Catalogs > Industrial Controls Catalog > Power & Energy Management
Power & Energy Management
SpecificationsPowermonitor 3000
| Environmental | ||
| Operating Temperature, Ambient | 1404-MX05X-000, DNT, 1404-DM | 20…+60 °C (4…+140 °F) |
| 1404-MX05X-RIO, RS232, ENT | 0…55 °C (32…132 °F) | |
| Storage Temperature | 40…+85 °C (40…+185 °F) | |
| Humidity | 5…95% non-condensing | |
| Vibration | 10…500 Hz | operational: 2 g (±0.012 in.) non-operational: 2.5 g (±0.015 in.) |
| Shock | 1/2 sine pulse, 11 ms duration |
operational: 30 g non-operational: 30 g |
| Input and Output Ratings | |
| Control Power Input | 120/240V AC 50/60Hz or 125/250V DC |
| Voltage Input Impedance | 1 MW min., 399V AC max. V1, V2, and V3 to N |
| Current Sense Inputs | Overload withstand: 15 A continuous, 200 A for 1 s Burden: 0.05 VA Impedance: 0.002 W Maximum crest factor (at 5 A): 3.0 |
| Status Inputs | Contact closure (internal 24V DC) |
| Control Relay Output | ANSI C37.90-1989 |
| KYZ Output | Solid-state KYZ = 80 mA at 240…300V DC |
| Operational Data | ||
| Nominal | Range | |
| Voltage | 347V 600V |
15…399V L-N rms 26…691V L-L rms |
| Current | 5 A | 50 mA…10.6 A rms |
| Frequency | 50 or 60 Hz | 40…75 Hz |
| Metering by model type | ||||
| M4 | M5 | M6 | M8 | |
| Accuracy | ||||
| Voltage | ±0.2% | ±0.05% | ±0.05% | ±0.05% |
| Current | ±0.2% | ±0.05% | ±0.05% | ±0.05% |
| Frequency | ±0.05 Hz | ±0.05 Hz | ±0.05 Hz | ±0.05 Hz |
| Power | ±0.4% | ±0.1% | ±0.1% | ±0.1% |
| Energy | Class 1.0 - ANSI C12.16 | Class 0.5 - ANSI C12.20 / EN 60687, Class 0.2 also available | ||
| Features | ||||
| Configurable Setpoints | 10 | 10 | 20 | 20 |
| Waveform Captures | — | — | 8 | 2 |
| Harmonic Analysis | ||||
| Order | — | — | 41st | 63rd |
| %THD | X | X | X | X |
| TIF | — | — | X | X |
| K-factor | X | X | X | X |
| Crest factor | — | — | X | X |
| IEEE 519 Compliance | — | — | X | X |
| Transient Detection | — | — | — | X |
Powermonitor 1000
| General Specifications | ||
| Dielectric withstand | Control power | 2500V |
| Voltage inputs | 2500V | |
| Current inputs | 2500V | |
| Status inputs | 2500V | |
| KYZ output | 2500V | |
| Terminal Blocks | 0.34…2.5 mm2 (22…14 AWG), 75 °C (167 °F) min. copper wire only; recommended torque 0.8 Nm (7 lbin) |
|
| Operating Temperature | -10…+60 °C (14…140 °F) | |
| Storage Temperature | -40…+85 °C (-40…+185 °F) | |
| Humidity | 5…95%, non-condensing | |
| Vibration | 2.0 g 10…500 Hz | |
| Shock | 30 g peak each axis (operating) 50 g peak each axis (non-operating) | |
| Input and Output Ratings | |
| Control Power | 85…264V AC, 47…63 Hz, 2.5 VA max. |
| Voltage Sense Inputs: V1, V2, V3 |
Input impedance: 5 MW Min. input current: 2 mA max. |
| Current Sense Inputs: I1, I2, I3, I4 |
Overload withstand: 15 A continuous, 200 A for 1/2 s Burden: 0.05 VA Impedance: 0.002 W Max. crest factor (at 5 A): 3.0 Starting current: 5 mA |
| Status Inputs | Contact closure (internal 24V DC) |
| KYZ Output | 30 mA at 240V AC/300V DC |
| Accuracy and Range | |||||||
| Parameter | Accuracy in % of Full-Scale Reading at 25 °C (77 °F) 50/60 Hz Unity Power Factor |
Nominal/ Range | |||||
| Applies to: | |||||||
| TR1 | TR2 | EM1 | EM2 | EM3 | |||
| Voltage Sense Inputs: V1, V2, V3 |
±0.5% | X | X | X | 347V/ 15…399V L‑N rms 600V/ 26…691V L‑L rms |
||
| Current Sense Input: I1, I2, I3, I4 |
±0.5% | X | X | X | 5 A/ 0.05…1.0 A rms | ||
| Frequency | ±0.05 Hz | X | X | X | 50 or 60 Hz/ 40…75 Hz | ||
| Power Functions: kW, kVA, kVAR |
EN62053-21:20 03 Accuracy Requirement Class 1★ |
X | X | ||||
| Demand Functions: kW, kVA |
X | X | |||||
| Energy Functions: kWH, kVAH |
kWh only | X | X | ||||
| Metering Update Rates | 100 ms: V, I, Hz 200 ms: Power |
X | X | X | X | X | |
| ★ Fast transient external influence tested at 2 kV. | |||||||
| Measured Parameters by model type | |||||
| Logged Parameters | TR1 | TR2 | EM1 | EM2 | EM3 |
| Voltage | X | X | X | ||
| Current | X | X | X | ||
| Frequency | X | X | X | ||
| Voltage Unbalance | X | X | X | ||
| Current Unbalance | X | X | X | ||
| Real Power [kW] | X | X | |||
| Reactive Power [kVAR] | X | X | |||
| Apparent Power [kVA] | X | X | |||
| True Power Factor | X | X | |||
| Real Energy [kWh] | X | X | X | ||
| Reactive Energy [kVARh] | X | X | |||
| Apparent Energy [kVAHh] | X | X | |||
| Real Power Demand [kW] | X | X | |||
| Reactive Power Demand [kVAR] | X | X | |||
| Apparent Power Demand [kVA] | X | X | |||
| Projected Real Power [kW ] | X | X | |||
| Projected Reactive Power [kVAR] | X | X | |||
| Projected Apparent Power [kVA] | X | X | |||
| Demand Power Factor | X | X | |||
| Logs | TR1 | TR2 | EM1 | EM2 | EM3 |
| Energy Log | X | X | X | ||
| Minimum/Maximum Log | X | X | X | X | |
| Load Factor Log | X | X | |||
| Status Log | X | X | X | X | X |
PowerPad Portable Powermonitor
| Electrical | |||
| Sampling Frequency | 256 samples per cycle | ||
| Data Storage | 4 MB partitioned for waveforms, transients, alarms, and trend recording | ||
| Voltage (TRMS) | Phase-to-Phase: 830V Phase-to-Neutral: 480V |
||
| Current (TRMS) | 240 A Clamp: 0…6 A/120 A or 0…240 A 1000 A AC/1400 A DC Clamp: 0…1000 A AC, 0…1400 A DC |
1200 A Clamp: 0…1200 A 6500 A Clamp: 0…6500 A★ |
|
| Measurement | Range | Resolution | Accuracy |
| Single-Phase RMS Voltages | 6…480V | 0.1V | ±0.5% ±2cts |
| Phase-to-Phase RMS Voltages | 10…830V | 0.1V | ±0.5% ±2cts |
| Single-Phase Peak Voltages | 6…680V | 1V | ±(1% ±5cts) |
| Phase-to-Phase Peak Voltages | 10…1360V | 1V | ±(1% ±5cts) |
| Frequency (Hz) | 40…69 Hz | 0.01 Hz | ±0.01 Hz |
| DC Voltage Component | 6…650V | 0.1V | ±1% ±2cts |
| Current Probes (Arms) MN Clamp SR Clamp AmpFlex™ Probe |
0…240 A 0…1200 A 10…6500 A |
0.1 A 0.1 A; 1…1000 A 0.1 A; 1…1000 A |
±(0.5% + 2 cts) ±(0.5% + 2 cts) ±(0.5% + 1 A) |
| Active (Real) Power (kW) | 0…9999 kW | Four digits (10 000ct) | ±1% ±1ct @ PF ³ 0.8 |
| Reactive Power (kVAR) | 0…9999 kVAR | Four digits (10 000ct) | ±1% ±1ct @ PF £ 0.8 |
| Apparent Power (kVA) | 0…9999 kVA | Four digits (10 000ct) | ±1% ±1ct |
| Power Factor (PF & DPF) | -1.000…1.000 | 0.001 | ±(1.5% + 0.01) |
| Active Energy (kWh) | 0…9999 MWh | Four digits (10 000ct) | ±1% ±1ct @ PF ³ 0.8 |
| Reactive Energy (kVARh) | 0…9999 MVARh | Four digits (10 000ct) | ±1% ±1ct @ PF £ 0.8 |
| Apparent Energy (kVAh) | 0…9999 MVAh | Four digits (10 000ct) | ±1% ±1ct |
| Unbalance (V & A) | 0…100% | 0.1% | ±1% ±1ct |
| Phase Angles (V-A, A-A, V-V) | -179…180° | 1° | ±2° ±1ct |
| Harmonics (1…50) F=40…69Hz (V ³ 50V, A > Inom/100 |
0…999% | 0.1% | ±1% + 5ct |
| Total Harmonic Distortion (V & A) | 0…999% | 0.1% | ±1% + 5ct |
| K-factor (Akf) | 1…99.99 | 0.01 | ±5% ±1ct |
| Flicker (Pst) | 0.00…9.99 | 0.01 | |
| Power Source | 9.6V NiMH rechargeable battery pack AC supply: 110/230VAC ±20% (50/60Hz) |
||
| Battery Life | 6 hours with display on; £96 hrs with display off (record mode) | ||
| Environmental | |||
| Operating Temperature | 0…50 °C (32…122 °F) | ||
| Storage Temperature | -20…+50 °C (-4…+122 °F) | ||
| Mechanical | |||
| Display | 1/4 VGA (320 x 240) color LCD | ||
| Dimensions | 240 x 180 x 55 mm (9.5 x 7 x 2 in.) | ||
| Weight | 2.1 kg (4.6 lb) | ||
| Safety | |||
| Safety Rating | EN 61010-1, 600V Cat. III, Pollution Degree 2 | ||
| Double Insulation | Yes | ||
| CE Mark | Yes | ||
| ★ Crest Factor at 6500 A = 1 | |||
Current Transformers
| Core Type | Split or solid |
| Current Ratio Range | 50:5…6000:5 |
| Burden Range | 1…200 VA |
| Window Sizes | Round Window: 1.00", 2.5", 1.13", 3.25", 1.47", 5.75", 2.31", 6.31", 8.25" Rectangular Window: 2.00 x 5.5", 0.75 x 0.75", 4.5 x 4.5", 1.3 x 1.6", 1.42 x 1.53", 1.3 x 2.15", 2.75 x 2.7", 2 x 3.5", 2.6 x 6.25" |
| Certifications | UL, CSA |
| Standards | ANSI/IEEE C57.13, IEC 44-1 |
RSPower Software
| System Hardware Requirements | |
| Compatible Microprocessor | Pentium 4 or P4 |
| RAM | 256 MB |
| Hard Disk | 100 MB of available space |
| Drive | CD-ROM/DVD-ROM |
| Disk Drive | 3.5 inch, 1.44 MB |
| Operating System | Windows 2000, Windows 2000 Server, Windows XP, or Windows Server 2003 |
| Microsoft .NET Framework 2.0 | |
| Application | Adobe Acrobat Reader |
| Communication Type | RSLinx Classic 2.51 OEM or higher (if not bundled with communications drivers) |
| Communication Interface | Appropriate communications interface to the Powermonitor |
| Devices | Bulletin 1400 Powermonitor, 1403 Powermonitor II, 1404 Powermonitor 3000, 1408 Powermonitor 1000 |
| External Connections | Serial, Ethernet, ControlNet™, DeviceNet™ or Remote I/O connection to the power monitor |
Combination Generator Control Module
| Operating Power Requirements | |||||
| Source | No. of Phases | Wiring Configuration | Voltage | Frequency | VA (max.) |
| Permanent Magnet Generator | 1 | PMG-A & PMG-C | Min: 56V rms Max: 300V rms |
Min: 50 Hz Max: 342 Hz |
3070 |
| 3 | Floating wye | Min: 56V L‑L rms Max: 300V L‑L rms |
|||
| Separately Excited | 1 | PMG-A & PMG-C | Min: 56V rms Max: 300V rms |
||
| 3 | Floating wye | Min: 56V L‑L rms Max: 300V L‑L rms |
|||
| 3 | Grounded wye (grounded neutral) |
Min: 56V L‑L rms Max: 300V L‑L rms |
|||
| 3 | Floating delta | Min: 56V L-L rms | |||
| 3 | Open delta, floating | Min: 56V L‑L rms Max: 300V L‑L rms |
|||
| Generator and Bus Voltage Sensing Values | ||||
| No. of Phases | Wiring Configuration | Grounded Connection Available | Voltage | Frequency |
| 1 | VA & VC | No | Min: 57V rms Max: 150V rms |
Min: 20 Hz Max: 90 Hz |
| 3 | Floating wye | No | Min: 99V L‑L rms Max: 208V L‑L rms |
|
| 1 | Grounded wye | Yes | Min: 99V L‑L rms Max: 208V L‑L rms |
|
| 3 | Open delta, grounded "B" phase | Yes | Min: 99V L‑L rms Max: 208V L‑L rms |
|
| Generator Current Sensing | |
| Type | Three-phase plus cross current compensation input |
| Frequency | 50/60 Hz |
| Range | 1 or 5 A maximum continuous |
| Burden | <0.1 VA per phase for metering CTs <2.5 VA per phase for cross current inputs |
| 3 Phase | Open delta, grounded "B" phase |
| Field Output | |
| Continuous Voltage | 32, 63, or 125V DC |
| Continuous Current | 15 A DC |
| 10 second Forcing Voltage | 50, 100, or 200V DC |
| 10 second Forcing Current | 30 A DC |
