Bulletin 700-FS High Performance Timing Relay
| Product Overview |
|
Bulletin 700-FS
- Adjustable function and timing range timing relays
- DIN Rail mounted without cost of socket
- 22.5 mm wide multi-function or single functions
- Available as SPDT or DPDT contact output, 8 A
- Timing Ranges From 0.05 s…60 hr
- Coil surge protection
Standards Compliance and Certifications
See Specifications.
Catalog Number Explanation
| 700 | | FS | H | 3 | U | U23 | ||||
| Bulletin Number | Type of Relay | Operating Mode | Contact Output | Timing Range | Input Voltage |
Single-Function (With SPDT 1 C/O contacts)
| 700FS | A | 3 | A | U23 | ||||
| a | b | c | d |
| a | |
| Operating Mode | |
| Code | Description |
| A | On-delay¬ |
| B | Off-delay¬ |
| C | On- and off-delay¬ |
| D | One shot¬ |
| E | Fleeting off-delay¬ |
| F | Flasher (repeat cycle starts with pulse)¬ |
| G | Flasher (repeat cycle starts with pause)¬ |
| I | On-delay pulse generator¬ |
| J | On-delay (pulse controlled)¬ |
| K | One shot/watch dog (pulse controlled)¬ |
| L | Pulse converter¬ |
| b | |
| Contact Output | |
| All functions: | |
| 3 One changeover contact (SPDT) |
1 C/O |
| c | |
| Timing Range | |
| Code | Description |
| A | 0.05…1 s |
| B | 0.15…3 s |
| C | 0.5…10 s |
| D | 1.5…30 s |
| E | 0.05…1 min |
| F | 0.15…3 min |
| G | 0.5…10 min |
| H | 1.5…30 min |
| I | 0.05…1 hr |
| J | 0.15…3 hr |
| K | 0.5…10 hr |
| L | 3.0…60 hr |
| U | 0.05 s…60 hrT |
| d | |
| Input Voltage | |
| Code | Description |
| Z12 | 12V DC |
| U23 | 24…48V DC 24…240V AC 50/60 Hz |
¬ Preferred availability item.
T Valid for functions "A" and "B" only.
Product Selection
| Build a Catalog Number |
Single Function (With 2PDT 2 C/O contacts)
| Operating Mode | Contact Output | Timing Range | Input Voltage | Cat. No. |
| On-delay | (DPDT) 2 C/O | 0.05 s…60 hr | 12V DC | 700-FSA4UZ12 |
| On-delay | (DPDT) 2 C/O | 24…48V DC 24…240V AC, 50/60 Hz |
700-FSA4UU23 | |
| Off-delay | (DPDT) 2 C/O | 12V DC | 700-FSB4UZ12 | |
| Off-delay | (DPDT) 2 C/O | 24…48V DC 24…240V AC, 50/60 Hz |
700-FSB4UU23 | |
| The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. | ||||
Single Function With Hazardous Location Certification § (With SPDT 1 C/O contacts)
| Operating Mode | Contact Output | Timing Range | Input Voltage | Cat. No. |
| One Shot / Watch Dog (Pulse Controlled) |
(SPDT) 1 C/O | 0.05 s…1 s | 24…48V DC 24…240V AC 50/60 Hz |
700-FSK3AU23-EX |
| 0.5 s…10 s | 700-FSK3CU23-EX | |||
Multi-Function (This device offers you the flexibility of selecting one of 8 single timing functions.)
| Operating Mode | Contact Output | Timing Range | Input Voltage | Cat. No. |
| Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) note: See connection diagrams for further description. |
(SPDT) 1 C/O | 0.05 s…60 hr | 12V DC | 700-FSM3UZ12 |
| (SPDT) 1 C/O | 24…48V DC 24…240V AC 50/60 Hz |
700-FSM3UU23 | ||
| (DPDT) 2 C/O | 12V DC | 700-FSM4UZ12 | ||
| (DPDT) 2 C/O | 24…48V DC 24…240V AC 50/60 Hz |
700-FSM4UU23 | ||
Multi-Function With Hazardous Location Certification § (This device offers you the flexibility of selecting one of 8 single timing functions.)
| Operating Mode | Contact Output | Timing Range | Input Voltage | Cat. No. |
| M Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) Note: See connection diagrams for further description. |
(SPDT) 1 C/O | 0.05 s…60 h¬ | 24…48V DC 24…240V AC 50/60 Hz |
700-FSM3UU23-EX |
| (DPDT) 2 C/O | 700-FSM4UU23-EX | |||
Special Function
| Operating Mode | Contact Output | Timing Range | Input Voltage | Cat. No. |
| Flasher (repeat cycle starting with pulse or pause) | (SPDT) 1 C/O | 0.05 s…60 hr¬ | 12V DC | 700-FSH3UZ12 |
| 24…48V DC 24…240V AC 50/60 Hz |
700-FSH3UU23 | |||
| 2 x 0.05 s…60 hr (2 ranges) | 12V DC | 700-FSH3VZ12 | ||
| 24…48V DC 24…240V AC, 50/60 Hz |
700-FSH3VU23 | |||
| OFF-delay without supply voltages (True OFF-delay) | (SPDT) 1 C/O | 0.15 s…10 minT | 24…240V DC 24…240V AC 50/60 Hz |
700-FSQ3QU18 |
| (DPDT) 2 C/O | 700-FSQ4QU18 | |||
| Star-Delta | 2 N.O. + 1 Common | 0.5 s…10 s | 24…48V DC | 700-FSY2CU23 |
| 1.5…30 s | 24…240V AC 50/60 Hz |
700-FSY2DU23 | ||
| 0.05 s…1 min | 700-FSY2EU23 | |||
| 0.15…3 min | 700-FSY2FU23 | |||
| 0.5…10 min | 700-FSY2GU23 | |||
| ¬ The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. | ||||
| T This time range is selectable in four smaller ranges: 0.15 s…2.5 s, 0.5 s…10 s, 4 s…80 s, 30 s…10 min. | ||||
| Due to shock during shipment, the state of the contacts should be verified before initial use. | ||||
Multi-Function Timing Relay Function and Time Range Settings
Accessories
| Description | Pkg. Quantity | Cat. No. | ||
|
Setting Knob with Scale (for time setting without tools) |
10 | 700-FSK | |
|
Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002 |
5 | 199-FSA | |
|
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm |
10 | 100-FMS | |
| Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover |
10 | 100-FMP | ||
| Transparent Cover To be used with marking tag sheets |
100 | 100-FMC | ||
| Marking Tag Adapters To be used with marking tag: System 1492 W |
100 | ¬ | 100-FMA2 | |
| ¬ Cat. No. 100-FMA2 is only a marking tag carrier. Please refer to the Terminal Block Accessories section, IEC Marking System of this publication for appropriate marker cards to be used with this carrier. | ||||
Connection Diagrams
(A) On-Delay
|
(B) Off-Delay (Min. Pulse AC 50 ms…DC 30 ms)
|
(C) On- and Off-Delay
|
(D) One Shot
|
(E) Fleeting Off-Delay (Min. Pulse AC 50 ms…DC 30 ms)
|
(F) Flasher (Repeat Cycle Starts with Pulse)
|
(G) Flasher (Repeat Cycle Starts with Pause)
|
(I) On-Delay Pulse Generator
|
(J) On-Delay (Pulse Controlled)
|
(K) One Shot/ Watch Dog (Pulse Controlled)
|
(On) ON-Function (Off) OFF-Function
|
(L) Pulse Converter (Min. Pulse AC 50 ms…DC 30 ms)
|
Cleverly Designed Function Display LED (Green)
|
¬ A voltage other than the supply voltage can be used at B1, but must be within voltages specified on timer.
T Output 2 is selectable as instantaneous contact with sliding switch (Ä) on front panel (instantaneous when switch is down, timed when switch is up).
Available on multifunction "M," and single function "A" or "B" option timing relays along with code "4" (2PDT contacts). Bridge or potentiometer 10 kW, 0.25 W min. (low voltage) for external time setting. Set timer dial to 0.0.
Special Function Flasher (Repeat Cycle Starting with Pulse or Pause) Timing Relays
| Description |
|
|
Supply Voltages (A1/A2)
Z12 12V DC
U23 24…48V DC,
24…240V AC, 50/60 Hz
| Function Diagram / Connection Diagram |
(H) Flasher (Repeat Cycle Starting with Pulse or Pause)
The repeat cycle timer permits different settings for on and off times.
The following operating modes are possible:
700-FSH3V provides (2) range settings for t1 and t2.
Supply Voltage Controlled, Oscillating Mode Starting with Pause — Switch Ä is Up
|
Supply Voltage Controlled, Oscillating Mode Starting with Pulse — Switch Ä is Down
|
Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms — DC 30 ms) — Switch Ä is Up One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing s to Energize B1 will Initiate One Cycle.
|
Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms — DC 30 ms) — Switch Ä is Down One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing s to Energize B1 will Initiate One Cycle.
|
Note:If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.
|
|
| Function Diagram / Connection Diagram |
(Q) Off-Delay without Supply Voltage (True Off-Delay) — When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the time delay.
|
Note:Min. pulse (tp) required:
800 ms
|
Specifications
| Time Characteristics (according to VDE 0435, Part 2021) | |
| Setting Accuracy | ±5% of full scale |
| Repeatability | ±0.2% of the setting values |
| Tolerance | Voltage: ±0.001%/%DU Temperature: ±0.025%/°C |
| Supply | |
| Supply Voltages | 24…48V DC and 24…240V AC, 50/60 Hz (multi voltage) |
| Voltage Tolerance | 20…+20% (DC), 15…+10% (AC) |
| Power Consumption | 0.5 W at 24V DC, 5 VA at 240V AC |
| Time Energized | 100% |
| Reset Time | 50 ms |
| Voltage Interruption | £20 ms without reset (supply voltage) |
| Input Impedance | Relay ON: 3K-13K ohms Relay OFF: 0.7K-4K ohms |
| Cable Length (Supply Voltage Control) | Max. 250 m (800 ft) |
| Pulse Control (B1) | |
| Pulse Duration | ³50 ms (AC), ³30 ms (DC) |
| Input Voltage | Supply voltage range |
| Input Current | 1 mA |
| Max. Leakage Current | 400 micro Amps |
| Cable Length | Max. 250 m (800 ft) without parallel load between B1 and A2 Max. 50 m (160 ft) with load (<3 kW) between B1 and A2 |
| Outputs | |
| Contact Type | Relay as changeover switch |
| Dielectric Coil to Contact Withstand Voltage |
5000 V |
| Switching Capacity | Voltage: 440V AC |
| Current Ith (AC-1): 8 A (5 A for 700- FSQ) |
|
| Power: 2000 VA | |
| According to IEC 947-5-1: | |
| 3 A/440V AC (inductive load, AC 14) | |
| 3 A/250V AC (inductive load, AC 15) | |
| 1 A/24V DC (inductive load, DC 13) | |
| According to UL 508: | |
| 1.5 A/250V AC (B300) | |
| 3 A/120V AC (B300) | |
| Short-Circuit Resistance | 10 A gL |
| Life | Mechanical: 30 million operations |
| Electrical operations: | |
| 4 Mil. at 1 A/250V AC, cos f = 1 | |
| 0.2 Mil. at 6 A/250V AC, cos f = 1 | |
| 1.5 Mil. at 1 A/250V AC, cos f = 0.3 | |
| 0.3 Mil. at 3 A/250V AC, cos f = 0.3 | |
| 0.5 Mil. at 6 A/24V DC, resistive | |
| 2 Mil. at 4 A/24V DC, resistive | |
| 2 Mil. at 0.2 A/230V DC, resistive | |
| 1 Mil. at 0.4 A/24V DC, L/R = 20 ms | |
| 1 Mil. at 0.2 A/110V DC, L/R = 20 ms | |
| 1 Mil. at 0.1 A/230V DC, L/R = 20 ms | |
| State Indicator | 1 LED, combination signal |
| General Data | |
| Insulation Characteristics | 2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 ms surge voltage according to IEC 947-1 between all inputs and outputs |
| EMC/Interference Immunity | Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 ms Burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD discharge according to IEC 1000-4-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3 |
| EMC/Emission | Electromagnetic fields according to EN 55 022: class B |
| Safe Isolation | According to VDE 106, part 101 |
| Climatic Withstand | 56 Cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3 |
| Vibration Resistance | 4 g in three axes at 10…500 Hz, test FC according to IEC 68-2-6 |
| Shock Resistance | 50 g according to IEC 68-2-27 |
| Protection Class | Enclosure:IP 40 IP 30 (Single-function) Terminal:IP 20 according to IEC 947-1 |
| Weight | 100 g |
| Approval | UL, C-UL |
| Ambient Temperature | Open: 25…+60 °C Enclosed: 25…+45 °C Storage: 40…+85 °C |
| Terminals | Screw terminal M3.5 for Number 2 Posidrive, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 Nm, max. 1.2 Nm). Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106. |
| Mounting | Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type) |
| Disposal | Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium |
| Certifications | cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked |
| Standards | EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14 |
¬ See Performance Data.