Control/Input Ratings
Cat. No. Rated Control
Voltage
Max. Operating Control Voltage Range [V DC] Max. Reverse Control Voltage [V] Impedance Control Voltage Levels
Pick-up Voltage Drop-out Voltage
700-SFZY3Z25 5…24V DC 4…28V DC –32 15 mA max.¬  4V DC max. 1V DC min.
700-SFTY3Z24 24V DC 19.2…28.8V DC –28.8 2 kW ± 20% 19.2V DC max. 1V DC min.
700-SFNY3Z25 5…24V DC 4…28V DC –28.8 1.5 kW + 20%/–10%T  4V DC max. 1V DC min.
  
¬  With constant current input circuit system, SSR impedance varies with a change in input voltage.
T  Input impedance reaches its maximum at the operating voltage.

Load/Output Ratings
Cat. No. Rated Load Voltage Max. Load Voltage Range Continuous Load Current (Resistive) [A] Max. Inrush Current‡ 
Min. Max.§ 
700-SFZY3Z25 100…240V AC 75…264V AC 0.1 3 45 A @ 50/60 Hz, 1 cycle
700-SFTY3Z24 0.1 3
700-SFNY3Z25 4…48V DC 3…52.8V DC 0.1 3 18 A (10 ms)
  
‡  If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 50 for more details.
§  Refer to "Load Current vs. Ambient Temperature Characteristics" on page 50 for additional load current details.

Characteristics
Description Cat. No. 700-SFZY3Z25 Cat. No. 700-SFTY3Z24 Cat. No. 700-SFNY3Z25
Load Switching Method/Device Triac Transistor
Pick-up Time 1/2 cycle of load power source cycle time §  + 1 ms max. 1 ms max. 0.5 ms max.
Drop-out Time 1/2 cycle of load power source cycle time§  + 1 ms max. 2 ms max.
Output ON Voltage Drop 1.6V (RMS) max. 1.5V max.
Output Leakage Current 5 mA max. (@ 100 V AC);
10 mA max. (@ 200 V AC)
2.5 mA max. (@ 100V AC);
5 mA max. (@ 200V AC)
5 mA max. (@ 50V DC)
Output VDRM, VCEO (V) 600 600 80
Output di/dt (A/uS) 50 50
Output dv/dt (V/uS) 250 250
Output I2t (A2S) 18 18
Output Tj (°C) Max. 125 125 150
Insulation Resistance 100 MW min. (at 500V DC)
Dielectric Strength 1,500V AC, 50/60 Hz for 1 min
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s2 (100 G)
Ambient Temperature Operating: –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage: –30…+100 °C (–22…=212 °F) with no icing or condensation
Ambient Humidity 45…85% (no condensation)
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-3, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified
Weight Approx. 50 g
  
§ 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time 20 ms

Note:These data are non-repetitive. Keep the inrush current to half the rated value if it occurs repetitively. Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.


Load Current vs. Ambient Temperature Characteristics

700-SF…

Click to enlarge - 700SF-50-1


Inrush Current Resistivity¬ 

700-SFZ… 700SFT…

Click to enlarge - 700SF-50-2


Inrush Current Resistivity¬ 

700-SFN…

Click to enlarge - 700SF-50-3


¬ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.