Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Soft Starters > SMC™ Dialog Plus Smart Motor Controller
SMC™ Dialog Plus Smart Motor Controller
| Introduction | Standards Compliance and Certifications | Modes of Operation | Cat. No. Explanation | Product Selection |
| Options | Accessories | Specifications | Approximate Dimensions |
| Functional Design Specifications | |||
| Standard Features | Installation | Power Wiring | The SMC Dialog Plus Controller can be wired with or without an isolation contactor. Bypass contactors can be employed after the controller has brought the motor to full speed. |
| Control Wiring | 2- and 3-wire control for a wide variety of applications. | ||
| Setup | Keypad | The SMC Dialog Plus Controller is configured with the front keypad and backlit LCD display. | |
| Software | Parameter values can be downloaded to the SMC Dialog Plus Controller with DriveTools programming software and the Cat. No. 1203-GD2 communication module. | ||
| Communications | One serial port provided for connection to optional human interface and communication modules. | ||
| Starting Modes | Soft start with selectable kickstart, current limit, dual ramp, and full voltage in one unit. | ||
| Protection and Diagnostics | Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. | ||
| Metering | Amps, volts, kW, kWH, elapsed time, power factor, motor thermal capacity usage. | ||
| Status Indication | Stopped, ramping, stopping, at speed, and fault. | ||
| Auxiliary Contacts | (1) Single-pole double-throw contact programmable as normal or up-to-speed; one programmable as normal or fault. | ||
| Optional Features | Soft Stop | Extended coast-to-rest to minimize load shifting. Ramp down time is adjustable from 0…60 s. | |
| Pump Control | Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting time is adjustable from 0…30 s. Stopping time is adjustable from 0…120 s. | ||
| Preset Slow Speed | Enables the operator to position material. The preset slow speed can be set for low (7% of base speed), high (15% of base speed), reverse low (10% of base speed) or reverse high (20% of base speed). | ||
| SMB Smart Motor Braking | Provides motor braking without additional equipment for applications that require the motor to stop quickly. Braking current is adjustable from 0…400% of the motors full-load current rating. | ||
| Accu-Stop/Slow Speed with Braking |
Combines Smart Motor Braking and Preset Slow Speed. Braking current is adjustable from 0…400% of full-load current. Slow speed can be set for either Low (7% of base speed) or High (15% of base speed). |
||
| Electrical Ratings | ||||
| UL/CSA/NEMA | IEC | |||
| Power Circuit | Rated Operation Voltage | 200…480V AC 200…600V AC (15%, +10%) |
200…415V 200…500V |
|
| Rated Insulation Voltage | N/A | 500V | ||
| Rated Impulse Voltage | N/A | 6000V | ||
| Dielectric Withstand | 2200V AC | 2500V | ||
| Repetitive Peak Inverse Voltage Rating | 200…480V AC: 1400V 200…600V AC: 1600V |
200…415V: 1400V 200…500V: 1600V |
||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Utilization Category | MG 1 | AC-53a | ||
| Protection Against Electrical Shock | N/A | IP00 (open device) | ||
| DV/DT Protection | RC Snubber Network | |||
| Transient Protection | Metal Oxide Varistors: 220 Joules @ 24…360 A 220 Joules @ 480V, 500…1000 A 300 Joules @ 600V, 500…1000 A |
|||
| Short-Circuit Protection |
SCPD Performance | Type 1 | ||
| SCPD List | Maximum Fuse or Circuit Breaker (A): | |||
| Device Operational Current Rating (A) | 24 | 80 | ||
| 35 | 125 | |||
| 54 | 200 | |||
| 97 | 350 | |||
| 135 | 500 | |||
| 180 | 600 | |||
| 240 | 700 | |||
| 360 | 1000 | |||
| 500 | 1200 | |||
| 650 | 1600 | |||
| 720 | 2000 | |||
| 850 | 2500 | |||
| 1000 | 3000 | |||
| Control Circuit | Rated Operational Voltage | 100…240V AC 24V AC 24V DC |
100…240V 24V 24V DC |
|
| Rated Insulation Voltage | N/A | 240V | ||
| Rated Impulse Voltage | N/A | 3000V | ||
| Dielectric Withstand | 1600V AC | 2000V | ||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Protection Against Electric Shock | N/A | IP20 | ||
| Power Requirements |
Control Module | 40 VA | ||
| Heatsink Fan(s) (A)¬ | 24 | — | ||
| 35 | — | |||
| 54 | — | |||
| 97 | 45 VA | |||
| 135 | 45 VA | |||
| 180 | 45 VA | |||
| 240 | 45 VA | |||
| 360 | 45 VA | |||
| 500 | 145 VA | |||
| 650 | 320 VA | |||
| 720 | 320 VA | |||
| 850 | 320 VA | |||
| 1000 | 320 VA | |||
| ¬ For devices rated 24…500 A, heatsink fans can be powered by either 110/120V AC or 220/240V AC. For devices rated 650…1000 A, heatsink fans can only be powered by 110/120V AC. | ||||
| Electrical Ratings, Continued | ||||
| UL/CSA/NEMA | IEC | |||
| Maximum Heat Dissipation (Watts) |
Controller Rating (A) |
24 | 110 | |
| 35 | 150 | |||
| 54 | 200 | |||
| 97 | 285 | |||
| 135 | 490 | |||
| 180 | 660 | |||
| 240 | 935 | |||
| 360 | 1170 | |||
| 500 | 1400 | |||
| 650 | 2025 | |||
| 720 | 2250 | |||
| 850 | 2400 | |||
| 1000 | 2760 | |||
| Auxiliary Contacts |
Rated Operation Voltage | 240V AC | 240V | |
| Rated Insulation Voltage | N/A | 240V | ||
| Dielectric Withstand | 1600V AC | 2000V | ||
| Operating Frequency | 50/60 Hz | 50/60 Hz | ||
| Utilization Category | B300 (terminals 18…19) C300 (terminals 18…20) C300 (terminals 29…30) |
AC-15 | ||
| SCPD Performance | Type 2 | |||
| SCPD List | Class CC 8 A @ 1000 A Available Fault Current | |||
| Environmental | ||||
| Operating Temperature Range | 0…+50 °C (32…122 °F) (open) 0…+40 °C (32…104 °F) (enclosed) |
|||
| Storage and Transportation Temperature Range | 20…+75 °C | |||
| 2000 m (6560 ft) | ||||
| Humidity | 5…95% (non-condensing) | |||
| Pollution Degree | 2 | |||
| Mechanical | ||||
| Resistance to Vibration |
Operational Non-Operational |
1.0 G Peak, 0.006 in. displacement 2.5 G, 0.015 in. displacement |
||
| Resistance to Shock |
Operational Non-Operational |
15 G 30 G |
||
| Construction | Power Poles |
Thermoset Moldings Heatsink hockey puck thyristor |
24…135 A 180…1000 A |
|
| Control Modules | Thermoset and Thermoplastic Moldings | |||
| Metal Parts | Anodized Aluminum, Plated Brass, Copper, or Painted Steel | |||
| Terminals | Power Terminals |
24…54 A | 6.0 mm hole with clamp screw | |
| 97 and 135 A | One 11.5 mm (0.453 in.) diameter hole each | |||
| 180…360 A | One 10.5 mm (0.413 in.) diameter hole each | |||
| 500 A | Two 13.5 mm (0.531 in.) diameter holes each | |||
| 650 and 720 A | Three 13.1 mm (0.515 in.) diameter holes each | |||
| 850 and 1000 A | Six 13.1 mm (0.515 in.) diameter holes each | |||
| Power Terminal Markings | NEMA, CENELEC EN50 012 | |||
| Control Terminals | M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate | |||
| Other | ||||
| EMC Emission Levels |
Conducted Radio Frequency Emissions Radiated Emissions |
Class A Class A |
||
| EMC Immunity Levels |
Electrostatic Discharge | 8 kV Air Discharge | ||
| Radio Frequency Electromagnetic Field | Per IEC 947-4-2 | |||
| Fast Transient | Per IEC 947-4-2 | |||
| Surge Transient | Per IEC 947-4-2 | |||
| Overload Characteristics |
Current Range | 1.0…999.9 A | ||
| Trip Classes | 10, 15, 20, and 30 | |||
| Trip Current Rating | 120% of Motor FLC | |||
| Number of Poles | 3 | |||
Specifications, Continued
Fuse Clip Sizing and Type for Fusible Combination Controllers¬ T
| Horsepower @ 480V | Fuse Clip Size/Type | Fuse Size Range [A] |
| 15 | 30 A/Class J | 0…30 |
| 20 | 60 A/Class J | 31…60 |
| 25 | 60 A/Class J | 31…60 |
| 30 | 60 A/Class J | 31…60 |
| 40 | 100 A/Class J | 61…100 |
| 50 | 100 A/Class J | 61…100 |
| 60 | 200 A/Class J | 101…200 |
| 75 | 200 A/Class J | 101…200 |
| 100 | 200 A/Class J | 101…200 |
| 125 | 400 A/Class J | 201…400 |
| 150 | 400 A/Class J | 201…400 |
| 200 | 400 A/Class J | 201…400 |
| 250 | 400 A/Class J | 401…600 |
| 300 | 600 A/Class J | 401…600 |
| 350 | 600 A/Class J | 401…600 |
| 400 | 1200 A/Class L | 601…1600 |
| 450 | 1200 A/Class L | 601…1600 |
| 500 | 1200 A/Class L | 601…1600 |
| 600 | 1200 A/Class L | 601…1600 |
| 700 | 1200 A/Class L | 601…1600 |
| 800 | 1200 A/Class L | 601…1600 |
| ¬ Consult NEC Handbook for proper fuse sizing guidelines. | ||
| T Optional fuse clip sizes and types are available upon request. Consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||
Circuit Breaker Sizes and Rating Plug Sizes
| Horsepower @ 480V | Circuit Breaker Size [A]/ Rating Plug Size [A] |
Interrupting Rating in Symmetrical Amps @ 480V |
| 15 | 150/50 | 14 000 |
| 20 | 150/50 | 14 000 |
| 25 | 150/60 | 14 000 |
| 30 | 150/70 | 14 000 |
| 40 | 150/100 | 14 000 |
| 50 | 150/125 | 14 000 |
| 60 | 250/150 | 25 000 |
| 75 | 250/175 | 25 000 |
| 100 | 250/225 | 25 000 |
| 125 | 250/250 | 25 000 |
| 150 | 400/300 | 35 000 |
| 200 | 400/400 | 35 000 |
| 250 | 600/500 | 35 000 |
| 300 | 600/600 | 35 000 |
| 350 | 800/800 | 35 000 |
| 400 | 800/800 | 50 000 |
| 450 | 1200/1000 | 50 000 |
| 500 | 1200/1200 | 50 000 |
| 600 | 1200/1200 | 50 000 |
| 700 | 2000/1600 | 65 000 |
| 800 | 2000/2000 | 65 000 |
| For higher interrupting ratings, consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||