Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > General Purpose Relays > Bulletin 700-HLF Terminal Block Timing Relay
Bulletin 700-HLF Terminal Block Timing Relay
| Introduction | Standards Compliance and Certifications | Catalog Number Explanation | Product Selection |
| Accessories | 700-HLF Function and Connection Diagrams | Specifications | Approximate Dimensions |
| Cat. No. 700-HLF… (Relay Output) | |||||||
| Electrical Ratings | |||||||
| Pilot Duty Rating | B 300, R 300 | ||||||
| Rated Thermal Current (Ith) | 1-Pole — 6 A | ||||||
| Rated Insulation Voltage (Ui) | 250V IEC, 300V UL/CSA | ||||||
| Contacts | Inductive | 1-Pole | |||||
| 24V AC, 1-phase |
30 A |
|
5 A |
|
|||
| 120V AC, 1-phase |
30 A | 3 A | |||||
| 240V AC, 1-phase |
15 A | 1.5 A | |||||
| Make, Break & Continuous V DC |
24V DC | 1.0 A | |||||
| 120V DC | 0.2 A | ||||||
| 240V DC | 0.1 A | ||||||
| Inductive Load | AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O. and N.C. Contact |
||||||
| Min. Permissible Contact Ratings | 12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts | ||||||
| Permissible Coil Voltage Variation | Pickup: |
85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC |
Must Dropout Voltage: |
10% of Nominal Voltage at AC 5% of Nominal Voltage at DC |
|||
| Power Consumption ±10% |
AC/DC | 0.5 VA | |||||
| Design Specification/Test Requirements | |||||||
| Dielectric Withstand Voltage | Pole to Pole (VRMS) |
1000V | |||||
| Contact to Coil (VRMS) |
4000V | ||||||
| Input Voltage | 24V AC/DC | ||||||
| Impedance (Ohms) | 2 K | ||||||
| Mechanical | |||||||
| Degree of Protection | IP20 | ||||||
| Mechanical Life Operations | 1 x 107 | ||||||
| Electrical Life Operations | 6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min. |
||||||
| Switching Frequency Operations (no-load) | 10 cycles/sec | ||||||
| Coil Voltages | See Overview/Product Selection | ||||||
| Timer Functions | On-Delay, One Shot, Pulse and Flasher | ||||||
| Timer Settings | 0.1...3 s, 3...60 s, 1...20 min, and 0.3...6 hr | ||||||
| Timer Adjustments | Min and Max adjustments with Potentionmeter | ||||||
| Timer Accuracy | Repeatability 1%, Recovery Time < 50 ms, Setting Accuracy Full Range 5% | ||||||
| Coil Surge Protection | Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode |
||||||
| Environmental | |||||||
| Temperature | Operating | 40…55 °C | |||||
| Storage | 40…100 °C | ||||||
| Altitude | 2000 m (6560 ft) | ||||||
| Construction | |||||||
| Insulating Material | Molded High Dielectric Material | ||||||
| Enclosure | Relay IP67 | ||||||
| Contact Material | Silver Tin Ox., AgSnO2 or Silver with Gold Plating, AgSnO2 + Au | ||||||
| Terminal Markings on Socket | In accordance with EN50 0005 | ||||||
| Certifications | cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked | ||||||
| Standards | EN60947-4-1,EN60947-5-1,CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant | ||||||
| UL Listed (UL 60079-15) |
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply) |
||||||
| CSA CertifiedT (CAN/CSA E60079-15) |
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) | ||||||
| ¬ Performance Data See this catalog, ImportantPerformance Data. | |||||||
| T Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%. | |||||||