General Purpose Electronic Timers and Counters

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > General Purpose Electronic Timers and Counters > Bulletin 700-HNC Miniature Timing Relay

Bulletin 700-HNC Miniature Timing Relay

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Specifications

Ratings
Item 700-HNC
Pilot Duty Rating NEMA B300
Pin type Plug-in
Operating voltage range 85%…110% of rated supply voltage (12V DC: 90%…110% of rated supply voltage)T 
Reset voltage 10% min. of rated supply voltage‡ 
Power consumption 24V AC: Relay ON:
Relay OFF:
1.5 VA (1.1 W) (at 24V AC, 60 Hz)
0.2 VA (0.1 W) (at 24V AC, 60 Hz)
100…120V AC: Relay ON:
Relay OFF:
1.5 VA (1.3 W) (at 120V AC, 60 Hz)
0.8 VA (0.5 W) (at 120V AC, 60 Hz)
200…230V AC: Relay ON:
Relay OFF:
1.8 VA (1.5 W) (at 230V AC, 60 Hz)
1.2 VA (0.9 W) (at 230V AC, 60 Hz)
12V DC: Relay ON:
Relay OFF:
0.9 W (at 12V DC)
0.07 W (at 12V DC)
24V DC: Relay ON:
Relay OFF:
0.9 W (at 24V DC)
0.07 W (at 24V DC)
48V DC: Relay ON:
Relay OFF:
1.0 W (at 48V DC)
0.2 W (at 48V DC)
100…110V DC: Relay ON:
Relay OFF:
1.3 W (at 110V DC)
0.3 W (at 110V DC)
125V DC: Relay ON:
Relay OFF:
1.3 W (at 125V DC)
0.3 W (at 125V DC)
Control outputs 4PDT: 5 A at 250V AC, resistive load (cosf = 1)
Characteristics
Click to enlarge - 700HA-69-1 120V AC 30 A
Make 240V AC 15 A
Click to enlarge - 700HA-69-2 120V AC 3 A
Break 240V AC 1.5 A
Hp at 120V AC 1/6 Hp
Hp at 240V AC 1/6 Hp
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 mW min. (at 500V DC)
Dielectric strength 2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts)¬ 
2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output)
2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Malfunction:10…55 Hz, 0.5 mm single amplitude
Shock resistance Malfunction:100 m/s2 (approx. 10G)
Ambient temperature Operating:-10 °C…50 °C (with no icing)
Storage:-25 °C…65 °C (with no icing)
Ambient humidity Operating:35%…85%
Life expectancy Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr)
Electrical:4PDT:
200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
  
¬ Single-phase, full-wave-rectified power supplies can be used.
T When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C…50 °C, supply 90%…110% of the rated supply voltages supply 95%…110% with 12V DC type).

Characteristics, Continued  
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise)
Static immunity Destruction:8 kV
Malfunction:4 kV
Enclosure rating IP40
Weight Approx. 50 g
EMC Emission Enclosure:EN55011 Group 1 class A
Emission AC Mains:EN55011 Group 1 class A
Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3)
Immunity Burst:EN61000-4-4:2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Standards UL 508, CSA 22.2 No. 14, EN/IEC 61812-1
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CSA Certified (File 224268), CE Marked, C-Tick Marked
  

Timing Charts

Note:t:Set time
Rt:Reset time


Operating Mode Timing Charts / Wiring Diagram
Click to enlarge - 700HNC-130-1 Click to enlarge - 700HNC-130-2 Click to enlarge - 700HNC-130-5
Click to enlarge - 700HNC-130-3 Click to enlarge - 700HNC-130-4
Click to enlarge - 700HNC-130-6 Click to enlarge - 700HNC-130-7
Click to enlarge - 700HNC-130-8 Click to enlarge - 700HNC-130-9
  

Pulse Operation

A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNC timing relay in interval mode as shown in the following timing charts.

Click to enlarge - 700HNC-130-10


Click to enlarge - 700HNC-130-11


DIP Switch Settings

Time Ranges

Cat. No. Time Range Time Setting Range Setting Factory-Set
700-HNC44AZ12
700-HNC44AZ24
700-HNC44AZ48
700-HNC44AZ11
700-HNC44AZ25
700-HNC44AA24
700-HNC44AA12
700-HNC44AA23
1 s 0.1 s…1 s Click to enlarge - 700HNC-131-1 Yes
10 s 1 s…10 s Click to enlarge - 700HNC-131-2 No
1 min 0.1 s…1 min Click to enlarge - 700HNC-131-3 No
10 min 1…10 min Click to enlarge - 700HNC-131-4 No
700-HNC44BZ12
700-HNC44BZ24
700-HNC44BZ48
700-HNC44BZ11
700-HNC44BZ25
700-HNC44BA24
700-HNC44BA12
700-HNC44BA23
1 min 0.1…1 min Click to enlarge - 700HNC-131-1 Yes
10 min 1…10 min Click to enlarge - 700HNC-131-2 No
1 hr 0.1…1 hr Click to enlarge - 700HNC-131-3 No
1 hr 1…10 hr Click to enlarge - 700HNC-131-4 No
  

Note: The top two DIP switch pins are used to select the time ranges.


Click to enlarge - 700HNC-131-9


Operating Modes

Operating Mode Setting Factory-set
ON-delay Click to enlarge - 700HNC-131-1 Yes
One Shot Click to enlarge - 700HNC-131-2 No
Repeat Cycle OFF-start Click to enlarge - 700HNC-131-3 No
Repeat Cycle ON-start Click to enlarge - 700HNC-131-4 No
  

Note: The bottom two DIP switch pins are used to select the time ranges.