Specifications

  Cat. No. 700-HV…
Electrical Ratings
Pilot Duty RatingT  NEMA B300
Rated Thermal Current (Ith) 10 A
Rated Insulation Voltage (Ui) 250V IEC, 300V UL/CSA
Contacts Inductive Make Break Hp
  Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2  
120V AC 30 A 3 A 1/2 N.O. 1/3 N.C.
240V AC 15 A 1.5 A 1/2 N.O. 1/3 N.C.
Resistive 28V DC 10 A 10 A
Permissible Coil Voltage Variation 85…110 of Nominal Voltage at 50 Hz
85…110 of Nominal Voltage at 60 Hz
80…110 of Nominal Voltage at DC
Power Consumption
±10%
AC 24V AC 2 VA
120V AC 4 VA
240V AC 4 VA
DC 1.3 W
Design Specification/Test Requirements
Dielectric Withstand Voltage Pole-to-Pole, same circuit (VRMS) 1000V AC
Pole-to-Pole, different circuits (VRMS) 2000V AC
Contact-to-Coil (VRMS) 2000V AC
Electrical Life Operations 100,000 minimum
Switching Frequency Operations 1800/hr
Coil Voltages See product selection
Mechanical
Degree of Protection Open Type (Guarded Terminal Sockets)
Mechanical Life Operations 10 x 106
Switching Frequency Operations 18,000/hr
Timing Duty Cycle Continuous
Repeat Accuracy
(constant voltage and temperature)
±2% (Time Delay: 0.1…2 s)
±1% (Time Delay: >2 s)
Repeat Accuracy
(variable voltage and temperature)
±10%
Scale Tolerance High End of Range +5%
Low End of Range -50%
Reset Time 100 ms
Environmental
Temperature Operating –28…+65 °C (50 °C max., 240V AC coil)
(–18…+149 °F) (122 °F max., 240V AC coil)
Storage –55…+85 °C
(–67…+185 °F)
Altitude 2000 m (6560 ft.)
Construction
Insulating Material Molded High Dielectric Material
Enclosure Impact Resistant Dust Cover
Contact Material Silver Cadmium Oxide
Terminal Markings on Socket In accordance with EN50 005
Sockets 8-Pin Socket
Cat. No. 700-HN100, -HN125
Certifications CSA Certified, File 223833; UL Recognized, File E3125; Guide NLDX 2; cULus Listed when used with 700-HN100 and 700-HN125 sockets; CE Marked
Standards EN 61812; EN 60947-1, -5-1; CSA 22.2 No. 14; UL 508
  
¬ Performance Data — See Performance Data, this catalog.
T NEMA Rating Chart is in publication 700-SG003B-EN-P._

Timing Diagram

Click to enlarge - 700HVtimediag