| Model
|
Timing Mode
|
Contact Output
|
Input Voltages
|
Timing Range
|
Socket Type
|
Cat. No.
|
|
On-Delay One Shot Repeat cycle, OFF-start Repeat cycle, ON-start
|
4PDT
|
12V DC
|
.1 s…10 min
|
700-HN103 700-HN128
|
700-HNC44AZ12
|
| .1 min…10 hr
|
700-HNC44BZ12
|
| 24V DC
|
.1 s…10 min
|
700-HNC44AZ24
|
| .1 min…10 hr
|
700-HNC44BZ24
|
| 48V DC
|
.1 s…10 min
|
700-HNC44AZ48
|
| .1 min.…10 hr
|
700-HNC44BZ48
|
| 100…110V DC
|
.1 s…10 min
|
700-HNC44AZ11
|
| .1 min…10 hr
|
700-HNC44BZ11
|
| 125V DC
|
.1 s…10 min
|
700-HNC44AZ25
|
| .1 min.…10 hr
|
700-HNC44BZ25
|
| 24V AC
|
.1 s…10 min
|
700-HNC44AA24
|
| .1 min.…10 hr
|
700-HNC44BA24
|
| 100…120V AC
|
.1 s…10 min
|
700-HNC44AA12
|
| .1 min.…10 hr
|
700-HNC44BA12
|
| 200…230V AC
|
.1 s…10 min
|
700-HNC44AA23
|
| Cat. No. 700-HNC
|
.1 min.…10 hr
|
700-HNC44BA23
|
|
|
|
|
Description
|
Pkg. Quantity
|
Cat. No.
|
|
Screw Terminal Socket — Panel or DIN Rail Mounting. Guarded Terminal Construction 14-Blade miniature socket for use with Bulletin 700-HNC timers.
|
10
|
700-HN103
|
| Cat. No. 700-HN103
|
|
Screw Terminal Base Sockets — Panel or DIN Rail Mounting. Open Style Construction 14-blade miniature socket for use with Bulletin 700-HNC timers.
|
10
|
700-HN128
|
| Cat. No. 700-HN128
|
|
|
|
|
Description
|
Pkg. Quantity
|
Cat. No.
|
|
Screw Terminal Socket Panel or DIN Rail Mounting. Guarded Terminal Construction 14-blade miniature socket for use with Bulletin 700-HNC timers. This socket has coil and contact separation.
|
10
|
700-HN104
|
| Cat. No. 700-HN104
|
|
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with Bulletin 700-HNC Timers. Secures Timer in Socket.
|
10
|
700-HN163
|
| Cat. No. 700-HN163
|
|
|
| Ratings
|
| Item
|
700-HNC
|
| Pilot Duty Rating
|
NEMA B300
|
| Pin type
|
Plug-in
|
| Operating voltage range
|
85%…110% of rated supply voltage (12V DC: 90%…110% of rated supply voltage)T
|
| Reset voltage
|
10% min. of rated supply voltage
|
| Power consumption
|
24V AC:
|
Relay ON: Relay OFF:
|
1.5 VA (1.1 W) (at 24V AC, 60 Hz) 0.2 VA (0.1 W) (at 24V AC, 60 Hz)
|
| 100…120V AC:
|
Relay ON: Relay OFF:
|
1.5 VA (1.3 W) (at 120V AC, 60 Hz) 0.8 VA (0.5 W) (at 120V AC, 60 Hz)
|
| 200…230V AC:
|
Relay ON: Relay OFF:
|
1.8 VA (1.5 W) (at 230V AC, 60 Hz) 1.2 VA (0.9 W) (at 230V AC, 60 Hz)
|
| 12V DC:
|
Relay ON: Relay OFF:
|
0.9 W (at 12V DC) 0.07 W (at 12V DC)
|
| 24V DC:
|
Relay ON: Relay OFF:
|
0.9 W (at 24V DC) 0.07 W (at 24V DC)
|
| 48V DC:
|
Relay ON: Relay OFF:
|
1.0 W (at 48V DC) 0.2 W (at 48V DC)
|
| 100…110V DC:
|
Relay ON: Relay OFF:
|
1.3 W (at 110V DC) 0.3 W (at 110V DC)
|
| 125V DC:
|
Relay ON: Relay OFF:
|
1.3 W (at 125V DC) 0.3 W (at 125V DC)
|
| Control outputs
|
4PDT: 5 A at 250V AC, resistive load (cosf = 1)
|
| Characteristics
|
|
120V AC
|
30 A
|
| Make
|
240V AC
|
15 A
|
|
120V AC
|
3 A
|
| Break
|
240V AC
|
1.5 A
|
| Hp at 120V AC
|
1/6 Hp
|
| Hp at 240V AC
|
1/6 Hp
|
| Accuracy of operating time
|
±1% FS max. (1 s range: ±1%±10 ms max.)
|
| Setting error
|
±10%±50 ms FS max.
|
| Reset time
|
Min. power-opening time: 0.1 s max. (including halfway reset)
|
| Influence of voltage
|
±2% FS max.
|
| Influence of temperature
|
±2% FS max.
|
| Insulation resistance
|
100 mW min. (at 500V DC)
|
| Dielectric strength
|
2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts)¬
|
| 2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output)
|
| 2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
|
| 1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
|
| 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
|
| Vibration resistance
|
Malfunction:10…55 Hz, 0.5 mm single amplitude
|
| Shock resistance
|
Malfunction:100 m/s2 (approx. 10G)
|
| Ambient temperature
|
Operating:-10 °C…50 °C (with no icing)
|
| Storage:-25 °C…65 °C (with no icing)
|
| Ambient humidity
|
Operating:35%…85%
|
| Life expectancy
|
Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr)
|
| Electrical:4PDT:
|
| 200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
|
|
|
| ¬ Single-phase, full-wave-rectified power supplies can be used.
|
| T When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C…50 °C, supply 90%…110% of the rated supply voltages supply 95%…110% with 12V DC type).
|
| Characteristics, Continued
|
|
| Noise immunity
|
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise)
|
| Static immunity
|
Destruction:8 kV Malfunction:4 kV
|
| Enclosure rating
|
IP40
|
| Weight
|
Approx. 50 g
|
| EMC
|
Emission Enclosure:EN55011 Group 1 class A
|
| Emission AC Mains:EN55011 Group 1 class A
|
| Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
|
| 8 kV air discharge (level 3)
|
| Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3)
|
| 10 V/m (pulse modulated, 900 MHz)
|
| Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3)
|
| Immunity Burst:EN61000-4-4:2 kV power-line (level 3)
|
| 2 kV I/O signal-line (level 4)
|
| Standards
|
UL 508, CSA 22.2 No. 14, EN/IEC 61812-1
|
| Certifications
|
cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CSA Certified (File 224268), CE Marked, C-Tick Marked
|
|
|
| Operating Mode
|
Timing Charts / Wiring Diagram
|
|
|
|
|
|
|
|
|
|
|
|
| Cat. No.
|
Time Range
|
Time Setting Range
|
Setting
|
Factory-Set
|
700-HNC44AZ12 700-HNC44AZ24 700-HNC44AZ48 700-HNC44AZ11 700-HNC44AZ25 700-HNC44AA24 700-HNC44AA12 700-HNC44AA23
|
1 s
|
0.1 s…1 s
|
|
Yes
|
| 10 s
|
1 s…10 s
|
|
No
|
| 1 min
|
0.1 s…1 min
|
|
No
|
| 10 min
|
1…10 min
|
|
No
|
700-HNC44BZ12 700-HNC44BZ24 700-HNC44BZ48 700-HNC44BZ11 700-HNC44BZ25 700-HNC44BA24 700-HNC44BA12 700-HNC44BA23
|
1 min
|
0.1…1 min
|
|
Yes
|
| 10 min
|
1…10 min
|
|
No
|
| 1 hr
|
0.1…1 hr
|
|
No
|
| 1 hr
|
1…10 hr
|
|
No
|
|
|