Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > General Purpose Electronic Timers and Counters > Bulletin 700-FS High Performance Timing Relay
Bulletin 700-FS High Performance Timing Relay
| Introduction | Standards Compliance and Certifications | Catalog Number Explanation | Product Selection | Accessories | Connection Diagrams | Specifications |
| Time Characteristics (according to VDE 0435, Part 2021) | |
| Setting Accuracy | ±5% of full scale |
| Repeatability | ±0.2% of the setting values |
| Tolerance | Voltage: ±0.001%/%DU Temperature: ±0.025%/°C |
| Supply | |
| Supply Voltages | 24…48V DC and 24…240V AC, 50/60 Hz (multi voltage) |
| Voltage Tolerance | 20…+20% (DC), 15…+10% (AC) |
| Power Consumption | 0.5 W at 24V DC, 5 VA at 240V AC |
| Time Energized | 100% |
| Reset Time | 50 ms |
| Voltage Interruption | £20 ms without reset (supply voltage) |
| Input Impedance | Relay ON: 3K-13K ohms Relay OFF: 0.7K-4K ohms |
| Cable Length (Supply Voltage Control) | Max. 250 m (800 ft) |
| Pulse Control (B1) | |
| Pulse Duration | ³50 ms (AC), ³30 ms (DC) |
| Input Voltage | Supply voltage range |
| Input Current | 1 mA |
| Max. Leakage Current | 400 micro Amps |
| Cable Length | Max. 250 m (800 ft) without parallel load between B1 and A2 Max. 50 m (160 ft) with load (<3 kW) between B1 and A2 |
| Outputs | |
| Contact Type | Relay as changeover switch |
| Dielectric Coil to Contact Withstand Voltage |
5000 V |
| Switching Capacity | Voltage: 440V AC |
| Current Ith (AC-1): 8 A (5 A for 700- FSQ) |
|
| Power: 2000 VA | |
| According to IEC 947-5-1: | |
| 3 A/440V AC (inductive load, AC 14) | |
| 3 A/250V AC (inductive load, AC 15) | |
| 1 A/24V DC (inductive load, DC 13) | |
| According to UL 508: | |
| 1.5 A/250V AC (B300) | |
| 3 A/120V AC (B300) | |
| Short-Circuit Resistance | 10 A gL |
| Life | Mechanical: 30 million operations |
| Electrical operations: | |
| 4 Mil. at 1 A/250V AC, cos f = 1 | |
| 0.2 Mil. at 6 A/250V AC, cos f = 1 | |
| 1.5 Mil. at 1 A/250V AC, cos f = 0.3 | |
| 0.3 Mil. at 3 A/250V AC, cos f = 0.3 | |
| 0.5 Mil. at 6 A/24V DC, resistive | |
| 2 Mil. at 4 A/24V DC, resistive | |
| 2 Mil. at 0.2 A/230V DC, resistive | |
| 1 Mil. at 0.4 A/24V DC, L/R = 20 ms | |
| 1 Mil. at 0.2 A/110V DC, L/R = 20 ms | |
| 1 Mil. at 0.1 A/230V DC, L/R = 20 ms | |
| State Indicator | 1 LED, combination signal |
| General Data | |
| Insulation Characteristics | 2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 ms surge voltage according to IEC 947-1 between all inputs and outputs |
| EMC/Interference Immunity | Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 ms Burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD discharge according to IEC 1000-4-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3 |
| EMC/Emission | Electromagnetic fields according to EN 55 022: class B |
| Safe Isolation | According to VDE 106, part 101 |
| Climatic Withstand | 56 Cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3 |
| Vibration Resistance | 4 g in three axes at 10…500 Hz, test FC according to IEC 68-2-6 |
| Shock Resistance | 50 g according to IEC 68-2-27 |
| Protection Class | Enclosure:IP 40 IP 30 (Single-function) Terminal:IP 20 according to IEC 947-1 |
| Weight | 100 g |
| Approval | UL, C-UL |
| Ambient Temperature | Open: 25…+60 °C Enclosed: 25…+45 °C Storage: 40…+85 °C |
| Terminals | Screw terminal M3.5 for Number 2 Posidrive, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 Nm, max. 1.2 Nm). Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106. |
| Mounting | Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type) |
| Disposal | Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium |
| Certifications | cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked |
| Standards | EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14 |
¬ See Performance Data.