Bulletin 700-SK "Slim Line" Relay

Product Overview


Click to enlarge - GenInfo-7-3


Bulletin 700-SK


Standards Compliance and Certifications


Product Selection

Build a Catalog Number


Input/Sensor Module
Input-to-Output Isolation Method Status Indicator Response Frequency Logic Level Rated Input Sensor Voltage Cat. No.
Supply Voltage Supply Current
Photocoupler Yes 10 Hz 4…32V DC 0.1…100 mA 100…240V AC¬  700-SKICA18
1 kHz 12…24V DC 700-SKICZ24
  

Output/SSR Module
Input-to-Output Isolation Method Zero Cross Function Status Indicator Output (Load) Max. Continuous Current and Rated Voltage Range Rated Input Control Voltage Cat. No.
Phototriac Yes Yes 2 A @ 100…240V AC¬  5…24V DC 700-SKOZ2Z25
No 700-SKON2Z25
Photocoupler Not Applicable 2 A @ 5…48V DC 700-SKOC2Z25
1.5 A @ 48…200V DC 700-SKOC1Z25
  
¬ 47…63 Hz

Accessories

  Description Pcs./Pkg. Cat. No.
Click to enlarge - 700SK-59-1 Screw Terminal Socket — Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1-pole, Bulletin 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip. 10 700-HN121
Click to enlarge - 700-HN221_4c Screw Terminal Socket — Panel or DIN Rail Mounting 5-blade miniature socket with 16 A rating for use with 1-pole, Bulletin 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories. 10 700-HN221
Click to enlarge - 700SA-32-4 DIN (#3) Symmetrical Rail
35 x 7.5 x 1 m
10 199-DR1
Click to enlarge - 700SA-32-5 Pre-Printed Identification Tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N40
Blank Identification Tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N41
  

Specifications

Input Sensor Module

Input Sensor Ratings
Cat. No. Rated Input Voltage Max. Operating Input Voltage Range Input Current Pick-up Voltage Drop-out Voltage
700-SKICZ24 12…24V DC 6.6…32V DC 8 mA max. 6.6V DC max. 3.6V DC min.
700-SKICA18 100…240V AC 60…264V AC 15 mA max. 60V AC max. 20V AC min.
  

Output Logic Ratings
Cat. No. Logic Level Supply Voltage Logic Level Supply Current Draw
700-SKICZ24 4…32V DC 0.1…100 mA
700-SKICA18
  

Characteristics
Description Cat. No. 700-SKICA18 Cat. No. 700-SKICZ24
Pick-up time 20 ms max. 0.1 ms max.
Drop-out time 20 ms max. 0.1 ms max.
Response frequency 10 Hz 1 kHz
Output ON voltage drop 1.6 V max.
Leakage current 5 mA max.
Output VDRM, VCEO (V) 80 (ref. value) 80 (ref. value)
Output di/dt (A/uS)
Output dv/dt (V/uS)
Output I2t (A2S)
Output Tj (°C) Max. 150 150
Insulation Resistance 100 MW min. between input and output
Dielectric Strength 4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s2 (100 G)
Ambient Temperature Operating –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage –30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient humidity        Operating 45…85% (no condensation)
Weight Approx. 18 g
  

Output SSR Module

Control/Input Ratings
Cat. No. Rated Control Voltage Max. Operating Control Voltage Range Max. Reverse
Control Voltage
Impedance¬  Pick-up
Voltage
Drop-out
Voltage
700-SKOZ2Z25 5…24V DC 4…32V DC -32V DC 15 mA max.
at 25 °C
(77 °F)
4V DC
max.
1V DC min.
700-SKON2Z25
700-SKOC2Z25 8 mA max.
700-SKOC1Z25
  

Load/Output Ratings
Cat. No.
Rated Load Voltage Maximum
Load Voltage Range
Continuous Load Current (Resistive) [A] Max. Inrush CurrentT 
Min. Max.‡ 
700-SKOZ2Z25 100…240V AC 75…264V AC 0.05 2 30 A (@50/60 Hz, 1 cycle)
700-SKON2Z25
700-SKOC2Z25 5…48V DC 4…60V DC 0.1 2 8 A (10 ms)
700-SKOC1Z25 48…200V DC 40…200V DC 0.1 1.5 8 A (10 ms)
  
¬  With a constant current input system. SSR impedance varies with a change in input voltage.
T  If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on Inrush Current
ResistivityT 
for more details.
‡  Refer to "Load Current Versus Ambient Temperature Characteristics" graphs on Inrush Current
ResistivityT 
for additional details.

Output Module, Continued

Characteristics
Description Cat. No. 700-SKOZ2Z25 Cat. No. 700-SKON2Z25 Cat. No. 700-SKOC2Z25 Cat. No. 700-SKOC1Z25
Load Switching Method/Device Triac Transistor
Pick-up Time 1/2 cycle of load power source cycle time¬  + 1 ms max. 1 ms max.
Drop-out Time 1/2 of load power source cycle time¬  + 1 ms max. 2 ms max.
Response Frequency 20 Hz 100 kHz
Output ON Voltage Drop 1.6V max. 2.5V max.
Leakage Current 1.5 mA max. 1 mA max.
Output VDRM, VCEO (V) 600 (ref.value) 600 (ref.value) 80 (ref.value) 400 (ref.value)
Output di/dt (A/uS) 30 30
Output dv/dt (V/uS) 300 300
Output I2t (A2S) 10.4 10.4
Output Tj (°C) Max. 125 125 150 150
Insulation Resistance 100 MW min. between input and output
Dielectric Strength 4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s2 (100 G)
Ambient Temperature Operating –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage –30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient Humidity Operating 45…85% (no condensation)
Weight Approx. 18 g
  
¬ 60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms

Load Current vs. Ambient Temperature Characteristics

Click to enlarge - 700SK-61-1


Inrush Current
ResistivityT 


Click to enlarge - Three Millisecond Charts


T Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.


Approximate Dimensions

All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes.


Note:The input module ( Bul. 700-SKI) and output module (Bul. 700-SKO) are compatible with the Cat. No. 700-HN121 socket.

Click to enlarge - 700SK-62-1


Application Considerations of Bulletin 700-SK

Connection

For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.

Protective Element (to extend SSR life)

Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load.
For additional details applying solid-state relays, refer to pub. 700-AT001A_EN-E, "Solid-State Relay Application Guide."