| General
|
|
|
Single-Phase and Single-Phase with Current Monitoring
|
Dual- and Three-Phase
|
Single-Phase with Analog Control
|
| Nominal Voltage Rating
|
230V AC
|
400/480/600V AC
|
230V AC
|
400/480/600V AC
|
230V AC
|
400/480V AC
|
600V AC
|
| Operational Voltage Range
|
24…265V AC
|
42…660V AC
|
24…280V AC
|
48…660V AC
|
90…265V AC
|
200…550V AC
|
410…660V AC
|
| Blocking Voltage
|
650Vp
|
1200Vp
|
650Vp
|
1200Vp
|
650Vp
|
1200Vp
|
1200Vp
|
| Operational frequency
|
45…65 Hz
|
| Power Factor Minimum
|
³ 0.5 @ 230V AC rms
|
³ 0.5 @ 600V AC rms
|
³ 0.5 @ 230V AC rms
|
³ 0.5 @ 600V AC rms
|
³ 0.9 @ 230V AC rms
|
³ 0.9 @ 480V AC rms
|
³ 0.9 @ 600V AC rms
|
Rated Insulation Voltage — Input to output, output to case
|
4000V AC rms
|
| Relay ON Indication
|
Green LED, ON when control input is detected
|
| Overtemp Alarm ON Indication⋆
|
Red LED, on when the solid-state contactor (SSC) temperature switching element (SCR) temperature is exceeded. SSC output (load) will switch OFF (Green LED: OFF). When overtemperature condition is removed, red LED will go OFF and normal operation will continue on the control input cycle.
|
| Overtemp Alarm⋆
|
I max.
|
50 mA DC
|
50 mA DC
|
50 mA DC
|
50 mA DC
|
—
|
—
|
—
|
| U max.
|
50V DC
|
50V DC
|
50V DC
|
50V DC
|
—
|
—
|
—
|
| Standards Compliance
|
cULus
|
| Environmental
|
| Operating Temperature
|
-30…+70 °C (-22…+158 °F)
|
| Storage Temperature
|
-40…+100 °C (-40…+212 °F)
|
| RoHS Compliance
|
Yes
|
| Vibration
|
6 G (per EN50155)
|
| Pollution Degree
|
2
|
| Mechanical
|
| Housing Material
|
PBT, Flame Retardent
|
| Heat Sink Material
|
Black Anodized Aluminum
|
| Din Rail Mount Base
|
Electroplated Steel
|
| Mounting
|
Vertical
|
| Approximate Weight
|
22.5 mm
|
0.225 kg (0.5 lb)
|
| 45 mm
|
0.43 kg (0.95 lb)
|
| 45 mm with Integrated Fan
|
0.46 kg (1.0 lb)
|
| 90 mm
|
0.75 kg (1.65 lb)
|
| 90 mm with Integrated Fan
|
0.78 kg (1.72 lb)
|
| Contactor Type
|
Single Phase
|
Dual- and Three-phase
|
| Package Size
|
22.5 mm
|
45 and 90 mm
|
45 and 90 mm
|
| Control Terminals
|
Screw Type
|
M4
|
M3
|
M3
|
| min wire size
|
1 x 0.5 mm2 (1 x 20 AWG)
|
1 x 0.5 mm2 (1 x 20 AWG)
|
(one wire min. & max.) 1 x 0.5 mm2 (1 x 20 AWG)…1 x 4.0 mm2 (1 x 12 AWG)
|
| max wire size
|
2 x 2.5 mm2 (2 x 14 AWG)
|
1 x 4.0 mm2 (1 x 12 AWG) or 2 x 2.5 mm2 (2 x 1 4 AWG)
|
(two wire min. & max.) 2 x 0.5 mm2 (2 x 20 AWG)…2 x 2.5 mm2 (2 x 1 4 AWG)
|
| max torque
|
2 Nm
|
0.6 Nm
|
0.6 Nm
|
| bit type
|
posidrive 1 bit
|
posidrive 0 bit
|
posidrive 0 bit
|
| Power Terminals
|
Screw Type
|
M4
|
M5
|
M3
|
| min wire size
|
1 x 0.5 mm2 (1 x 20 AWG)
|
1 x 4.0 mm2 (1 x 12 AWG)
|
(one wire min. & max.) 1 x 0.5 mm2 (1 x 20 AWG)…1 x 4.0 mm2 (1 x 12 AWG)
|
| max wire size
|
2 x 2.5 mm2 (2 x 14 AWG)
|
1 x 25 mm2 (1 x 3 AWG) or 2 x 10 mm2 (2 x 6 AWG)
|
(two wire min. & max.) 2 x 0.5 mm2 (2 x 20 AWG)…2 x 2.5 mm2 (2 x 14 AWG)
|
| max torque
|
2 Nm
|
2.5 Nm
|
0.6 Nm
|
| bit type
|
posidrive 1 bit
|
posidrive 2 bit
|
posidrive 0 bit
|
|
|
| ⋆ Alarm capability exists on 1-phase 75 and 90 A, 5…24V DC control and 3-phase 32 A, 5…24V DC control units.
|
| Control Input
|
| Control voltage range (±10%)
|
Single-Phase, Single-Phase with Current Monitoring, and Single-Phase with Analog Control
|
Dual- and Three-Phase
|
| DC
|
AC/DC
|
DC
|
AC/DC
|
| Control Voltage Range
|
4…32V
|
24…275V AC/24…48V DC
|
5…32V DC
|
24…275V AC/24…190V DC
|
| Pick Up Voltage
|
3.8V DC
|
22V AC/DC
|
4.7V DC
|
22V AC/DC
|
| Reverse Voltage
|
32V DC
|
—
|
32V DC
|
—
|
| Drop Out Voltage
|
1.2V DC
|
6V AC/DC
|
1.2V DC
|
6V AC/DC
|
| Maximum Input Current
|
12 mA
|
17 mA
|
24 mA
|
15 mA
|
| Maximum Response Time Pick Up and Drop Out
|
1/2 Cycle
|
1 Cycle
|
1 Cycle
|
1 Cycle
|
|
|
| Power Output
|
|
|
Housing Size [mm]
|
Rated Operational Current ♦
|
Min. Oper. Current
|
Max. Repetitive Overload Current (ACrms) t = 1 s
|
Non-Repetitive Surge Current (ACrms) Tj = 25 °C t = 10 ms
|
Max. Off-State Leakage Current @ Rated Voltage and Frequency Tj = 25 °C t = 10 ms
|
I2t for Fusing t = 10 ms♣
|
Max. SCCR (65 kA) Fuse Current§
|
On-State Voltage Drop @ Rated Current Tj = 25 °C t = 10 ms
|
Critical dV/dT Off-State
|
| AC51 @ 25 °C
|
AC53a @ 25 °C
|
| Single-Phase
|
156-B20…1
|
22.5
|
20 A
|
5 A
|
350 mA
|
35 A
|
300 A
|
3 mA
|
450 A2s
|
20 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B30…1
|
22.5
|
30 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B45…1
|
45
|
45 A
|
20 A
|
400 mA
|
150 A
|
1150 A
|
3 mA
|
6600 A2s
|
60 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B50…1
|
45
|
50 A
|
30 A
|
500 mA
|
200 A
|
1900 A
|
3 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B70…1
|
90
|
70 A
|
30 A
|
500 mA
|
200 A
|
1900 A
|
3 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B75…1
|
45 with fan∆
|
75 A
|
30 A
|
500 mA
|
200 A
|
1900 A
|
3 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B90…1
|
90 with fan∆
|
90 A
|
30 A
|
500 mA
|
200 A
|
1900 A
|
3 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
500 V/uS
|
| Dual-Phase
|
156-B25…2
|
45
|
25 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B32…2
|
90
|
32 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| Three-Phase
|
156-B20…3
|
45
|
20 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B25…3
|
90
|
25 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| 156-B32…3
|
45 with fan∆
|
32 A
|
15 A
|
250 mA
|
125 A
|
600 A
|
3 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
500 V/uS
|
| Single-Phase with Current Monitoring
|
156-B30…
|
45
|
30 A
|
15 A
|
150 mA
|
125 A
|
600 A
|
5 mA
|
1800 A2s
|
40 A
|
1.6 Vrms
|
1000 V/uS
|
| 156-B50…
|
45
|
50 A
|
30 A
|
500 mA
|
200 A
|
1900 A
|
5 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
1000 V/uS
|
| Single-Phase with Analog Control
|
156-B30…
|
45
|
30 A
|
—
|
150 mA
|
55 A
|
325 A
|
3 mA
|
525 A2s
|
30 A
|
1.6 Vrms
|
1000 V/uS
|
| 156-B50…
|
45
|
50 A
|
—
|
500 mA
|
200 A
|
1900 A
|
3 mA
|
18000 A2s
|
90 A
|
1.6 Vrms
|
1000 V/uS
|
|
|
| AC51 indicates a resistive load. For details, refer to IEC 60947-4-3. AC53a indicates an inductive (motor) load. For details, refer to IEC 60947-4-2.
|
| ♣ To potentially protect the solid-state contactor from a short-circuit condition, select a semiconductor fuse with an I2T value less than the one indicated below for the SSC.
|
| § Provides Type 1 protection using a Class J or CC fuse.
|
| ∆ Includes an integrated fan in the heat sink assembly. Fan will automatically switch on when necessary (approximately 125 °C internal temp.). DC control Includes overtemperature alarm cutout.
|
| ♦ Current per each phase.
|
| Power Dissipation
|
|
|
Size [A]
|
Power Dissipation [W/A]
|
| Single-Phase
|
20
|
1.10
|
| 30
|
0.95
|
| 45
|
0.90
|
| 50
|
0.85
|
| 75
|
0.90
|
| 70
|
0.90
|
| 90
|
0.93
|
| Dual-Phase
|
25/32
|
2.80
|
| Three-Phase
|
20/25/32
|
1.92
|
| Single-Phase with Current Monitoring
|
30
|
1.00
|
| 50
|
0.85
|
| Single-Phase with Multi-Function Analog Control
|
30
|
0.95
|
| 50
|
0.85
|
|
|
| Additional Specifications that only apply to the Single-Phase with Current Monitoring Contactor
|
| Supply Status Indication
|
Green LED, Half Intensity
|
| Control Status Indication
|
Green LED
|
| Overtemp Alarm Trip Indication
|
Red LED, Intermittent
|
| Alarm Indication (except for overtemp alarm)
|
Red LED
|
| Power Supply Voltage, Vcc
|
24V DC +/- 15%
|
| Maximum Supply Currrent
|
22 mA (per device)
|
| Maximum Control Input Current
|
1.5 mA
|
| Maximum PLC Current @ 24 VDC
|
275 uA (per device)
|
| Alarm Output Current, Maximum
|
50 mA DC
|
| Alarm Output Voltage
|
NPN (N.O.)
|
1 + 0.15 Io
|
| PNP (N.O.)
|
VCC - 1 - 0.15 Io
|
| Maximum number of Parallel Outputs
|
£ 50
|
| Current Monitoring Measurement Range
|
30 A
|
0.3 … 30 A AC rms
|
| 50 A
|
0.5 … 50 A AC rms
|
| Minimum Teach Current
|
30 A
|
0.3 A AC rms
|
| 50 A
|
0.5 A AC rms
|
| Minimum Partial Load Current
|
30 A
|
50 mA AC rms
|
| 50 A
|
83 mA AC rms
|
|
|
| Additional Specifications that only apply to the Single-Phase with Multi-Function Analog Control Contactor
|
| Load Status Indication
|
Red LED
|
| Control Status Indication
|
Green LED
|
| Current Controlled Input Specifications
|
Control Current Range
|
4…20 mA
|
| Max. Allowable Current
|
50 mA
|
| Pick Up Current
|
4.2 mA
|
| Drop Out Current
|
3.9 mA
|
| Reverse Polarity Protected
|
Yes
|
| Voltage Drop
|
10V DC @ 20 mA
|
| Voltage Controlled Input Specifications
|
Supply Voltage Range, Vss♣
|
20…28V AC/DC
|
| Supply Current♣
|
18 mA @ 24V DC 23 mA @ 24V AC
|
| Control Voltage Range, Vcc
|
0…10V DC
|
| Control Input Current
|
0.1 mA @ 10V DC
|
| Reverse Polarity Protected
|
Yes
|
| Pick up Voltage
|
0.5V DC
|
| Drop out Voltage
|
0.05V DC
|
| Output Power Range
|
0…99%
|
| Transfer Characteristics - Output Power %
|
|
Current Control Level
|
Voltage Control Level
|
| 0%
|
4 mA
|
0V DC
|
| 25%
|
8 mA
|
2.5V DC
|
| 50%
|
12 mA
|
5V DC
|
| 75%
|
16 mA
|
7.5V DC
|
| 99%
|
20 mA
|
10V DC
|
| Output Power Resolution
|
Mode 1 - Phase Angle
|
1/300 @ 50 Hz , 1/300 @ 60 Hz
|
| Mode 2 - Full Cycle
|
1/64 @ 50 Hz , 1/64 @ 60 Hz
|
| Mode 3 - 1 Sec Burst
|
1/50 @ 50 Hz , 1/60 @ 60 Hz
|
| Mode 4 - 3 Sec Burst
|
1/150 @ 50 Hz , 1/180 @ 60 Hz
|
| Mode 5 - 10 Sec Burst
|
1/500 @ 50 Hz , 1/600 @ 60 Hz
|
|
|
| ♣ The 0…10V DC type contactor requires a 24V AC/DC supply to power the control circuitry of the solid-state contactor.
|