Bulletin 700-SK Slim Line Relay
| Product Overview |
|
Bulletin 700-SK — Slim Line Relay
- High-response speed models
- Input sensor module to sllow high voltage 100…240V AC or 12…24V DC sensor
- Interface to low voltage (logic) device such as a PC output module for typical SSR applications
- LED indicator
- Input modules and output modules can be used with the Bulletin 700-HN121 or 700-HN221 sockets
Standards Compliance and Certifications
- See Specifications.
Product Selection
| Build a Catalog Number |
| Input/Sensor Module | ||||||
| Input-to-Output Isolation Method | Status Indicator | Response Frequency | Logic Level | Rated Input Sensor Voltage | Cat. No. | |
| Supply Voltage | Supply Current | |||||
| Photocoupler | Yes | 10 Hz | 4…32V DC | 0.1…100 mA | 100…240V AC⋆ | 700-SKICA18 |
| 1 kHz | 12…24V DC | 700-SKICZ24 | ||||
| Output/SSR Module | |||||
| Input-to-Output Isolation Method | Zero Cross Function | Status Indicator | Output (Load) Max. Continuous Current and Rated Voltage Range | Rated Input Control Voltage | Cat. No. |
| Phototriac | Yes | Yes | 2 A @ 100…240V AC⋆ | 5…24V DC | 700-SKOZ2Z25 |
| No | 700-SKON2Z25 | ||||
| Photocoupler | Not Applicable | 2 A @ 5…48V DC | 700-SKOC2Z25 | ||
| 1.5 A @ 48…200V DC | 700-SKOC1Z25 | ||||
| ⋆ 47…63 Hz | |||||
Accessories
Specifications
Input Sensor Module
| Input Sensor Ratings | |||||
| Cat. No. | Rated Input Voltage | Max. Operating Input Voltage Range | Input Current | Pick-up Voltage | Drop-out Voltage |
| 700-SKICZ24 | 12…24V DC | 6.6…32V DC | 8 mA max. | 6.6V DC max. | 3.6V DC min. |
| 700-SKICA18 | 100…240V AC | 60…264V AC | 15 mA max. | 60V AC max. | 20V AC min. |
| Output Logic Ratings | ||
| Cat. No. | Logic Level Supply Voltage | Logic Level Supply Current Draw |
| 700-SKICZ24 | 4…32V DC | 0.1…100 mA |
| 700-SKICA18 | ||
| Characteristics | |||
| Description | Cat. No. 700-SKICA18 | Cat. No. 700-SKICZ24 | |
| Pick-up time | 20 ms max. | 0.1 ms max. | |
| Drop-out time | 20 ms max. | 0.1 ms max. | |
| Response frequency | 10 Hz | 1 kHz | |
| Output ON voltage drop | 1.6V max. | ||
| Leakage current | 5 mA max. | ||
| Output VDRM, VCEO (V) | 80 (ref. value) | 80 (ref. value) | |
| Output di/dt (A/uS) | — | — | |
| Output dv/dt (V/uS) | — | — | |
| Output I2t (A2S) | — | — | |
| Output Tj (°C) Max. | 150 | 150 | |
| Insulation Resistance | 100 MW min. between input and output | ||
| Dielectric Strength | 4000V AC, 50/60 Hz for 1 min between input and output | ||
| Vibration Resistance (Max.) | 10…55 Hz, 1.5 mm double amplitude (10 G) | ||
| Shock Resistance (Max.) | 1000 m/s2 (100 G) | ||
| Ambient Temperature | Operating | 30…+80 °C (22…+176 °F) with no icing or condensation | |
| Storage | 30…+100 °C (22…+212 °F) with no icing or condensation | ||
| Standards Compliance | UL 508, CSA C22.2 No. 14, EN/IEC 60950 | ||
| Certifications | cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified | ||
| Ambient humidity Operating | 45…85% (no condensation) | ||
| Weight | Approx. 18 g | ||
Output SSR Module
| Control/Input Ratings | ||||||
| Cat. No. | Rated Control Voltage | Max. Operating Control Voltage Range | Max. Reverse Control Voltage |
Impedance⋆ | Pick-up Voltage |
Drop-out Voltage |
| 700-SKOZ2Z25 | 5…24V DC | 4…32V DC | -32V DC | 15 mA max. at 25 °C (77 °F) |
4V DC max. |
1V DC min. |
| 700-SKON2Z25 | ||||||
| 700-SKOC2Z25 | 8 mA max. | |||||
| 700-SKOC1Z25 | ||||||
| Load/Output Ratings | |||||
| Cat. No. |
Rated Load Voltage | Maximum Load Voltage Range |
Continuous Load Current (Resistive) [A] | Max. Inrush Current | |
| Min. | Max.§ | ||||
| 700-SKOZ2Z25 | 100…240V AC | 75…264V AC | 0.05 | 2 | 30 A (@50/60 Hz, 1 cycle) |
| 700-SKON2Z25 | |||||
| 700-SKOC2Z25 | 5…48V DC | 4…60V DC | 0.1 | 2 | 8 A (10 ms) |
| 700-SKOC1Z25 | 48…200V DC | 40…200V DC | 0.1 | 1.5 | 8 A (10 ms) |
| ⋆ With a constant current input system. SSR impedance varies with a change in input voltage. | |||||
| If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the Inrush Current Resistivity graphs on Inrush Current Resistivity for more details. | |||||
| § Refer to "Load Current vs. Ambient Temperature Characteristics" graphs on Inrush Current Resistivity for additional details. | |||||
Output Module, Continued
| Characteristics | |||||
| Description | Cat. No. 700-SKOZ2Z25 | Cat. No. 700-SKON2Z25 | Cat. No. 700-SKOC2Z25 | Cat. No. 700-SKOC1Z25 | |
| Load Switching Method/Device | Triac | Transistor | |||
| Pick-up Time | 1/2 cycle of load power source cycle time⋆ + 1 ms max. | 1 ms max. | |||
| Drop-out Time | 1/2 of load power source cycle time⋆ + 1 ms max. | 2 ms max. | |||
| Response Frequency | 20 Hz | 100 kHz | |||
| Output ON Voltage Drop | 1.6V max. | 2.5V max. | |||
| Leakage Current | 1.5 mA max. | 1 mA max. | |||
| Output VDRM, VCEO (V) | 600 (ref.value) | 600 (ref.value) | 80 (ref.value) | 400 (ref.value) | |
| Output di/dt (A/uS) | 30 | 30 | — | — | |
| Output dv/dt (V/uS) | 300 | 300 | — | — | |
| Output I2t (A2S) | 10.4 | 10.4 | — | — | |
| Output Tj (°C) Max. | 125 | 125 | 150 | 150 | |
| Insulation Resistance | 100 MW min. between input and output | ||||
| Dielectric Strength | 4000V AC, 50/60 Hz for 1 min between input and output | ||||
| Vibration Resistance (Max.) | 10…55 Hz, 1.5 mm double amplitude (10 G) | ||||
| Shock Resistance (Max.) | 1000 m/s2 (100 G) | ||||
| Ambient Temperature | Operating | 30…+80 °C (22…+176 °F) with no icing or condensation | |||
| Storage | 30…+100 °C (22…+212 °F) with no icing or condensation | ||||
| Standards Compliance | UL 508, CSA C22.2 No. 14, EN/IEC 60950 | ||||
| Certifications | cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified | ||||
| Ambient Humidity Operating | 45…85% (no condensation) | ||||
| Weight | Approx. 18 g | ||||
| ⋆ 60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms. | |||||
Load Current vs. Ambient Temperature Characteristics
|
Inrush Current Resistivity
|
Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
Approximate Dimensions
All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes.
Note:The input module ( Bul. 700-SKI) and output module (Bul. 700-SKO) are compatible with the Cat. No. 700-HN121 socket.
|
Application Considerations of Bulletin 700-SK
Connection
For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life)
Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load.
For additional details applying solid-state relays, refer to pub. 700-AT001A*, Solid-State Relay Application Guide.