General Purpose Relays

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > General Purpose Relays > Bulletin 700-HG Power Relay

Bulletin 700-HG Power Relay

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Specifications

Cat. No. 700-HG...
Electrical Ratings
Pilot Duty Rating T  A600
Rated Thermal Current (/th) 40 A
Rated Insulation Voltage (Ui) 600V UL
Contact Ratings: AC Ratings SPST-NO-DM Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT
Volts Inductive Resistive -
Make/Break
and Continuous
HP Volts Inductive Resistive -
Make/Break
and Continuous
HP‡ 
Make Break Continuous Make Break Continuous
120 60 A 6 A 10 A 40 A 2 120 60 A 6 A 10 A 40 A 1 - 1/2
240 30 A 3 A 10 A 40 A 240 30 A 3 A 10 A 40 A
480 15 A 1.5 A 10 A 12 A 2 480 15 A 1.5 A 10 A 5 A 1 - 1/2
600 12 A 1.2 A 10 A 10 A 600 12 A 1.2 A 10 A 5 A
DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous        Est Drop 125V 1.2...3 A
DC Ratings: With Magnetic Blowouts: SPST - NO - DM SPDT, DPST - NO and DPDT
Make, Break
and Continuous
110V 20 A 10 A
220V 8 A 4 A
325V 4 A 2 A
500V 2 A
Permissible Coil
Voltage Variation
80...100% of Nominal Voltage at 50 Hz
85...110% of Nominal Voltage at 60 Hz
80...110% of Nominal Voltage at DC
  50 HZ 60 HZ
Coil Consumption ±10% AC Coils Inrush 13 VA 16 VA
Sealed 10 VA 11 VA
DC Coils   2.0 W
Design Specification/Test Requirements
Dielectric
Withstand
Voltage
Pole-to-Pole 2200V AC
Contact to Pole 2200V
Contact to Frame 2200V AC
Mechanical
Degree of Protection Open Type
Mechanical Life Operations 5 x 106
Switching Frequency Operations 1600/Hr
Coil Voltage See Overview/Product Selection
Operating Time at Nominal Voltage at 20 °C Pickup
Dropout
40 ms
35 ms
Maximum Operating Rate
Environmental
Temperature Operating -30...+55 °C
(-22...+149 °F)
Storage -30...+65 °C
(-22...+149 °F)
Altitude 2000 m (6560 ft.)
Construction
Insulating Material Molded Thermo
Setting Plastic
Enclosure
Contact Material Silver Cadmium Oxide
Terminal Markings on Socket
Sockets N/A
Certifications CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked
Standards UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1
  
¬ Performance Data - See Performance Data, this catalog.
T NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P.
‡ For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.