Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Solid-State Relays > Bulletin 700-SE Flat Pack Relay
Bulletin 700-SE Flat Pack Relay
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
| Control/Input Ratings¬ | |||||||
| Cat. No. | Rated Control Voltage |
Max. Operating Control Voltage Range | Max. Reverse Control Voltage [V] | Impedance | Control Voltage Levels | ||
| With Zero Cross Function | Without Zero Cross Function | Pick-up Voltage | Drop-out Voltage | ||||
| 700-SE_ _ _Z05 | 5V DC | 4…6V DC | 6 | 250 W ± 20% | 300 W ± 20% | 4V DC max. | 1V DC min. |
| 700-SE_ _ _Z12 | 12V DC | 9.6…14.4V DC | 14.4 | 600 W ± 20% | 800 W ± 20% | 9.6V DC max. | |
| 700-SE_ _ _Z24 | 24V DC | 19.2…28.8V DC | 28.8 | 1.6k W ± 20% | 19.2V DC max. | ||
| ¬ Each 5 A, 10 A, and 20 A model has 5V DC, 12V DC, and 24V DC input versions. | |||||||
| Load/Output Ratings | |||||||
| Cat. No. |
Rated Load Voltage | Max. Load Voltage Range | Continuous Load Current (Resistive) | Max. Inrush Current | |||
| With Heat SinkT [A] | Without Heat SinkT [A] | ||||||
| Min. | Max. | Min. | Max. | ||||
| 700-SE05… | 100…240V AC | 75…264V AC | 0.1 | 5 | 0.1 | 5 | 60 A (@50/60 Hz, 1 cycle) |
| 700-SE10… | 0.1 | 10 | 0.1 | 5 | 150 A (@50/60 Hz, 1 cycle) | ||
| 700-SE20… | 0.1 | 20 | 0.1 | 5 | 220 A (@50/60 Hz, 1 cycle) | ||
| T Refer to "Load Current vs. Ambient Temperature Characteristics¬ " regarding maximum load current with and without heat sinks. | |||||||
| If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to Inrush Current ResistivityT for more details. | |||||||
| Characteristics | ||
| Description | Cat. No. 700-SE_ _ _Z… | Cat. No. 700-SE_ _ _N… |
| Load Switching Method/Device | Triac | |
| Pick-up Time | 1/2 of load power source cycle time§ + 1 ms max. | 1 ms max. |
| Drop-out Time | 1/2 of load power source cycle time§ + 1 ms max. | |
| Output ON Voltage Drop | 1.6V (RMS) max. | |
| Output Leakage current | 5 mA max (@ 100 V AC) 10 mA max (@ 200 V AC) |
|
| Output VDRM, VCEO (V) | 600 | |
| Output di/dt (A/uS) | SE05GZ = 100 SE10GZ & SE20 GZ = 50 |
SE05GN = 100 SE10 GN & SE20GN = 50 |
| Output dv/dt (V/uS) | SE05GZ = 200, SE10GZ = 500, SE20GZ = 100 | SE05GN = 200, SE10GN = 500, SE20GN = 100 |
| Output I2t (A2S) | SE05GZ = 24.5, SE10GZ = 60, SE20GZ = 260 | SE05GN = 24.5, SE10GN = 60, SE20GN = 260 |
| Output Tj (°C) Max. | 125 | |
| Insulation Resistance | 100 MW min (at 500V DC) | |
| Dielectric Strength | 2000V AC, 50/60 Hz for 1 min. | |
| Vibration Resistance (Max.) | 10…55 Hz, 1.5 mm double amplitude (10 G) | |
| Shock Resistance (Max.) | 1000 m/s2 (100 G) | |
| Ambient Temperature | Operating: 30…+80 °C (22…+176 °F) with no icing or condensation Storage: 30…+100 °C (22…+212 °F) with no icing or condensation |
|
| Ambient Humidity Operating | 45…85% (no condensation) | |
| Standards Compliance | UL 508, CSA C22.2 No. 14, EN/IEC 60950, EN5 0011, EN 62000-6-2 | |
| Certifications | cURus Recogonized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified | |
| Weight | Approx. 37 g | |
| § 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms | ||
Load Current vs. Ambient Temperature Characteristics¬
|
Inrush Current ResistivityT
|
¬ All graphs assume conductive grease (Allen-Bradley repair part number W46801-010) is being used.
T Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.