Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Single Loop Temperature/Heater Controllers > Bulletin 900-CONV
Bulletin 900-CONV
| Introduction | Standards Compliance and Certifications | Product Selection | Specifications | Approximate Dimensions | External Connections | Bulletin 900-CONV Front Display/Operations |
| Technical/Control Ratings | ||||
| Communications Method | Master Device (PC) | RS-232C | ||
| Slave Device (900-TCx Controller) | RS-485 (2-wire, half duplex) (selectable) | |||
| Synchronization Method | Start-stop synchronization | |||
| Master Device (PC) | RS-232C Interface | Max. transmission distance | 15 m | |
| Max. number of connectable units | 1 unit | |||
| USB Interface | Max. transmission distance | 5 m or when the total time (hub delay time plus the cable delay time) is less than or equal to 70 ns | ||
| Max. number of connectable slave units | 1 unit | |||
| USB Standard | V1.1 | |||
| Slave Device (900-TCx) RS-485 Interface | Max. transmission distance |
500 m | ||
| Max. number of connectable slave units |
31 units (for multi-drop connection) | |||
| Baud Rate | 1200/2400/4800/9600/19 200/38 400 bps (Default setting: 9600) | |||
| Data Bit Length | 7 or 8 bits (Default setting: 7) | |||
| Stop Bit Length | 1 or 2 bits (Default setting: 2) | |||
| Communications Parity | None, even, odd (Default setting: Even) | |||
| Echoback Selection | Echoback: With/without (Default setting: Without) | |||
| Selection Switch Response Delay | Approx. 30 ms | |||
| General/Environmental Ratings | ||||
| Supply Voltage | 100…240V AC, 50/60 Hz | 24 V AC, 50/60 Hz or 24 V DC | ||
| Operating Voltage Range | 85…110% of rated supply voltage | |||
| Power Consumption | 5 VA max. | 24 V AC: 3 VA max., 24 V DC: 3 W max. | ||
| Ambient Temperature | RS-232C | 10…+55 °C (with no icing) | ||
| USB | 0...+55 °C (with no icing) | |||
| Ambient Humidity | 25…85% (with no condensation) | |||
| Storage Temperature | 20…+65 °C | |||
Specifications, Continued
| General/Environmental Ratings | |||
| Insulation Resistance | 20 MW min. measured at 500V DC between the following: External terminals « casing RS-232C terminals « RS-485 terminals power supply terminals |
||
| Isolation Method | Communications | Phototransistor coupler | |
| Power supply | Isolating transformer | ||
| Dielectric Strength | 1,500 V AC for 1 min. between the external terminal and case, and between the RS-232C RS-485 block power supply terminal | ||
| Noise Immunity | 500 V AC for 1 min. between the RS-232C/USB block and RS-485 block | ||
| Vibration (Max.) | 10…55 Hz, 0.5 mm single amplitude for 10 min. each in X, Y, and Z directions (1 G) | ||
| Shock (Max.) | 98 m/s2 (10 G), 3 times each in X, Y, and Z directions | ||
| Weight | Approx. 150 g | ||
| Enclosure Rating | Front Panel Operation Parts | Conforms to IEC standards, equivalent to IP20 (when terminal cover mounted) ⋆ | |
| Terminals | Equivalent to VDE 0106/100 (when terminal cover mounted) ⋆ | ||
| Memory Protection | No protective functions (communications data is not protected for power interruptions during communications) | ||
| EMC | Radiated Emission | EN61326 class A | |
| Conducted Emission | EN61326 class A | ||
| Immunity ESD | EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3) | ||
| Immunity RF-Interference | EN61000-4-3: 10V/m (amplitude modulated, 80 MHz…1 GHz) (level 3) 10V/m (pulse modulated, 900 MHz) |
||
| Immunity Conducted Disturbance | EN61000-4-6: 10V (0.15…80 MHz) (level 3) | ||
| Immunity Burst | EN61000-4-3: 2 kV power-line (level 3); 2 kV I/O signal-line (level 4) | ||
| Conformity to Standards | UL508, CSA C22.2 No. 14-95 Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC 61010-1) Conforms to VDE 0106/part 100 (Finger Protection), when the terminal cover is mounted. |
||
| ⋆ When USB communication is used, the cover must be removed | |||