Bulletin 700-FS High Performance Timing Relay

Product Overview


Click to enlarge - 700-fsshot


Bulletin 700-FS


Standards Compliance and Certifications

See Specifications.

Catalog Number Explanation

700 FS    H    3    U    U23
Bulletin Number    Type of Relay    Operating Mode    Contact Output    Timing Range    Input Voltage

Single-Function (With SPDT 1 C/O contacts)

700–FS    A    3    A    U23
      a    b    c    d

a
Operating Mode
Code Description
A On-delay¬ 
B Off-delay¬ 
C On- and off-delay¬ 
D One shot¬ 
E Fleeting off-delay¬ 
F Flasher (repeat cycle starts
with pulse)¬ 
G Flasher (repeat cycle starts
with pause)¬ 
I On-delay pulse generator¬ 
J On-delay (pulse
controlled)¬ 
K One shot/watch dog (pulse
controlled)¬ 
L Pulse converter¬ 

b
Contact Output
All functions:  
3 One changeover
contact (SPDT)
1 C/O

c
Timing Range
Code Description
A 0.05…1 s
B 0.15…3 s
C 0.5…10 s
D 1.5…30 s
E 0.05…1 min
F 0.15…3 min
G 0.5…10 min
H 1.5…30 min
I 0.05…1 hr
J 0.15…3 hr
K 0.5…10 hr
L 3.0…60 hr
U 0.05 s…60 hrT 

d
Input Voltage
Code Description
Z12 12V DC
U23 24…48V DC
24…240V AC 50/60 Hz

¬ Preferred availability item.
T Valid for functions "A" and "B" only.


Product Selection

Build a Catalog Number


Single Function (With 2PDT 2 C/O contacts)

Operating Mode Contact Output Timing Range Input Voltage Cat. No.
On-delay (DPDT) 2 C/O 0.05 s…60 hr‡  12V DC 700-FSA4UZ12
On-delay (DPDT) 2 C/O 24…48V DC
24…240V AC, 50/60 Hz
700-FSA4UU23
Off-delay (DPDT) 2 C/O 12V DC 700-FSB4UZ12
Off-delay (DPDT) 2 C/O 24…48V DC
24…240V AC, 50/60 Hz
700-FSB4UU23
  
‡ The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.

Single Function With Hazardous Location Certification §  (With SPDT 1 C/O contacts)

Operating Mode Contact Output Timing Range Input Voltage Cat. No.
One Shot / Watch Dog
(Pulse Controlled)
(SPDT) 1 C/O 0.05 s…1 s 24…48V DC
24…240V AC
50/60 Hz
700-FSK3AU23-EX
0.5 s…10 s 700-FSK3CU23-EX
  

§  Click to enlarge - ex II 3 G, EEx nL IIC T4
DEMKO 04 ATEX 0404974X
2A 32VDC MAX. Ta £ 70 °C
Click to enlarge - C UL US mark Ind. Cont. Eq. for Hazardous
Location Listed 87SL
Class 1, Div. 2, Groups A,B,C,D
Class 1, Zn 2, Group IIC
Temp. Code T4A
2A 32VDC MAX.
Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.
  

Multi-Function (This device offers you the flexibility of selecting one of 8 single timing functions.)

Operating Mode Contact Output Timing Range Input Voltage Cat. No.
Multi-function timing relays
8 Single-functions:
A, B, C, D, E, F, I, and L
ON and OFF function additional
(for installation and maintenance)
note: See connection diagrams for further description.
(SPDT) 1 C/O 0.05 s…60 hr 12V DC 700-FSM3UZ12
(SPDT) 1 C/O 24…48V DC
24…240V AC
50/60 Hz
700-FSM3UU23
(DPDT) 2 C/O 12V DC 700-FSM4UZ12
(DPDT) 2 C/O 24…48V DC
24…240V AC
50/60 Hz
700-FSM4UU23
  

Multi-Function With Hazardous Location Certification §  (This device offers you the flexibility of selecting one of 8 single timing functions.)

Operating Mode Contact Output Timing Range Input Voltage Cat. No.
M Multi-function timing relays
8 Single-functions:
A, B, C, D, E, F, I, and L
ON and OFF function additional
(for installation and maintenance)
Note: See connection diagrams for further description.
(SPDT) 1 C/O 0.05 s…60 h¬  24…48V DC
24…240V AC
50/60 Hz
700-FSM3UU23-EX
(DPDT) 2 C/O 700-FSM4UU23-EX
  

§  Click to enlarge - ex II 3 G, EEx nL IIC T4
DEMKO 04 ATEX 0404974X
2A 32VDC MAX. Ta £ 70 °C
Click to enlarge - C UL US mark Ind. Cont. Eq. for Hazardous
Location Listed 87SL
Class 1, Div. 2, Groups A,B,C,D
Class 1, Zn 2, Group IIC
Temp. Code T4A
2A 32VDC MAX.
Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.
  

Special Function

Operating Mode Contact Output Timing Range Input Voltage Cat. No.
Flasher (repeat cycle starting with pulse or pause) (SPDT) 1 C/O 0.05 s…60 hr¬  12V DC 700-FSH3UZ12
24…48V DC
24…240V AC
50/60 Hz
700-FSH3UU23
2 x 0.05 s…60 hr (2 ranges) 12V DC 700-FSH3VZ12
24…48V DC
24…240V AC, 50/60 Hz
700-FSH3VU23
OFF-delay without supply voltages (True OFF-delay)‡  (SPDT) 1 C/O 0.15 s…10 minT  24…240V DC
24…240V AC
50/60 Hz
700-FSQ3QU18
(DPDT) 2 C/O 700-FSQ4QU18
Star-Delta 2 N.O. + 1 Common 0.5 s…10 s 24…48V DC 700-FSY2CU23
1.5…30 s 24…240V AC
50/60 Hz
700-FSY2DU23
0.05 s…1 min 700-FSY2EU23
0.15…3 min 700-FSY2FU23
0.5…10 min 700-FSY2GU23
  
¬ The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.
T This time range is selectable in four smaller ranges: 0.15 s…2.5 s, 0.5 s…10 s, 4 s…80 s, 30 s…10 min.
‡ Due to shock during shipment, the state of the contacts should be verified before initial use.

Multi-Function Timing Relay Function and Time Range Settings

Description Click to enlarge - 700FE-118-3 SPDT Click to enlarge - 700FE-118-3 Click to enlarge - 700FE-118-3 DPDT
Click to enlarge - 700-FSM_GS Multi-function timing relays 700-FSM3U includes 10 setting functions: Multi-Time Setting Range 0.05 s…60 h
(A)On-Delay Click to enlarge - 700FS-121-5 (1 s) 0.05…1 s
(3 s) 0.15…3 s
(10 s) 0.5…10 s
(1 min) 0.05…1 min
(3 min) 0.15…3 min
(10 min) 0.5…10 min
(1 hr) 0.05…1 hr
(3 hr) 0.15…3 hr
(10 hr) 0.5…10 hr
(60 hr) 3.…60 hr
Click to enlarge - 700FS-121-6
(B)Off-Delay
(C)On- and Off-Delay
(D)One shot
(E)Fleeting Off-Delay
(F)Flasher (repeat cycle starts with pulse)
(I)On-Delay pulse generator
(L)Pulse converter
(On)ON-Function§ 
(Off)OFF-Function§ 
Note: Switch Ä is on DPDT relays only. When switch is down, one contact is instantaneous and one is timed. When switch is up, both contacts are timed.   
        
§ For installation and maintenance.

Accessories

  Description Pkg. Quantity Cat. No.
Click to enlarge - 700FS-122-2 Setting Knob with Scale
(for time setting without tools)
10 700-FSK
Click to enlarge - 700FE-118-1 Panel Mounting Adapter
For surface mounting according to drilling plan EN 50 002
5 199-FSA
Click to enlarge - 700FS-122-4 Label Sheet
105 self-adhesive paper labels each, 6 x 17 mm
10 100-FMS
Marking Tag Sheet
160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
10 100-FMP
Transparent Cover
To be used with marking tag sheets
100 100-FMC
Marking Tag Adapters
To be used with marking tag: System 1492 W
100 ¬  100-FMA2
  
¬ Cat. No. 100-FMA2 is only a marking tag carrier. Please refer to the Terminal Block Accessories section, IEC Marking System of this publication for appropriate marker cards to be used with this carrier.

Connection Diagrams

(A) On-Delay

Click to enlarge - 700FS-123-1


(B) Off-Delay (Min. Pulse AC 50 ms…DC 30 ms)

Click to enlarge - 700FS-123-2


(C) On- and Off-Delay

Click to enlarge - 700FS-123-3


(D) One Shot

Click to enlarge - 700FS-123-4


(E) Fleeting Off-Delay (Min. Pulse AC 50 ms…DC 30 ms)

Click to enlarge - 700FS-123-5


(F) Flasher (Repeat Cycle Starts with Pulse)

Click to enlarge - 700FS-123-6


(G) Flasher (Repeat Cycle Starts with Pause)

Click to enlarge - 700FS-123-7


(I) On-Delay Pulse Generator

Click to enlarge - 700FS-123-8


(J) On-Delay (Pulse Controlled)

Click to enlarge - 700FS-123-9


(K) One Shot/ Watch Dog (Pulse Controlled)

Click to enlarge - 700FS-123-10


(On) ON-Function  (Off) OFF-Function

Click to enlarge - 700FS-123-11


(L) Pulse Converter (Min. Pulse AC 50 ms…DC 30 ms)

Click to enlarge - 700FS-123-12


Cleverly Designed Function Display LED (Green)

Click to enlarge - 700FS-123-13


¬ A voltage other than the supply voltage can be used at B1, but must be within voltages specified on timer.
T Output 2 is selectable as instantaneous contact with sliding switch (Ä) on front panel (instantaneous when switch is down, timed when switch is up).
‡ Available on multifunction "M," and single function "A" or "B" option timing relays along with code "4" (2PDT contacts). Bridge or potentiometer 10 kW, 0.25 W min. (low voltage) for external time setting. Set timer dial to 0.0.


Special Function Flasher (Repeat Cycle Starting with Pulse or Pause) Timing Relays

Description
 

Click to enlarge - 700FS-124-1
700-FSH3U


Click to enlarge - 700FS-124-2
700-FSH3V


Supply Voltages (A1/A2)

Z12 12V DC

U23 24…48V DC,

24…240V AC, 50/60 Hz


Function Diagram / Connection Diagram
 

(H) Flasher (Repeat Cycle Starting with Pulse or Pause)
The repeat cycle timer permits different settings for on and off times.
The following operating modes are possible:
  • Oscillating mode; repeat cycle starts with voltage applied at A1 and B1, and continues to repeat until voltage is off.


  • One cycle mode; started by energizing B1 with voltage on A1 and A2.


  • Output starts with pulse or pause (switch Ä Up or Down).


  • 700-FSH3U provides (1) range setting for t1 and t2.
     700-FSH3V provides (2) range settings for t1 and t2.


  • Supply Voltage Controlled, Oscillating Mode Starting with Pause — Switch Ä is Up

    Click to enlarge - 700FS-124-3


    Supply Voltage Controlled, Oscillating Mode Starting with Pulse — Switch Ä is Down

    Click to enlarge - 700FS-124-4


    Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms — DC 30 ms) — Switch Ä is Up One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.

    Click to enlarge - 700FS-124-5


    Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms — DC 30 ms) — Switch Ä is Down One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.

    Click to enlarge - 700FS-124-6


    Note:If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.

       
    Click to enlarge - 700FS-124-7  
       

    Function Diagram / Connection Diagram
     

    (Q) Off-Delay without Supply Voltage (True Off-Delay) — When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the time delay.

    Click to enlarge - 700FS-125-1


    Note:Min. pulse (tp) required:
    800 ms


    Click to enlarge - 700FS-125-2


    (Y) Star-Delta Timing Relay — When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns to shelf state. After the fixed time (50… 60 ms), the output contact 17/28D changes state. Both output contacts return to shelf state whenever the power is removed.
    Click to enlarge - 700FS-125-3
     

    Specifications

    Time Characteristics (according to VDE 0435, Part 2021)
    Setting Accuracy ±5% of full scale
    Repeatability ±0.2% of the setting values
    Tolerance Voltage: ±0.001%/%DU
    Temperature: ±0.025%/°C
      

    Supply
    Supply Voltages 24…48V DC and 24…240V AC, 50/60 Hz (multi voltage)
    Voltage Tolerance –20…+20% (DC), –15…+10% (AC)
    Power Consumption 0.5 W at 24V DC, 5 VA at 240V AC
    Time Energized 100%
    Reset Time 50 ms
    Voltage Interruption £20 ms without reset (supply voltage)
    Input Impedance Relay ON: 3K-13K ohms
    Relay OFF: 0.7K-4K ohms
    Cable Length (Supply Voltage Control) Max. 250 m (800 ft)
      

    Pulse Control (B1)
    Pulse Duration ³50 ms (AC), ³30 ms (DC)
    Input Voltage Supply voltage range
    Input Current 1 mA
    Max. Leakage Current 400 micro Amps
    Cable Length Max. 250 m (800 ft) without parallel load between B1 and A2
    Max. 50 m (160 ft) with load (<3 kW) between B1 and A2
      

    Outputs
    Contact Type Relay as changeover switch
    Dielectric Coil to Contact
    Withstand Voltage
    5000 V
    Switching Capacity Voltage: 440V AC
    Current Ith (AC-1): 8 A (5 A for 700-
    FSQ)
    Power: 2000 VA
    According to IEC 947-5-1:
    3 A/440V AC (inductive load, AC 14)
    3 A/250V AC (inductive load, AC 15)
    1 A/24V DC (inductive load, DC 13)
    According to UL 508:
    1.5 A/250V AC (B300)
    3 A/120V AC (B300)
    Short-Circuit Resistance 10 A gL
    Life Mechanical: 30 million operations
    Electrical operations:
    4 Mil. at 1 A/250V AC, cos f = 1
    0.2 Mil. at 6 A/250V AC, cos f = 1
    1.5 Mil. at 1 A/250V AC, cos f = 0.3
    0.3 Mil. at 3 A/250V AC, cos f = 0.3
    0.5 Mil. at 6 A/24V DC, resistive
    2 Mil. at 4 A/24V DC, resistive
    2 Mil. at 0.2 A/230V DC, resistive
    1 Mil. at 0.4 A/24V DC, L/R = 20 ms
    1 Mil. at 0.2 A/110V DC, L/R = 20 ms
    1 Mil. at 0.1 A/230V DC, L/R = 20 ms
    State Indicator 1 LED, combination signal
      

    General Data
    Insulation Characteristics 2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 ms surge voltage according to IEC 947-1 between all inputs and outputs
    EMC/Interference Immunity Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 ms
    Burst according to IEC 1000-4-4: 6 kV 6/50 ns
    ESD discharge according to IEC 1000-4-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3
    EMC/Emission Electromagnetic fields according to EN 55 022: class B
    Safe Isolation According to VDE 106, part 101
    Climatic Withstand 56 Cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3
    Vibration Resistance 4 g in three axes at 10…500 Hz, test FC according to IEC 68-2-6
    Shock Resistance 50 g according to IEC 68-2-27
    Protection Class Enclosure:IP 40
    IP 30 (Single-function)
    Terminal:IP 20 according to IEC 947-1
    Weight 100 g
    Approval UL, C-UL
    Ambient Temperature Open: –25…+60 °C
    Enclosed: –25…+45 °C
    Storage: –40…+85 °C
    Terminals Screw terminal M3.5 for Number 2 Posidrive, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 N•m, max. 1.2 N•m).
    Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106.
    Mounting Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type)
    Disposal Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium
    Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
    Standards EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
      

    ¬ See Performance Data.


    Click to enlarge - ex II 3 G, EEx nL IIC T4
    DEMKO 04 ATEX 0404974X
    2A 32VDC MAX. Ta £ 70 °C
    Click to enlarge - C UL US mark Ind. Cont. Eq. for Hazardous
    Location Listed 87SL
    Class 1, Div. 2, Groups A,B,C,D
    Class 1, Zn 2, Group IIC
    Temp. Code T4A
    2A 32VDC MAX.
    Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.