Timing Mode
|
Socket Type
|
Contact Output
|
Timing Range
|
Input Voltage
|
Cat. No.
|
|
On-Delay One Shot Repeat Cycle, OFF-start Repeat Cycle, ON-start
|
700-HN121
|
SPDT¬
|
0.1 s…10 min
|
12V DC
|
700-HNK41AZ12
|
| 24V DC
|
700-HNK41AZ24
|
| 24V AC
|
700-HNK41AA24
|
| 0.1 min…10 hr
|
12V DC
|
700-HNK41BZ12
|
| 24V DC
|
700-HNK41BZ24
|
| 24V AC
|
700-HNK41BA24
|
| 700-HN122
|
DPST-NOT
|
0.1 s…10 min
|
12V DC
|
700-HNK42AZ12
|
| 24V DC
|
700-HNK42AZ24
|
| 24V AC
|
700-HNK42AA24
|
| 0.1 min…10 hr
|
12V DC
|
700-HNK42BZ12
|
| 24V DC
|
700-HNK42BZ24
|
Cat. No. 700-HNK SPDT, DPST-NO
|
24V AC
|
700-HNK42BA24
|
|
|
| ¬ 5-blade terminal type only.
|
| T 8-blade terminal type only.
|
|
|
Description
|
Pkg. Quantity
|
Cat. No.
|
|
Screw Terminal Socket — Panel or DIN Rail Mounting 5-blade miniatue socket. For use with 1-pole type 700-HNK41 timers. Socket includes a retainer clip.
|
10
|
700-HN121
|
| Cat. No. 700-HN121
|
|
Screw Terminal Socket — Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole, Bulletin 700-HNK42 timers. This socket includes a retainer clip.
|
10
|
700-HN122
|
| Cat. No. 700-HN122
|
|
|
| Ratings
|
| Item
|
|
| Pilot Duty Rating
|
NEMA B300
|
| Rated Supply Voltage
|
24V AC; 12, 24V DC
|
| Pin Type
|
Plug-in
|
| Operating Mode
|
ON-delay, One Shot, Repeat Cycle OFF start, or Repeat Cycle ON start selectable with DIP switch.
|
| Operating Voltage Range
|
85%…110% of rated supply voltage (12 VDC: 90%…110% of rated supply voltage)¬
|
| Power Consumption
|
24V AC:Relay ON:approx. 0.8 VA (at 24 VAC, 60 Hz) Relay OFF:0.5 VA (at 24V AC, 60 Hz) 12V DC:Relay ON:approx. 0.4 W (at 12V DC) Relay OFF:0.1 W (at 12V DC) 24V DC:Relay ON:approx. 0.5 W (at 24V DC) Relay OFF:0.2 W (at 24V DC)
|
| Control Outputs
|
5 A at 250V AC, resistive load (cosf = 1) The minimum applicable load is 10 mA at 5 VDC (P reference value).
|
| Characteristics
|
|
120V AC
|
30 A
|
| Make
|
240V AC
|
15 A
|
|
120V AC
|
3 A
|
| Break
|
240V AC
|
1.5 A
|
| Hp at 240V AC
|
1/6 Hp
|
| Accuracy of Operating Time
|
±1% FS max. (1 s range: +1%±10 ms max.)
|
| Setting Error
|
±15%+50 ms FS max.
|
| Reset Time
|
Min. power-opening time:
|
12, 24V DC: 0.1 s max. (including halfway reset) 24V AC: 0.5 s max. (including halfway reset)
|
| Influence of Voltage
|
±2% FS max.
|
| Influence of Temperature
|
±2% FS max.
|
| Insulation Resistance
|
100 mW min. (at 500V DC)
|
| Dielectric Strength
|
2000V AC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different poles) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
|
| Vibration Resistance
|
Malfunction:10…55 Hz, 0.5 mm single amplitude
|
| Shock Resistance
|
Malfunction:100 m/s2 (approx. 10G)
|
| Ambient Temperature
|
Operating:-10 °C…50 °C (with no icing) Storage:-25 °C…65 °C (with no icing)
|
| Ambient Humidity
|
Operating:35…85%
|
| Life Expectancy
|
Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr) Electrical:100 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
|
| Impulse Withstand Voltage
|
Between power terminals: 1 kV
|
| Noise Immunity
|
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise)
|
| Static Immunity
|
Destruction:8 kV Malfunction:4 kV
|
| Enclosure Rating
|
IP20
|
| Weight
|
Approx. 18 g
|
| EMC
|
Emission Enclosure:EN55011 Group 1 class A Emission AC Mains:EN55011 Group 1 class A Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz…1GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst:EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
|
| Standards
|
UL508, CSA C22.2 No. 14, EN/IEC 60947-5-1, EN/IEC 61812-1
|
| Certifications
|
cURus Recognized Component (File No. E14843, Guide NRNTZ/NRNT8), CE Marked, C-Tick Marked
|
|
|
¬ When using 700-HNK timer in any place where the ambient temperature is more than 50 °C, supply 90…110% of the rated voltages (12V DC: 95…11 % of the rated voltage).
|
| Mode
|
Terminals
|
| Pulse Operation
|
Power supply between 3 and 8 Short-circuit between 4 and 1 Input signal between 3 and 1
|
| Operating mode; One shot and all other modes
|
Power supply between 1 and 8
|
|
|
| Cat. No.
|
Time Range
|
Time Setting Range
|
Setting
|
Factory-Set
|
700-HNK41AZ12 700-HNK41AZ24 700-HNK41AA24 700-HNK42AZ12 700-HNK42AZ24 700-HNK42AA24
|
1 s
|
0.1…1 s
|
|
Yes
|
| 10 s
|
1…10 s
|
|
No
|
| 1 min
|
0.1 s…1 min
|
|
No
|
| 10 min
|
1…10 min
|
|
No
|
700-HNK41BZ12 700-HNK41BZ24 700-HNK41BA24 700-HNK42BZ12 700-HNK42BZ24 700-HNK42BA24
|
1 min
|
0.1…1 min
|
|
Yes
|
| 10 min
|
1…10 min
|
|
No
|
| 1 hr
|
0.1…1 hr
|
|
No
|
| 10 hr
|
1…10 hr
|
|
No
|
|
|
| Note:The left two DIP switch pins are used to select the time ranges.
|
| Operating Mode
|
Setting
|
Factory-set
|
| On-delay
|
|
Yes
|
| One Shot
|
|
No
|
| Repeat Cycle Off-start
|
|
No
|
| Repeat Cycle On-start
|
|
No
|
|
|
| Note:The right two DIP switch pins are used to select the operating modes.
|