Single Loop Temperature/Heater Controllers

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Single Loop Temperature/Heater Controllers > Bulletin 900-CONV

Bulletin 900-CONV

Introduction Standards Compliance and Certifications Product Selection Specifications Approximate Dimensions External Connections Bulletin 900-CONV Front Display/Operations
External Connections

RS-485 Connection

Click to enlarge - 900CONV-21-1


⋆ If RS-485 is selected as the communications method (i.e., pin 9 of the DIP switch is set to OFF), terminals 8 and 9, and terminals 11 and 12 are connected internally.
‡ A 100…240 V AC, 24 V AC, or 24 V DC (not polarity sensitive) input power supply is required.


Function Terminal Number Name Signal Direction Explanation
For connecting the operating power supply 1 and 4 PWR 100…240V AC or 24 V AC/DC model
Connection terminals for RS-232C communications with master device (DIP switch pin 8: OFF) 3 SG Connect to signal ground.
5 SD Input Receives data from SD of the master device.
6 RD Output Sends data to RD of the master device.
Used for RS-485 communications with slave device (DIP switch pin 9: OFF) 8 RDA (–) Input/
output
SD and RD for RS-485 (cold side)
Terminals 8 and 9 are connected internally when pin 9 of the DIP switch is set to OFF.
9 SDA (–)
11 RDB (+) Input/
output
SD and RD for RS-485 (hot side)
Terminals 11 and 12 are connected internally when pin 9 of the DIP switch is set to OFF.
12 SDB (+)
  
Note:Terminals 2 and 10 are not used.

Connection to an RS-232C Master Device

Set the same communications conditions (baud rate, stop bits, data length, and parity) for the master device, the Interface Converter, and slave devices.

Click to enlarge - 900conv-21-3


§ With RS-485 communications, connect a terminating resistance (120W, 1/2 W recommended) to both ends of the communications link/network.
♣ The Bulletin 900-TCx communications number must be set.
∆ A pre-fabricated 3 m RS-232 cable with a 9-pin female D-shell connector on one end and three flying leads at the other is available from Allen-Bradley (Cat. No. 900-CP1X).
♦ RS-485 allows connecting 32 devices.
♠ Use a commercially available USB cable
∇ To use the USB mode requires the download of "free" software into your PC. This software can be found at: http://ab.rockwellautomation.com/Sensors-Switches/Temperature-Sensors/900Builder-Lite-Temperature-Controller-Software


Terminal Specifications

Make sure to check the input and output specifications for the signal pins of connected devices before connecting the terminals.