220 Joules @ 480V, 500…1000 A 300 Joules @ 600V, 500…1000 A |
|||
| Short-Circuit Protection |
SCPD Performance | Type 1 | ||
| SCPD List | Maximum Fuse or Circuit Breaker (A): | |||
| Device Operational Current Rating (A) | 24 | 80 | ||
| 35 | 125 | |||
| 54 | 200 | |||
| 97 | 350 | |||
| 135 | 500 | |||
| 180 | 600 | |||
| 240 | 700 | |||
| 360 | 1000 | |||
| 500 | 1200 | |||
| 650 | 1600 | |||
| 720 | 2000 | |||
| 850 | 2500 | |||
| 1000 | 3000 | |||
| Control Circuit | Rated Operational Voltage | 100…240V AC 24V AC 24V DC |
100…240V 24V 24V DC |
|
| Rated Insulation Voltage | N/A | 240V | ||
| Rated Impulse Voltage | N/A | 3000V | ||
| Dielectric Withstand | 1600V AC | 2000V | ||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Protection Against Electric Shock | N/A | IP20 | ||
| Power Requirements |
Control Module | 40 VA | ||
| Heatsink Fan(s) (A)¬ | 24 | — | ||
| 35 | — | |||
| 54 | — | |||
| 97 | 45 VA | |||
| 135 | 45 VA | |||
| 180 | 45 VA | |||
| 240 | 45 VA | |||
| 360 | 45 VA | |||
| 500 | 145 VA | |||
| 650 | 320 VA | |||
| 720 | 320 VA | |||
| 850 | 320 VA | |||
| 1000 | 320 VA | |||
| ¬ For devices rated 24…500 A, heatsink fans can be powered by either 110/120V AC or 220/240V AC. For devices rated 650…1000 A, heatsink fans can only be powered by 110/120V AC. | ||||
| Electrical Ratings, Continued | ||||
| UL/CSA/NEMA | IEC | |||
| Maximum Heat Dissipation (Watts) |
Controller Rating (A) |
24 | 110 | |
| 35 | 150 | |||
| 54 | 200 | |||
| 97 | 285 | |||
| 135 | 490 | |||
| 180 | 660 | |||
| 240 | 935 | |||
| 360 | 1170 | |||
| 500 | 1400 | |||
| 650 | 2025 | |||
| 720 | 2250 | |||
| 850 | 2400 | |||
| 1000 | 2760 | |||
| Auxiliary Contacts |
Rated Operation Voltage | 240V AC | 240V | |
| Rated Insulation Voltage | N/A | 240V | ||
| Dielectric Withstand | 1600V AC | 2000V | ||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Utilization Category | B300 (terminals 18…19) C300 (terminals 18…20) C300 (terminals 29…30) |
AC-15 | ||
| SCPD Performance | Type 2 | |||
| SCPD List | Class CC 8 A @ 1000 A Available Fault Current | |||
| Environmental | ||||
| Operating Temperature Range | 0…+50 °C (32…122 °F) (open) 0…+40 °C (32…104 °F) (enclosed) |
|||
| Storage and Transportation Temperature Range | 20…+75 °C | |||
| 2000 m (6560 ft) | ||||
| Humidity | 5…95% (non-condensing) | |||
| Pollution Degree | 2 | |||
| Mechanical | ||||
| Resistance to Vibration |
Operational Non-Operational |
1.0 G Peak, 0.006 in. displacement 2.5 G, 0.015 in. displacement |
||
| Resistance to Shock |
Operational Non-Operational |
15 G 30 G |
||
| Construction | Power Poles |
Thermoset Moldings Heatsink hockey puck thyristor |
24…135 A 180…1000 A |
|
| Control Modules | Thermoset and Thermoplastic Moldings | |||
| Metal Parts | Anodized Aluminum, Plated Brass, Copper, or Painted Steel | |||
| Terminals | Power Terminals |
24…54 A | 6.0 mm hole with clamp screw | |
| 97 and 135 A | One 11.5 mm (0.453 in.) diameter hole each | |||
| 180…360 A | One 10.5 mm (0.413 in.) diameter hole each | |||
| 500 A | Two 13.5 mm (0.531 in.) diameter holes each | |||
| 650 and 720 A | Three 13.1 mm (0.515 in.) diameter holes each | |||
| 850 and 1000 A | Six 13.1 mm (0.515 in.) diameter holes each | |||
| Power Terminal Markings | NEMA, CENELEC EN50 012 | |||
| Control Terminals | M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate | |||
| Other | ||||
| EMC Emission Levels |
Conducted Radio Frequency Emissions Radiated Emissions |
Class A Class A |
||
| EMC Immunity Levels |
Electrostatic Discharge | 8 kV Air Discharge | ||
| Radio Frequency Electromagnetic Field | Per IEC 947-4-2 | |||
| Fast Transient | Per IEC 947-4-2 | |||
| Surge Transient | Per IEC 947-4-2 | |||
| Overload Characteristics |
Current Range | 1.0…999.9 A | ||
| Trip Classes | 10, 15, 20, and 30 | |||
| Trip Current Rating | 120% of Motor FLC | |||
| Number of Poles | 3 | |||
Specifications, Continued
Fuse Clip Sizing and Type for Fusible Combination Controllers¬ T
| Horsepower @ 480V | Fuse Clip Size/Type | Fuse Size Range [A] |
| 15 | 30 A/Class J | 0…30 |
| 20 | 60 A/Class J | 31…60 |
| 25 | 60 A/Class J | 31…60 |
| 30 | 60 A/Class J | 31…60 |
| 40 | 100 A/Class J | 61…100 |
| 50 | 100 A/Class J | 61…100 |
| 60 | 200 A/Class J | 101…200 |
| 75 | 200 A/Class J | 101…200 |
| 100 | 200 A/Class J | 101…200 |
| 125 | 400 A/Class J | 201…400 |
| 150 | 400 A/Class J | 201…400 |
| 200 | 400 A/Class J | 201…400 |
| 250 | 400 A/Class J | 401…600 |
| 300 | 600 A/Class J | 401…600 |
| 350 | 600 A/Class J | 401…600 |
| 400 | 1200 A/Class L | 601…1600 |
| 450 | 1200 A/Class L | 601…1600 |
| 500 | 1200 A/Class L | 601…1600 |
| 600 | 1200 A/Class L | 601…1600 |
| 700 | 1200 A/Class L | 601…1600 |
| 800 | 1200 A/Class L | 601…1600 |
| ¬ Consult NEC Handbook for proper fuse sizing guidelines. | ||
| T Optional fuse clip sizes and types are available upon request. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||
Circuit Breaker Sizes and Rating Plug Sizes
| Horsepower @ 480V | Circuit Breaker Size [A]/ Rating Plug Size [A] |
Interrupting Rating in Symmetrical Amps @ 480V |
| 15 | 150/50 | 14 000 |
| 20 | 150/50 | 14 000 |
| 25 | 150/60 | 14 000 |
| 30 | 150/70 | 14 000 |
| 40 | 150/100 | 14 000 |
| 50 | 150/125 | 14 000 |
| 60 | 250/150 | 25 000 |
| 75 | 250/175 | 25 000 |
| 100 | 250/225 | 25 000 |
| 125 | 250/250 | 25 000 |
| 150 | 400/300 | 35 000 |
| 200 | 400/400 | 35 000 |
| 250 | 600/500 | 35 000 |
| 300 | 600/600 | 35 000 |
| 350 | 800/800 | 35 000 |
| 400 | 800/800 | 50 000 |
| 450 | 1200/1000 | 50 000 |
| 500 | 1200/1200 | 50 000 |
| 600 | 1200/1200 | 50 000 |
| 700 | 2000/1600 | 65 000 |
| 800 | 2000/2000 | 65 000 |
| For higher interrupting ratings, consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||
Approximate Dimensions
Approximate Dimensions and Shipping Weights
Open Type Controllers
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
| Controller Rating [A] |
Height | Width | Depth | Weight |
| 24 | 180 (7.09) |
154 (6.06) |
185 (7.29) |
4.5 kg (10 lbs) |
| 35 | 240 (9.45) |
214 (8.43) |
195 (7.68) |
6.8 kg (15 lbs) |
| 54 | 290 (11.42) |
244 (9.61) |
225 (8.86) |
11.3 kg (25 lbs) |
| 97 | 336 (13.23) |
248 (9.77) |
256 (10.09) |
10.4 kg (23 lbs) |
| 135 | 336 (13.23) |
248 (9.77) |
256 (10.09) |
11.8 kg (26 lbs) |
| 180 | 560 (22.06) |
273 (10.75) |
294 (11.58) |
25 kg (55 lbs) |
| 240 | 560 (22.06) |
273 (10.75) |
294 (11.58) |
30 kg (65 lbs) |
| 360 | 560 (22.06) |
273 (10.75) |
294 (11.58) |
30 kg (65 lbs) |
| 500 | 588 (23.17) |
508 (20.00) |
311 (12.23) |
40.8 kg (90 lbs) |
| 650…1000 | 1524 (60.0) |
813 (32.00) |
402 (15.83) |
167.8 kg (370 lbs) |
Enclosed Type Controllers
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes. All dimensions are subject to change.
Factory-installed options may affect enclosure size requirements.
Exact dimensions can be obtained after order entry. Consult your local Rockwell Automation sales office or Allen-Bradley distributor.
|
| Controller Rating [A] |
A | J | |||||||
| IP30 (Type 1) | IP54 (Type 12) | IP65 (Type 4) | |||||||
| B Height | A Width | C Depth | B Height | A Width | C Depth | B Height | A Width | C Depth | |
| Non-Combination Controller | |||||||||
| 24 | 610 (24) | 406 (16) | 229 (9) | 610 (24) | 406 (16) | 229 (9) | 610 (24) | 406 (16) | 229 (9) |
| 35 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 54 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 97 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 135 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 180 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 240 | 965 (38) | 762 (30) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) |
| 360 | 1295 (51) | 914 (36) | 356 (14) | 1524 (60) | 914 (36) | 356 (14) | 1524 (60) | 914 (36) | 356 (14) |
| 500 | 1524 (60) | 914 (36) | 356 (14) | 2286 (90) | 889 (35) | 508 (20) | 2134 (90) | 1016 (35) | 457 (20) |
| 650 | 2286 (90) | 889 (35) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) |
| 720 | 2286 (90) | 889 (35) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) |
| 850 | 2286 (90) | 889 (35) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) |
| 1000 | 2286 (90) | 889 (35) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) | 2286 (90) | 1778 (60) | 508 (20) |
| Combination Controllers with Fusible Disconnect | |||||||||
| 24 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 35 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 54 (60 A Disconnect) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 54 (100 A Disconnect) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 97 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 135 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 180 | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) |
| 240 | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) |
| 360 | 1524 (60) | 965 (38) | 356 (15) | 1524 (60) | 965 (38) | 356 (15) | 1524 (60) | 965 (38) | 356 (15) |
| 500 (600 A Disconnect) | 2134 (84) | 1016 (40) | 457 (18) | 2134 (84) | 1016 (40) | 457 (18) | 2134 (84) | 1016 (40) | 457 (18) |
| 500 (1200 A Disconnect) | 2286 (90) | 1143 (55) | 508 (20) | 2286 (90) | 1270 (55) | 508 (20) | 2286 (90) | 1778 (55) | 508 (20) |
| 650 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 1778 (55) | 508 (20) | 2286 (90) | 1778 (55) | 508 (20) |
| 720 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 1778 (55) | 508 (20) | 2286 (90) | 1778 (55) | 508 (20) |
| 850 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 2667 (95) | 508 (20) | 2286 (90) | 2667 (95) | 508 (20) |
| 1000 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 2667 (95) | 508 (20) | 2286 (90) | 2667 (95) | 508 (20) |
| Combination Controllers with Circuit Breaker | |||||||||
| 24 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 35 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 54 | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) | 762 (30) | 610 (24) | 305 (12) |
| 97 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 135 | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) | 965 (38) | 762 (30) | 356 (14) |
| 180 | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) |
| 240 | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) | 1295 (51) | 914 (36) | 356 (14) |
| 360 | 1524 (60) | 965 (38) | 356 (14) | 1524 (60) | 965 (38) | 356 (14) | 1524 (60) | 965 (38) | 356 (14) |
| 500 | 2134 (90) | 1016 (35) | 457 (20) | 2134 (90) | 1016 (35) | 457 (20) | 2134 (90) | 1016 (35) | 457 (20) |
| 650 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 1778 (50) | 508 (20) | 2286 (90) | 1778 (50) | 508 (20) |
| 720 | 2286 (90) | 1397 (55) | 508 (20) | 2286 (90) | 1778 (50) | 508 (20) | 2286 (90) | 1778 (50) | 508 (20) |
| 850 | 2286 (90) | 1778 (55) | 508 (20) | 2286 (90) | 2667 (65) | 508 (20) | 2286 (90) | 2667 (65) | 508 (20) |
| 1000 | 2286 (90) | 1778 (55) | 508 (20) | 2286 (90) | 2667 (65) | 508 (20) | 2286 (90) | 2667 (65) | 508 (20) |