Solid-State Relays

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Solid-State Relays > Bulletin 700-SE Flat Pack Relay

Bulletin 700-SE Flat Pack Relay

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Specifications

Control/Input Ratings¬ 
Cat. No. Rated Control
Voltage
Max. Operating Control Voltage Range Max. Reverse Control Voltage [V] Impedance Control Voltage Levels
With Zero Cross Function Without Zero Cross Function Pick-up Voltage Drop-out Voltage
700-SE_ _ _Z05 5V DC 4…6V DC –6 250 W ± 20% 300 W ± 20% 4V DC max. 1V DC min.
700-SE_ _ _Z12 12V DC 9.6…14.4V DC –14.4 600 W ± 20% 800 W ± 20% 9.6V DC max.
700-SE_ _ _Z24 24V DC 19.2…28.8V DC –28.8 1.6k W ± 20% 19.2V DC max.
  
¬  Each 5 A, 10 A, and 20 A model has 5V DC, 12V DC, and 24V DC input versions.

Load/Output Ratings
Cat. No.
Rated Load Voltage Max. Load Voltage Range Continuous Load Current (Resistive) Max. Inrush Current‡ 
With Heat SinkT  [A] Without Heat SinkT  [A]
Min. Max. Min. Max.
700-SE05… 100…240V AC 75…264V AC 0.1 5 0.1 5 60 A (@50/60 Hz, 1 cycle)
700-SE10… 0.1 10 0.1 5 150 A (@50/60 Hz, 1 cycle)
700-SE20… 0.1 20 0.1 5 220 A (@50/60 Hz, 1 cycle)
  
T  Refer to "Load Current vs. Ambient Temperature Characteristics¬ " regarding maximum load current with and without heat sinks.
‡  If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to “Inrush Current ResistivityT ” for more details.

Characteristics
Description Cat. No. 700-SE_ _ _Z… Cat. No. 700-SE_ _ _N…
Load Switching Method/Device Triac
Pick-up Time 1/2 of load power source cycle time§  + 1 ms max. 1 ms max.
Drop-out Time 1/2 of load power source cycle time§  + 1 ms max.
Output ON Voltage Drop 1.6V (RMS) max.
Output Leakage current 5 mA max (@ 100 V AC)
10 mA max (@ 200 V AC)
Output VDRM, VCEO (V) 600
Output di/dt (A/uS) SE05GZ = 100
SE10GZ & SE20 GZ = 50
SE05GN = 100
SE10 GN & SE20GN = 50
Output dv/dt (V/uS) SE05GZ = 200, SE10GZ = 500, SE20GZ = 100 SE05GN = 200, SE10GN = 500, SE20GN = 100
Output I2t (A2S) SE05GZ = 24.5, SE10GZ = 60, SE20GZ = 260 SE05GN = 24.5, SE10GN = 60, SE20GN = 260
Output Tj (°C) Max. 125
Insulation Resistance 100 MW min (at 500V DC)
Dielectric Strength 2000V AC, 50/60 Hz for 1 min.
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s2 (100 G)
Ambient Temperature Operating: –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage: –30…+100 °C (–22…+212 °F) with no icing or condensation
Ambient Humidity Operating 45…85% (no condensation)
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60950, EN5 0011, EN 62000-6-2
Certifications cURus Recogonized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Weight Approx. 37 g
  
§ 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms

Load Current vs. Ambient Temperature Characteristics¬ 

Click to enlarge - 175178_a


Inrush Current ResistivityT 

Click to enlarge - 175178_b


¬ All graphs assume conductive grease (Allen-Bradley repair part number W46801-010) is being used.
T Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.