Catalogs > Industrial Controls Catalog > Motor Control, Solid-State > Contactors
Contactors
| Introduction | Standards Compliance and Certifications | Product Selection | Specifications | Approximate Dimensions | Current Monitoring Operation | Multi-Function Analog Operation |
http://raise.rockwellautomation.com/RAConfig/browsecatalog.asp?KW=&PID=156&DLID=ABStdData&LID=ABStdProds&locID=USA&onKil=browsecatalog.asp%3FLID%3DABStdProds%26DLID%3DABStdData%26KW%3D%26HKW%3D%26locID%3DUSA"target="_blank
Solid-State Power Contactors
Single-Phase§
| Current Rating [A] | Control Voltage | Hp Rating @ 40 °C (104 °F) | Operational Voltage | ||||||
| 24…230V AC | 42…600V AC | ||||||||
| 115V | 230V | 480V | 600V | Cat. No. | |||||
| 20 | 24…275V AC, 24…48V DC | 1/6 | 1/2 | 1 | 2 | 156-B20AA1 | 156-B20CA1 | ||
| 5…24V DC | 156-B20AB1 | 156-B20CB1 | |||||||
| 30 | 24…275V AC, 24…48V DC | 1/2 | 1-1/2 | 3 | 5 | 156-B30AA1 | 156-B30CA1 | ||
| 5…24V DC | 156-B30AB1 | 156-B30CB1 | |||||||
| 45 | 24…275V AC, 24…48V DC | 1 | 2 | 5 | 7-1/2 | 156-B45AA1 | 156-B45CA1 | ||
| 5…24V DC | 156-B45AB1 | 156-B45CB1 | |||||||
| 50 | 24…275V AC, 24…48V DC | 1 | 2 | 5 | 7-1/2 | 156-B50AA1 | 156-B50CA1 | ||
| 5…24V DC | 156-B50AB1 | 156-B50CB1 | |||||||
| 70 | 24…275V AC, 24…48V DC | 1-1/2 | 3 | 5 | 10 | 156-B70AA1 | 156-B70CA1 | ||
| 5…24V DC | 156-B70AB1 | 156-B70CB1 | |||||||
| 75 | 24…275V AC, 24…48V DC | 1-1/2 | 3 | 5 | 10 | ∆ | 156-B75AA1 | ∆ | 156-B75CA1 |
| 5…24V DC | ∆ | 156-B75AB1 | ∆ | 156-B75CB1 | |||||
| 90 | 24…275V AC, 24…48V DC | 1-1/2 | 3 | 5 | 10 | ∆ | 156-B90AA1 | ∆ | 156-B90CA1 |
| 5…24V DC | ∆ | 156-B90AB1 | ∆ | 156-B90CB1 | |||||
| § Includes an integrated varistor for surge protection. | |||||||||
| These Hp ratings only apply to units with operational voltage ranges of 42…600V AC. | |||||||||
| ∆ Includes an integrated fan in the heat sink assembly. Fan will automatically switch on when necessary (approximately 125 °C internal temp.). Includes overtemperature protection. See Overtemperature Alarm Cutout/Protection Operation for details. | |||||||||
Dual-Phase§
| Current Rating [A] | Control Voltage | Hp Rating @ 40 °C (104 °F) | Operational Voltage | ||||
| 24…230V AC | 48…600V AC | ||||||
| 115V | 230V | 480V | 600V | Cat. No. | |||
| 25 | 24…275V AC, 24…190V DC | 1 | 3 | 5 | 7-1/2 | 156-B25AA2 | 156-B25CA2 |
| 5…24V DC | 156-B25AB2 | 156-B25CB2 | |||||
| 32 | 24…275V AC, 24…190V DC | 1 | 3 | 7-1/2 | 10 | 156-B32AA2 | 156-B32CA2 |
| 5…24V DC | 156-B32AB2 | 156-B32CB2 | |||||
| § Includes an integrated varistor for surge protection. | |||||||
| These Hp ratings only apply to units with operational voltage ranges of 48…600V AC. | |||||||
Three-Phase
| Current Rating [A] | Control Voltage | Hp Rating @ 40 °C (104 °F) | Operational Voltage | ||||||
| 24…230V AC | 48…600V AC | ||||||||
| 115V | 230V | 480V | 600V | Cat. No. | |||||
| 20 | 24…275V AC, 24…190V DC | 1 | 3 | 5 | 7-1/2 | 156-B20AA3 | 156-B20CA3 | ||
| 5…24V DC | 1 | 3 | 5 | 7-1/2 | 156-B20AB3 | 156-B20CB3 | |||
| 25 | 24…275V AC, 24…190V DC | 1 | 3 | 7-1/2 | 10 | 156-B25AA3 | 156-B25CA3 | ||
| 5…24V DC | 1 | 3 | 7-1/2 | 10 | 156-B25AB3 | 156-B25CB3 | |||
| 32 | 24…275V AC, 24…190V DC | 1 | 3 | 7-1/2 | 10 | ∆ | 156-B32AA3 | ∆ | 156-B32CA3 |
| 5…24V DC | 1 | 3 | 7-1/2 | 10 | ∆ | 156-B32AB3 | ∆ | 156-B32CB3 | |
| These Hp ratings only apply to units with operational voltage ranges of 48…600V AC. | |||||||||
| ∆ Includes an integrated fan in the heat sink assembly. Fan will automatically switch on when necessary (approximately 125 °C internal temp.). Includes overtemperature protection. See Overtemperature Alarm Cutout/Protection Operation for details. | |||||||||
Solid-State Specialty Contactors
Single-Phase with Current Monitoring⋆
| Current Rating [A] | Supply Voltage | Control Voltage | Rated Hp @ 40 °C (104 °F), 50/60 Hz | Alarm Type | Operational Voltage | ||||
| 24…265V AC | 42…660V AC | ||||||||
| 115V AC | 230V AC | 480V AC | 600V AC | Cat. No. | |||||
| 30 | 24V DC | 4…32V DC | 3/4 | 2 | 5 | 5 | PNP, N.O. | 156-B30ABP | 156-B30CBP |
| NPN, N.O. | 156-B30ABN | 156-B30CBN | |||||||
| 50 | 1 | 2 | 5 | 7-1/2 | PNP, N.O. | 156-B50ABP | 156-B50CBP | ||
| NPN, N.O. | 156-B50ABN | 156-B50CBN | |||||||
| These Hp ratings only apply to units with operational voltage ranges of 42…660V AC. | |||||||||
| ⋆ For current monitoring range, please see additional specifications on and monitoring Operations data on Product Description. | |||||||||
Single-Phase, Single-Pole, Multi-function Analog♣
| Current Rating [A] | Control Input | Operational Voltage | ||
| 90…265V AC | 200…550V AC | 410…660V AC | ||
| Cat. No. | ||||
| 30 | 0…10V DC§ | 156-B30AV1 | 156-B30BV1 | 156-B30CV1 |
| 4…20 mA | 156-B30AC1 | 156-B30BC1 | 156-B30CC1 | |
| 50 | 0…10V DC§ | 156-B50AV1 | 156-B50BV1 | 156-B50CV1 |
| 4…20 mA | 156-B50AC1 | 156-B50BC1 | 156-B50CC1 | |
| ♣ See additional specifications, see and current monitoring data on Product Description. | ||||
| § Requires a 24V AC/DC supply to power the control circuitry of the solid-state contactor. See wiring diagrams on Single-Phase for additional details. | ||||