Industrial Controls Catalog

Catalogs > Industrial Controls Catalog > Power & Energy Management

Power & Energy Management

Introduction Specifications Product Selection
Specifications

Powermonitor 3000

Environmental
Operating Temperature, Ambient 1404-MX05X-000, DNT, 1404-DM –20…+60 °C (–4…+140 °F)
1404-MX05X-RIO, RS232, ENT 0…55 °C (32…132 °F)
Storage Temperature –40…+85 °C (–40…+185 °F)
Humidity 5…95% non-condensing
Vibration 10…500 Hz operational: 2 g (±0.012 in.)
non-operational: 2.5 g (±0.015 in.)
Shock 1/2 sine pulse,
11 ms duration
operational: 30 g
non-operational: 30 g
  

Input and Output Ratings
Control Power Input 120/240V AC 50/60Hz or 125/250V DC
Voltage Input Impedance 1 MW min., 399V AC max.
V1, V2, and V3 to N
Current Sense Inputs Overload withstand: 15 A continuous, 200 A for 1 s
Burden: 0.05 VA
Impedance: 0.002 W
Maximum crest factor (at 5 A): 3.0
Status Inputs Contact closure (internal 24V DC)
Control Relay Output ANSI C37.90-1989
KYZ Output Solid-state KYZ = 80 mA at 240…300V DC
  

Operational Data
  Nominal Range
Voltage 347V
600V
15…399V L-N rms
26…691V L-L rms
Current 5 A 50 mA…10.6 A rms
Frequency 50 or 60 Hz 40…75 Hz
  

Metering by model type
  M4 M5 M6 M8
Accuracy
Voltage ±0.2% ±0.05% ±0.05% ±0.05%
Current ±0.2% ±0.05% ±0.05% ±0.05%
Frequency ±0.05 Hz ±0.05 Hz ±0.05 Hz ±0.05 Hz
Power ±0.4% ±0.1% ±0.1% ±0.1%
Energy Class 1.0 - ANSI C12.16 Class 0.5 - ANSI C12.20 / EN 60687, Class 0.2 also available
Features
Configurable Setpoints 10 10 20 20
Waveform Captures 8 2
Harmonic Analysis
Order 41st 63rd
%THD X X X X
TIF X X
K-factor X X X X
Crest factor X X
IEEE 519 Compliance X X
Transient Detection X
  

Powermonitor 1000

General Specifications
Dielectric withstand Control power 2500V
Voltage inputs 2500V
Current inputs 2500V
Status inputs 2500V
KYZ output 2500V
Terminal Blocks 0.34…2.5 mm2 (22…14 AWG), 75 °C (167 °F) min. copper wire only;
recommended torque 0.8 N•m (7 lb•in)
Operating Temperature -10…+60 °C (14…140 °F)
Storage Temperature -40…+85 °C (-40…+185 °F)
Humidity 5…95%, non-condensing
Vibration 2.0 g 10…500 Hz
Shock 30 g peak each axis (operating) 50 g peak each axis (non-operating)
 

Input and Output Ratings
Control Power 85…264V AC, 47…63 Hz, 2.5 VA max.
Voltage Sense Inputs:
V1, V2, V3
Input impedance: 5 MW
Min. input current: 2 mA max.
Current Sense Inputs:
I1, I2, I3, I4
Overload withstand: 15 A continuous, 200 A for 1/2 s
Burden: 0.05 VA
Impedance: 0.002 W
Max. crest factor (at 5 A): 3.0
Starting current: 5 mA
Status Inputs Contact closure (internal 24V DC)
KYZ Output 30 mA at 240V AC/300V DC
  

Accuracy and Range
Parameter Accuracy in % of Full-Scale Reading
at 25 °C (77 °F)
50/60 Hz Unity Power Factor
Nominal/ Range
  Applies to:
TR1 TR2 EM1 EM2 EM3
Voltage Sense Inputs:
V1, V2, V3
±0.5% X X     X 347V/ 15…399V L‑N rms
600V/ 26…691V L‑L rms
Current Sense Input:
I1, I2, I3, I4
±0.5% X X     X 5 A/ 0.05…1.0 A rms
Frequency ±0.05 Hz X X     X 50 or 60 Hz/ 40…75 Hz
Power Functions:
kW, kVA, kVAR
EN62053-21:20
03 Accuracy
Requirement
Class 1★ 
  X     X  
Demand Functions:
kW, kVA
      X X
Energy Functions:
kWH, kVAH
    kWh only X X
Metering Update Rates 100 ms: V, I, Hz
200 ms: Power
X X X X X
  
★ Fast transient external influence tested at 2 kV.

Measured Parameters by model type
Logged Parameters TR1 TR2 EM1 EM2 EM3
Voltage X X     X
Current X X     X
Frequency X X     X
Voltage Unbalance X X     X
Current Unbalance X X     X
Real Power [kW]   X     X
Reactive Power [kVAR]   X     X
Apparent Power [kVA]   X     X
True Power Factor   X     X
Real Energy [kWh]     X X X
Reactive Energy [kVARh]       X X
Apparent Energy [kVAHh]       X X
Real Power Demand [kW]       X X
Reactive Power Demand [kVAR]       X X
Apparent Power Demand [kVA]       X X
Projected Real Power [kW ]       X X
Projected Reactive Power [kVAR]       X X
Projected Apparent Power [kVA]       X X
Demand Power Factor       X X
Logs TR1 TR2 EM1 EM2 EM3
Energy Log     X X X
Minimum/Maximum Log X X   X X
Load Factor Log       X X
Status Log X X X X X
  

PowerPad Portable Powermonitor

Electrical
Sampling Frequency 256 samples per cycle
Data Storage 4 MB partitioned for waveforms, transients, alarms, and trend recording
Voltage (TRMS) Phase-to-Phase: 830V
Phase-to-Neutral: 480V
Current (TRMS) 240 A Clamp: 0…6 A/120 A or 0…240 A
1000 A AC/1400 A DC Clamp: 0…1000 A AC, 0…1400 A DC
1200 A Clamp: 0…1200 A
6500 A Clamp: 0…6500 A★ 
Measurement Range Resolution Accuracy
Single-Phase RMS Voltages 6…480V 0.1V ±0.5% ±2cts
Phase-to-Phase RMS Voltages 10…830V 0.1V ±0.5% ±2cts
Single-Phase Peak Voltages 6…680V 1V ±(1% ±5cts)
Phase-to-Phase Peak Voltages 10…1360V 1V ±(1% ±5cts)
Frequency (Hz) 40…69 Hz 0.01 Hz ±0.01 Hz
DC Voltage Component 6…650V 0.1V ±1% ±2cts
Current Probes (Arms)
–MN Clamp
–SR Clamp
–AmpFlex™ Probe

0…240 A
0…1200 A
10…6500 A

0.1 A
0.1 A; 1…1000 A
0.1 A; 1…1000 A

±(0.5% + 2 cts)
±(0.5% + 2 cts)
±(0.5% + 1 A)
Active (Real) Power (kW) 0…9999 kW Four digits (10 000ct) ±1% ±1ct @ PF ³ 0.8
Reactive Power (kVAR) 0…9999 kVAR Four digits (10 000ct) ±1% ±1ct @ PF £ 0.8
Apparent Power (kVA) 0…9999 kVA Four digits (10 000ct) ±1% ±1ct
Power Factor (PF & DPF) -1.000…1.000 0.001 ±(1.5% + 0.01)
Active Energy (kWh) 0…9999 MWh Four digits (10 000ct) ±1% ±1ct @ PF ³ 0.8
Reactive Energy (kVARh) 0…9999 MVARh Four digits (10 000ct) ±1% ±1ct @ PF £ 0.8
Apparent Energy (kVAh) 0…9999 MVAh Four digits (10 000ct) ±1% ±1ct
Unbalance (V & A) 0…100% 0.1% ±1% ±1ct
Phase Angles (V-A, A-A, V-V) -179…180° ±2° ±1ct
Harmonics (1…50)
F=40…69Hz (V ³ 50V, A > Inom/100
0…999% 0.1% ±1% + 5ct
Total Harmonic Distortion (V & A) 0…999% 0.1% ±1% + 5ct
K-factor (Akf) 1…99.99 0.01 ±5% ±1ct
Flicker (Pst) 0.00…9.99 0.01
Power Source 9.6V NiMH rechargeable battery pack
AC supply: 110/230VAC ±20% (50/60Hz)
Battery Life 6 hours with display on; £96 hrs with display off (record mode)
Environmental
Operating Temperature 0…50 °C (32…122 °F)
Storage Temperature -20…+50 °C (-4…+122 °F)
Mechanical
Display 1/4 VGA (320 x 240) color LCD
Dimensions 240 x 180 x 55 mm (9.5 x 7 x 2 in.)
Weight 2.1 kg (4.6 lb)
Safety
Safety Rating EN 61010-1, 600V Cat. III, Pollution Degree 2
Double Insulation Yes
CE Mark Yes
 
★ Crest Factor at 6500 A = 1

Current Transformers

Core Type Split or solid
Current Ratio Range 50:5…6000:5
Burden Range 1…200 VA
Window Sizes Round Window: 1.00", 2.5", 1.13", 3.25", 1.47", 5.75", 2.31", 6.31", 8.25"
Rectangular Window: 2.00 x 5.5", 0.75 x 0.75", 4.5 x 4.5", 1.3 x 1.6", 1.42 x 1.53", 1.3 x 2.15", 2.75 x 2.7", 2 x 3.5", 2.6 x 6.25"
Certifications UL, CSA
Standards ANSI/IEEE C57.13, IEC 44-1
  

RSPower Software

System Hardware Requirements
Compatible Microprocessor Pentium 4 or P4
RAM 256 MB
Hard Disk 100 MB of available space
Drive CD-ROM/DVD-ROM
Disk Drive 3.5 inch, 1.44 MB
Operating System Windows 2000, Windows 2000 Server, Windows XP, or Windows Server 2003
  Microsoft .NET Framework 2.0
Application Adobe Acrobat Reader
Communication Type RSLinx Classic 2.51 OEM or higher (if not bundled with communications drivers)
Communication Interface Appropriate communications interface to the Powermonitor
Devices Bulletin 1400 Powermonitor, 1403 Powermonitor II, 1404 Powermonitor 3000, 1408 Powermonitor 1000
External Connections Serial, Ethernet, ControlNet™, DeviceNet™ or Remote I/O connection to the power monitor
  

Combination Generator Control Module

Operating Power Requirements
Source No. of Phases Wiring Configuration Voltage Frequency VA (max.)
Permanent Magnet Generator 1 PMG-A & PMG-C Min: 56V rms
Max: 300V rms
Min: 50 Hz
Max: 342 Hz
3070
3 Floating wye Min: 56V L‑L rms
Max: 300V L‑L rms
Separately Excited 1 PMG-A & PMG-C Min: 56V rms
Max: 300V rms
3 Floating wye Min: 56V L‑L rms
Max: 300V L‑L rms
3 Grounded wye
(grounded neutral)
Min: 56V L‑L rms
Max: 300V L‑L rms
3 Floating delta Min: 56V L-L rms
3 Open delta, floating Min: 56V L‑L rms
Max: 300V L‑L rms
  

Generator and Bus Voltage Sensing Values
No. of Phases Wiring Configuration Grounded Connection Available Voltage Frequency
1 VA & VC No Min: 57V rms
Max: 150V rms
Min: 20 Hz
Max: 90 Hz
3 Floating wye No Min: 99V L‑L rms
Max: 208V L‑L rms
1 Grounded wye Yes Min: 99V L‑L rms
Max: 208V L‑L rms
3 Open delta, grounded "B" phase Yes Min: 99V L‑L rms
Max: 208V L‑L rms
  

Generator Current Sensing
Type Three-phase plus cross current compensation input
Frequency 50/60 Hz
Range 1 or 5 A maximum continuous
Burden <0.1 VA per phase for metering CTs
<2.5 VA per phase for cross current inputs
3 Phase Open delta, grounded "B" phase
  

Field Output
Continuous Voltage 32, 63, or 125V DC
Continuous Current 15 A DC
10 second Forcing Voltage 50, 100, or 200V DC
10 second Forcing Current 30 A DC