Bulletin 700-HLF Terminal Block Timing Relay

Click to enlarge - 700-HLF-Relay-4c


Bulletin 700-HLF Terminal Block Timing Relay


Standards Compliance and Certifications

See Specifications.

Catalog Number Explanation

700 HL    F    1    U24    X¬ 
Bulletin Number    Series Type    Relay Type    Terminal Type    Supply Voltage    Gold-Plated Contact Option

a
Series Type
Code Description
HL Terminal Block relay

b
Relay Type
Code Description
F Timing Relay

c
Terminal Type
Code Description
1 Screw Terminal

d
Supply Voltage
Code Description
U24 24V AC/DC

e¬ 
Gold-Plated Contact Option
Code Description
Blank None
X Gold Plate

¬ For Gold-plated contacts: Add the letter "X" at the end of the catalog number. Example: Cat. No. 700-HLF1U24 with gold plated contacts is catalog number 700-HLF1U24X.


Product Selection

Build a Catalog Number


Standard built-in Features:
  • LED

  • Reverse Polarity Protection for DC Inputs

  • Coil Surge Protection § 
  • Click to enlarge - 700-HLF-Relay-4c
    Cat. No. 700-HLF1U24
    Specifications Click to enlarge - 700HL-102-6
    Output Type SPDT (1 C/O); Ith = 6A‡ 
    Recommended Tightening Torque 0.5 Nm max. (4.4 lb.–in.)
    Wire Range Screw Terminal: 0.14 mm2…2.5 mm2 (#26…#14 AWG)
    Approvals cULus, cURus, CE
      
     
    ‡ For Gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-HLF1U24 is required with gold plating, the new cat. no. is 700-HLF1U24X.

    Assembled Devices Pkg. Quantity Cat. No.
    Input Voltage
    24V AC/DC 10 700-HLF1U24
      
    § Diode surge protection provided.

    Accessories

      Description Pkg. Quantity Socket Input Voltage Cat. No.
    Click to enlarge - 700-TBR24_GS Replacement Relays
    Order must be for 20 relays or multiples of 20.
    20 24V AC/DC 700-TBR24¬ 
    Click to enlarge - 700HL-103-3 20-Way Jumper
    Can be cut to required length. Ith = 36 A max per 20-way jumper.
    1 Color
    Red 700-TBJ20R
    Grey 700-TBJ20G
    Cat. No. 700-TBJ20B Blue 700-TBJ20B
    Click to enlarge - 700-HN177_GS End Barrier
    Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.
    10 Black 700-HN177
    Cat. No. 700HN177
    Click to enlarge - 700HA-68-2 Snap-in Marker
    These snap-in markers have a 6 x 10 mm surface and snap into the ejection lever for the relay.
    100 Blank 1492-MC6X10
    Standard 1492-MC6X10 www.ab.com/
    catalogs for information
    Custom T 
      
    ¬ For gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X.
    T Go to http://www.ab.com/software/ and click on "Terminal Marking System and WinABMS " to download software. Create custom text, save file, and e-mail to your local Rockwell Automation sales office or Allen-Bradley distributor.
    Note:Terminal block timing relay bases are not sold separately.

    700-HLF Function and Connection Diagrams

    On-Delay
    Click to enlarge - 700-HLF-Ondelay
    One Shot
    Click to enlarge - 700-HLF-Offdelay
    Pulse
    Click to enlarge - 700-HLF-Pulse
    Flasher
    Click to enlarge - 700-HLF-Flasher

    Specifications

    Cat. No. 700-HLF… (Relay Output)
    Electrical Ratings
    Pilot Duty Rating B 300, R 300
    Rated Thermal Current (Ith) 1-Pole — 6 A
    Rated Insulation Voltage (Ui) 250V IEC, 300V UL/CSA
    Contacts Inductive 1-Pole
    24V AC,
    1-phase
    30 A Click to enlarge - 700HA-69-1 5 A Click to enlarge - 700HA-69-2  
    120V AC,
    1-phase
    30 A 3 A
    240V AC,
    1-phase
    15 A 1.5 A
    Make, Break &
    Continuous
    V DC
    24V DC 1.0 A
    120V DC 0.2 A
    240V DC 0.1 A
    Inductive Load AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact
    DC-13 24V, 1 A N.O. and N.C. Contact
    Min. Permissible Contact Ratings 12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts
    Permissible Coil Voltage Variation Pickup:

    85…110% of Nominal Voltage at 50 Hz
    85…110% of Nominal Voltage at 60 Hz
    80…110% of Nominal Voltage at DC
    Must Dropout Voltage:

    10% of Nominal Voltage at AC
    5% of Nominal Voltage at DC
    Power Consumption
    ±10%
    AC/DC 0.5 VA
    Design Specification/Test Requirements
    Dielectric Withstand Voltage Pole to Pole
    (VRMS)
    1000V
    Contact to Coil
    (VRMS)
    4000V
    Input Voltage 24V AC/DC
    Impedance (Ohms) 2 K
    Mechanical
    Degree of Protection IP20
    Mechanical Life Operations 1 x 107
    Electrical Life Operations 6 A Resistive: 100 000 min.
    24V DC, 1 A Inductive: 200 000 min.
    120V AC 1 A Inductive: 300 000 min.
    Switching Frequency Operations (no-load) 10 cycles/sec
    Coil Voltages See Overview/Product Selection
    Timer Functions On-Delay, One Shot, Pulse and Flasher
    Timer Settings 0.1...3 s, 3...60 s, 1...20 min, and 0.3...6 hr
    Timer Adjustments Min and Max adjustments with Potentionmeter
    Timer Accuracy Repeatability 1%, Recovery Time < 50 ms, Setting Accuracy Full Range 5%
    Coil Surge Protection Per EN 61000-4.5; Surge Immunity (801-5)
    Class III: 2 kV common and 1 kV differential mode
    Environmental
    Temperature Operating –40…55 °C
    Storage –40…100 °C
    Altitude 2000 m (6560 ft)
    Construction
    Insulating Material Molded High Dielectric Material
    Enclosure Relay IP67
    Contact Material Silver Tin Ox., AgSnO2 or Silver with Gold Plating, AgSnO2 + Au
    Terminal Markings on Socket In accordance with EN50 0005
    Certifications cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked
    Standards EN60947-4-1,EN60947-5-1,CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant
      UL Listed
    (UL 60079-15)
    700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
    700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
      CSA CertifiedT 
    (CAN/CSA E60079-15)
    700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
      
    ¬ Performance Data – See this catalog, ImportantPerformance Data.
    T Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

    Approximate Dimensions

    Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

    Click to enlarge - 700-HLF_Front_Dims Click to enlarge - 700-HLF_Side_Dims

    Bulletin 700-HLF Screw Terminal Design
    Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG)
    Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG)
    Wire Type: Solid or stranded, copper only
    Strip Length: 9 mm (11/32 in.). Torque: 0.5 N•m (4.4 lb•in)

    Click to enlarge - 700HA-72-2
    Cat. No. 199-DR1 DIN Mounting Rail Series BCat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes


    Cat. No. A B C D Approx.
    Shipping Wt.
    199-DR1 35
    (1-3/8)
    27
    (1-1/16)
    7.5
    (19/64)
    1.02
    (1/64)
    1.85 kg
    (4.07 lb) (10/pkg)
    199-DR4 35
    (1-3/8)
    27
    (1-1/16)
    15
    (19/32)
    2.3
    (3/32)
    3.68 kg
    (8 lb) (5/pkg)