General Functions
Bulletin 900-TC8
|
USB-Serial Conversion Cable (900-CPOEM1)
|
| Communications Parameter | Set-up Value |
| Unit No. | .01 |
| Baud Rate | 38.4 (kbps |
| Data Length | 7 (bits) |
| Stop Bits | 2 |
| Parity | Even |
Bulletin 900-TC16
|
Bulletin 900-TC32
|
Cat. No. 900-TC8, 900-TC16, and 900-TC32 Input Ranges
|
⋆ Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W:W5Re/W26Re, ASTM E998-1990
PLII: According to Platinel ll electromotive force charts from BASF (previously Engelhard)
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC 751
§ The non-contact temperature sensor must be configurable for type K thermocouple output within either of the four specified ranges. For example, an OMRON
ES1A or Calex EL Series (Convir) infrared sensor.
♣ Shaded setting number indicates default setting for thermocouple or platinum RTD type 900-TC8xGT or 900-TC16xGT controllers.
Bulletin 900-TC8 and 900-TC16
Controllers with Analog Inputs ⋆
| Input Type | Current | Voltage | |||
| Input Specification | 4...20 mA | 0...20 mA | 1...5V DC | 0...5V DC | 0...10V DC |
| Setting Range | Usable in the following ranges by scaling: -1999...9999, -199.9...999.9, -19.99...99.99 or -1.999...9.999 |
||||
| Setting Number | 0 | 1 | 2 | 3 | 4 |
| ⋆ Shaded area is the default setting for analog input type 900-TC8xAB or 900-TC16xAB controllers. | |||||
⋆ Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC 751
§ The non-contact temperature sensor must be configurable for type K thermocouple output within either of the four specified ranges. For example, an OMRON ES1A or Calex EL Series (Convir) infrared sensor.
♣ Shaded setting number indicates default setting for thermocouple (900-TC32xT) or platinum RTD (900-TC32xP) type 900-TC32 controllers.
Bulletins 900-TC8, 900-TC16, and 900-TC32⋆
| Technical/Control Ratings | ||||
| Supply Voltage (Line) | 100…240V AC, 50/60 Hz | 24 V AC, 50/60 Hz / 24 V DC | ||
| Operating Voltage Range (Line) | 85…110% of rated supply voltage | |||
| Power Consumption |
900-TC8 | 10 VA | 5.5 VA / 4 W | |
| 900-TC16 | 7.5 VA | 5 VA / 3 W | ||
| 900-TC32 | 5.5 VA | 3 VA / 2 W | ||
| Temperature Input | Thermocouple | J, K, T, E, L, U, N, R, S, B, W and PL11 (controller applies cold junction compensation) | ||
| Platinum Resistance Thermometer | Pt100, JPt100 (controller RTD excitation current: approx. 1 mA) 2- or 3-wire configuration | |||
| Non-Contact Temperature Sensor | 10…70 °C, 60…120 °C, 115…165 °C, 140…260 °C | |||
| MIllivolt Input | 0…50 mV | |||
| 900-TC8 and 900-TC16 | Analog Voltage Input | 1...5V DC, 0...5V DC and 0...10V DC | ||
| Analog Current Input | 4...20 mA and 0...20 mA | |||
| Analog Input Impedance | Current Input: | 150 W max. |
||
| Voltage: | 1 MW max. | |||
| Control Output |
Electromechanical Relay output |
900-TC8 | SPST-NO, 250V AC @ 5 A, 30V DC @ 10 A (max. resistive load), electrical life: 100 000 operations, min. load 5V, 10 mA | |
| 900-TC16 | SPST-NO, 250V AC @ 3 A, 30V DC @ 10 A (max. resistive load), electrical life: 100 000 operations, min. load 5V, 10 mA | |||
| 900-TC32 | SPST-NO, 250V AC @ 2 A, 30V DC @ 2 A (max. resistive load), electrical life: 100 000 operations | |||
| Voltage output (SSR compatible) |
900-TC8 | 12V DC +15%/-20% (PNP), max. load current: 40 mA, with current limit protection Output 2 max. load current 21 mA | ||
| 900-TC16 | 12V DC ±15% (PNP), max. load current: 21 mA, with current limit protection | |||
| 900-TC32 | 12V DC (PNP), max. load current: 21 mA, with current limit protection | |||
| Triac output (AC only) | 900-TC8 | SPST-No, 250V AC @ 3 A (max. resistive load)♣ | ||
| 900-TC16 | SPST-NO, 250V AC @ 3 A (max. resistive load)♣ | |||
| 900-TC32 | NA | |||
| Analog Output | 900-TC8 | DC: 4...20 mA, 0...20 mA, max. load 600 ohms, resolution 10,000 | ||
| 900-TC16 | DC: 4...20 mA, 0...20 mA, max. load 600 ohms, resolution 10,000 | |||
| 900-TC32 | NA | |||
| Auxiliary Output | 900-TC8, 900-TC16 | SPST-NO, 250V AC @ 3 A, 30V DC @ 5 A (max. resistive load), electrical life: 100 000 operations, min. load 5V, 10 mA | ||
| 900-TC32 | SPST-NO, 250V AC @ 2 A, 30V DC @ 2 A (max. resistive load), electrical life: 100 000 operations, min. load 5V, 10 mA | |||
| Event Input § | Contact | ON: 1K W (max.) OFF: 100K W (min.) |
||
| Non-contact | ON: Voltage Drop 1.5V (max.) OFF: Leakage current 0.1 mA (max.) |
|||
| Control Method | ON/OFF control or 2-PID (auto-tune and self-tune) | |||
| Configuration Method | Digital configuration using front panel keys or 900Builder Lite software for 900-TC8x and 900-TC16x, and 900-TC32x | |||
| Indication Method | 11-segment digital display and individual indicators: Bulletin 900-TC8 and 900-TC16, and 900-TC32. | |||
| Character Height |
900-TC8 | Process Value Display: 11.8 mm; Set Point Display: 8.1 mm; MV Display: 5.8 | ||
| 900-TC16 | Process Value Display: 11 mm; Set Point Display: 6.5 mm | |||
| 900-TC32 | Process Value Display: 7.5 mm; Set Point Display: 3.6 mm | |||
| Indication Accuracy |
Thermocouple | ±0.3 % of indicated value or ±1 °C, whichever greater ±1 digit max. | ||
| Platinum Resistance Thermometer (RTD) | ±0.2 % of indicated value or ±1 °C, whichever greater ±1 digit max. | |||
| Analog Input (900-TC8, 900-TC16) | ±0.2% FS±1 digit max. | |||
| CT Input (900-TC8, 900-TC16) | ±5% FS±1 digit max. | |||
| Affect of Signal Source Resistance | Thermocouple: 0.1°C/ohm max. (100 ohm max.) Platinum RTD: 0.1°C/ohm max. |
|||
| ⋆ Unless noted, specifications apply to Bulletins 900-TC8, 900-TC16, and 900-TC32. | ||||
| The indication of K thermocouples in the 200…+1300 °C range, and T and N thermocouples at a temperature of 100 °C or less, and U and L thermocouples at any temperature is ±2 °C ±1 digit maximum. The indication of B thermocouples at a temperature of 400 °C or less is not specified. The indication of R and S thermocouples at a temperature of 200 °C or less is ±3 °C ±1 digit maximum. | ||||
| § Applies to 900-TC8 or 900-TC16. | ||||
| ♣ Electrical life: 1 million operations, Load Power Supply voltage: 75 to 250V AC (NA DC), Minimum Load: 5V, 10 mA, Leakage Current:5 mA at 250V AC 60 Hz. | ||||
| ⁵900-TC8 and 900-TC16, 0.1°C/ohm max. for all thermocouple types, 900-TC32,B, R, and S sensors: 0.2° C/ohm max. (100 ohm max.) | ||||
Bulletins 900-TC8, 900-TC16, and 900-TC32, Continued
| Technical/Control Ratings | |
| Influence of Ambient Temperature∇ and Line Voltage∇ | |
| Hysteresis (Controller with Temperature Inputs) | 0.1…999.9 EU (in units of 0.1 EU)♦ |
| Hysteresis (Controller with Analog Inputs) | 0.01 to 99.99% FS (in units of 0.01% Full Scale) |
| Proportional Band (P) Controller with Temperature Inputs | 0.1…999.9 EU (in units of 0.1 EU)♦ |
| Proportional Band Controller with Analog Inputs | 0.1 to 999.9% FS ( in units of 0.1% FS) |
| Integral Time (I) | 0…3999 s (in units of 1 s) |
| Derivative Time (D) | 0…3999 s (in units of 1 s)♠ |
| Control Period | 0.5, 1…99 s (in units of 1 s) |
| Manual Reset Value | 0.0…100.0% (in units of 0.1%) |
| Alarm Setting Range | 1999…+9999 (decimal point position depends on input type) |
| Sampling Period | 250 ms |
| Other Functions | According to Controller model |
| ♦ Engineering Unit (EU) is used as the unit after scaling. For a temperature sensor, the EU is °C or °F. | |
| ♠ When Robust Tuning (RT) is on, the differential is is 0.0... 999.9 in units of 0.1 sec. | |
| ∇ Conditions: Ambient temperature: -10°C to 23°C to 55°C. Voltage Range: -15% to +10% of rated voltage. | |
| General/Environmental Ratings | ||
| Weight (includes carton) | 900-TC8 | Approx. 360 g (12.7 oz.) with mounting bracket |
| 900-TC16 | Approx. 160 g (5.6 oz.) with mounting bracket | |
| 900-TC32 | Approx. 100 g (3.5 ounces) | |
| 900-TC8232, COM, EIM | Approx. 20 g (0.7 ounces) | |
| 900-TC16COM, EIM | Approx. 35 g (1.2 ounces) | |
| Ambient Temperature | 10…+55 °C (with no condensation or icing) | |
| Ambient Humidity | 25…85% | |
| Storage Temperature | 25…+65 °C (with no condensation or icing) | |
| Insulation Resistance | 20 MW min. (at 500V DC) | |
| Dielectric Strength | 2300V AC, 50 or 60 Hz for 1 min. (between terminals with different charge) | |
| Maximum Operating Vibration | 10…55 Hz, 20 m/s2 (2 G) for 10 minutes each in X, Y, and Z directions | |
| Maximum Shock Operating | 100 m/s2 (10 G), 3 times each in X, Y, and Z directions. | |
| Protective Structure | Front panel:IP66 (IEC61010-1) Rear case: IP20, Terminals: IP00 |
|
| Installation Environment | Installation category II, pollution class 2 (IEC 61010-1 compliant) | |
| Memory Protection | EEPROM (non-volatile memory) (number of writes: 100 000) | |
| EMC | EMI | EN 61326 |
| Radiated Interference Electromagnetic Field Strength | EN 55011 Group 1, class A | |
| Noise Terminal Voltage | EN 55011 Group 1, class A | |
| EMS | EN 61326 | |
| ESD Immunity | EN 61000-4-2 | |
| Electromagnetic Field Immunity | EN 61000-4-3 | |
| Burst Noise Immunity | EN 61000-4-4 | |
| Conducted Disturbance Immunity | EN 61000-4-6 | |
| Surge Immunity | EN 61000-4-5 | |
| Power Frequency Magnetic Field Immunity | EN 61000-4-8 | |
| Voltage Dip/Interrupting Immunity | EN 61000-4-11 | |
| Conformed Standards | Conforms to EN61010-1 (IEC 61010-1) and VDE 0106/part 100 (finger protection) when the terminal cover is installed, Pollution Level 2, Overcurrent Category II | |
| The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications configuration function group. | ||
| Communications | ||
| Transmission Path Connection | RS485 Multiple points | |
| Communications Method ⋆ | 900-TC8 | RS-232C or RS-485 (2-wire, half duplex) |
| 900-TC16 | RS-485 (2-wire, half duplex) | |
| 900-TC32 | RS-485 (2-wire, half duplex) | |
| Synchronization Method | Start-stop synchronization | |
| Protocol | 900TC proprietary or Modbus RTU Slave | |
| Baud Rate | 1200/2400/4800/9600/19 200, 38 400, 57 600 bps | |
| Data Bit Length | 7 or 8 bits | |
| Stop Bit Length | 1 or 2 bits | |
| Error Detection | Vertical Parity (None, even, odd) BCC or with ModBus CRC-16 | |
| Flow Control | Not available | |
| Interface | 900-TC8 ⋆ | RS-485/RS-232C |
| 900-TC16 ⋆ | RS-485 | |
| 900-TC32 ⋆ | RS-485 | |
| Retry Function | Not available | |
| Communications Response Wait Time | 0...99 ms (Default: 20 ms) | |
| Communications Buffer | 217 bytes | |
| ⋆ RS-232C communications is only supported for Bulletin 900-TC8 (Cat. No. 900-TC8232 option board installed). All controllers support RS-485 communications (32 linked/networked devices) by appropriate option unit or correct controller catalog number. | ||
| The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications configuration function group. | ||
⋆ The temperature controller is mounted on the flat surface of an enclosure that is rated and marked "Type 4X for Indoor Use Only"
| Current Transformer (Sold Separately) Ratings (Use with Bulletins 900-TC8 and 900-TC16 Only) | ||
| Dielectric Strength | 1000V AC (1 min.) | |
| Vibration Resistance | 50 Hz 98 m/s2 (10 G) | |
| Weight (includes carton) | 900-CT1 | Approx. 19 g (0.67 ounces) |
| 900-CT2 | Approx. 65 g (2.3 ounces) | |
| Heater Burnout and Heater Short-Circuit and overcurrent Failure Alarm (Use with Bulletins 900-TC8 and 900-TC16 Only—Current Transformer Required) | ||
| Max. Heater Current | Single-Phase AC | 50 A |
| Input Current Readout Accuracy | ±5%FS ±1 digit max. | |
| Alarm Setting Range | 0.1…49.9 A (0.1 A units) § | |
| Min. Detection ON or OFF Time | 100 ms ♣ | |
| Approved Standards | ||
| Standards | UL 61010-1, CSA C22.2 No. 1010.1 | |
| ♣ When the heater ON/OFF time is less than 100 ms, heater current cannot be measured and the heater burnout alarm (ON) or SSR failure alarm (OFF) will not activate. | ||
| § When the configured value of the alarm is 00 A, the alarm will always be OFF for heater burnout and ON for SSR failure. When the configured value is 50.0 A, the heater burnout alarm will always be ON and the SSR failure will be OFF. | ||
| USB-Serial Cable (900-CPOEM1) | |
| Applicable OS | Windows 2000, XP or Vista |
| Applicable Configuration Software | 900Builder Lite |
| Applicable Models | Cat. No. 900-TC8, 900-TC16, and 900-TC32 |
| USB Interface Standard | Conforms to USB Speficiation 1.1 |
| DTE Speed | 38400 bps |
| Connector Specifications | Computer: USB (type A plug) Temperature Controller : 4-pin Serial |
| Power Supply | Bus Power (Supplied from USB host controller) |
| Power Supply Voltage | 5V DC |
| Current Consumption | 70 mA |
| Ambient Operating Temperature | 0...55 °C (with no condensation or icing) |
| Ambient Operating Humidity | 10%...80% |
| Storage Temperature | -20...-60 °C (with no condensation or icing) |
| Storage Humidity | 10%...80% |
| Altitude | 2000 m max. |
| Weight | Approx. 100 g |