Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Soft Starters > SMC™ Dialog Plus Smart Motor Controller
SMC™ Dialog Plus Smart Motor Controller
| Introduction | Standards Compliance and Certifications | Modes of Operation | Cat. No. Explanation | Product Selection |
| Options | Accessories | Specifications | Approximate Dimensions |
Open Type Options (only one selection allowed)
| Option | Description | Cat. No. Modification |
| Soft Stop | Provides a ramp down time of 0…60 s for applications which require an extended coast-to-rest. | A§ |
| Pump Control | Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s, and stopping time is adjustable from 0…120 s. | B§ |
| Preset Slow Speed | Provides preset slow speeds for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load motor current. | C§ |
| SMB Smart Motor Braking | Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of the motors full-load current rating. | D§ |
| Accu-Stop | Provides stopping control for general positioning or to minimize jogging to stop. A 3-phase braking current is applied to the motor (adjustable from 0…400% of full-load current) until it reaches a preset slow speed (either 7% or 15% of rated motor speed). The motor is held at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Slow speed current is adjustable from 0…450% of full-load current. | E§ |
| Slow Speed with Braking | Provides a preset slow speed for positioning or alignment applications. Preset speeds can be selected at either 7% or 15% of rated motor speed, with adjustable slow speed current from 0…450% of full-load current. Provides a microprocessor-based braking system that applies 3-phase braking current to a standard squirrel-cage induction motor. The strength of the braking current is adjustable from 0…400% of full-load motor current. |
F§ |
§ Add the designated letter to the end of the cat. no. Example: To add the Pump Control option: Cat. No. 150-B24NBDB.
Enclosed Options
| Option | Description | Cat. No. Modification |
|
| Soft Stop | Provides a ramp down time of 0…60 s for applications that require an extended coast-to-rest. | -A¬ | |
| Pump Control | Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 0…30 s and stopping time is adjustable from 0…120 s. | -B¬ | |
| 24 A | |||
| 35 A | |||
| 54 A | |||
| 97 A | |||
| 135 A | |||
| 180 A | |||
| 240 A | |||
| 360 A | |||
| 500 A | |||
| 650 A | |||
| 720 A | |||
| 850 A | |||
| 1000 A | |||
| Push Buttons | Start-Stop Push Button | -1 | |
| Start-Stop Push Button with H-O-A Selector Switch | -1F | ||
| Soft Stop Push ButtonT | -1XA | ||
| Pump Stop Push ButtonT | -1XB | ||
| Brake Push ButtonT | -1XD | ||
| Selector Switch | Hand-Off-Auto Selector Switch | -3 | |
| SMC-Off-Bypass Selector Switch | -3B | ||
| Pilot Light | Transformer Pilot Light (Red or Green Lens) | -4_ | |
| Push-To-Test Pilot Light (Red Lens) | -5_ | ||
| Control Circuit Transformer | Control Circuit Transformer (fused primary and secondary) | -6P | |
| SCR Fusing | Fast Acting Current Limiting SCR Fusing | for 24 A unit | -SCR |
| Fast Acting Current Limiting SCR Fusing | for 35 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 54 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 97…135 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 180 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 240 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 360 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 500 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 650…720 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 850 A unit | ||
| Fast Acting Current Limiting SCR Fusing | for 1000 A unit | ||
| Door-Mounted Human Interface Module |
Programmer Only (Type 1) | -HAP | |
| Programmer Only (Type 4/12) | -HJP | ||
| Digital Contral Panel (Type 1) | -HA2 | ||
| Digital Control Panel (Type 4/12) | -HJ2 | ||
| Communication Module | Remote I/O | -GD1 | |
| RS-232/422/485, DH485 | -GD2 | ||
| DeviceNet™ Network | -GK5 | ||
| Enhanced DeviceNet | -GU6 | ||
| ControlNet | -CN1 | ||
| ¬ Add the designated letter to the end of the Cat. No. For example, to add the pump control option Cat. No. 152H-B180JBDB-51 . | |||
| T Option push buttons are available only when the corresponding option module is selected. For example, Cat. No. 150-A24JBDA-1XA. | |||
| Specify pilot light lens color. Options: Red, Green. | |||
| Option | Description | Cat. No. Modification |
|
| Protective Module¬ | 480V Line Side Protective Module | 24…54 A | -8L |
| 480V Line Side Protective Module | 97…360 A | ||
| 600V Line Side Protective Module | 24…54 A | ||
| 600V Line Side Protective Module | 97…360 A | ||
| 480V Load Side Protective Module | 24…54 A | -8M | |
| 480V Load Side Protective Module | 97…360 A | ||
| 600V Load Side Protective Module | 24…54 A | ||
| 600V Load Side Protective Module | 97…360 A | ||
| 480V Both Line and Load Side Protective Module | 24…54 A | -8B | |
| 480V Both Line and Load Side Protective Module | 97…360 A | ||
| 600V Both Line and Load Side Protective Module | 24…54 A | ||
| 600V Both Line and Load Side Protective Module | 97…360 A | ||
| Auxiliary ContactsT | N.O. auxiliary contacts | for 24…240 A | -90 |
| N.O. auxiliary contacts | for 360…1000 A | ||
| N.C. auxiliary contacts | for 24…240 A | -91 | |
| N.C. auxiliary contacts | for 360…1000 A | ||
| 1 N.O and 1 N.C. auxiliary contacts | for 24…240 A | -901 | |
| 1 N.O. and 1 N.C. auxiliary contacts | for 360…1000 A | ||
| Unwired Control RelaysØ | Bulletin 700CF 4-pole relay 2 N.O. and 2 N.C. | -89F22 | |
| Bulletin 700CF 4-pole relay 3 N.O. and 1 N.C. | -89F31 | ||
| Bulletin 700CF 4-pole relay 4 N.O. | -89F40 | ||
| Disconnect Auxiliaryz | N.O. disconnect auxiliary mounted on operating mechanism | -98 | |
| N.C. disconnect auxiliary mounted on operating mechanism | -99 | ||
| Circuit Breaker Disconnect Auxilaryª |
Internal N.O. circuit breaker auxiliary | -98X | |
| Internal N.C. circuit breaker auxiiary | -99X | ||
| Service Entrance Label | Service Entrance Label | 24…650 A | -SEL |
| 720…1000 A | |||
| UL Label | UL Label | -UL | |
| NEMA Bypass Contactor§ | NEMA Bypass | for 24…97 A unit | -NB |
| NEMA Bypass | for 135…180 A unit | ||
| NEMA Bypass | for 240 A unit | ||
| NEMA Bypass | for 360 A unit | ||
| NEMA Bypass | for 500 A unit | ||
| NEMA Isolation Contactor§ | NEMA Isolation | for 24…97 A unit | -NI |
| NEMA Isolation | for 135…180 A unit | ||
| NEMA Isolation | for 240 A unit | ||
| NEMA Isolation | for 360 A unit | ||
| NEMA Isolation | for 500 A unit | ||
| ¬ Line and Load Side Protective Modules are standard on 500…1000 A units. | |||
| T Available only with enclosed Bulletin 150, 152 and 153 devices with bypass contactor. Maximum of four (4) auxiliary contacts. | |||
| § Thermal overload for Bulletin 150 enclosed controllers only. Overload is standard on Bulletins 152 and 153. | |||
| Ø Instantaneous auxiliary contacts on Bulletin 700CF relays are non-convertible. | |||
| z Available only with Bulletin 152 and 153 devices. Maximum of two (2) disconnect auxiliaries. | |||
| ª Available only with Bulletin 153 devices. Maximum of two (2) disconnect auxiliaries. | |||
| v Order to be released to manufacturing upon release of signed print approval drawings. | |||
| § 650, 720, 850, and 1000 A units currently use a NEMA contactor. | |||