Bulletin 700-HS Timing Relay
| Product Overview |
|
|
Bulletin 700-HS
- Timing relay (ON-delay or OFF-delay)
- Rugged blade-style quick connect socket mounting
- 12 A, DPDT contact rating
- 0.1…180 s Range Available As a Single Range or Fixed Timing (0.1 s…600 s)
Standards Compliance and Certifications
See Specifications.
Product Selection
| Build a Catalog Number |
Single Range Timing Relay with Blade Style Quick Connect/Solder Terminations
| Operating Mode | Wiring Diagrams | ||
| U.S./Canada | International | ||
|
On-Delay |
|
|
| Socket | 700-HN154 or 700-HN153 |
700-HN153 | |
| Off-Delay |
|
|
|
| Bulletin 700-HS DPDT 2-Pole 2 Form C Contacts |
Socket | 700-HN154 or 700-HN153 |
700-HN153 |
| 700 | | HS | 2 | 2 | A | A1 | ||||
| a | b | c | d | e |
| a | |
| Timer Type | |
| Code | Description |
| HS | Square Base Adjustable Timing Relay |
| b | |
| Mode Type | |
| Code | Mode |
| 1 | On-Delay |
| 2 | Off-Delay |
| c | |
| Number of Poles | |
| Code | Description |
| 2 | 2PDT |
| d | |
| Timing Range | |
| Code | Adjustable Time — Type HS |
| A | 0.1…10 s |
| B | 1.0…100 s |
| C | 0.1…10 min |
| D | 1.0…100 min |
| E | 0.1…10 hr |
| e | |
| Coil Voltage | |
| Code | Volts |
| U12 | 12V AC/DC, 50/60 Hz |
| U24 | 24V AC/DC, 50/60 Hz |
| U120 | 120V AC/DC, 50/60 Hz |
Fixed Timing Relays
| 700 | | HSF | 2 | 2 | 025 | S | U24 | |||||
| a | b | c | d | e | f |
| a | |
| Timer Type | |
| Code | Description |
| HSF | Square Base Fixed Timing Relay |
| b | |
| Mode Type | |
| Code | Mode |
| 1 | On-Delay |
| 2 | Off-Delay |
| c | |
| Number of Poles | |
| Code | Description |
| 2 | 2PDT |
| d | |
| Timing Value ¬ | |
| Code | Value |
| 001…999 | The three digit code represents a numeric value with one decimal place. For example: code 001 is 0.1, code 025 is 2.5, and code 999 is 99.9 The acceptable range for each time unit is listed below: Seconds - 001…999 Minutes - 001…999 Hours - 001…100 |
| e | |
| Timing Units ¬ | |
| Code | Units |
| S | Seconds |
| M | Minutes |
| H | Hours |
| f | |
| Coil Voltage | |
| Code | Volts |
| U12 | 12V AC/DC, 50/60 Hz |
| U24 | 24V AC/DC, 50/60 Hz |
| U120 | 120V AC/DC, 50/60 Hz |
¬ Use both the Timing Value and Timing Units tables to properly select the desired fixed time relay.
For example: 700-HSF22025SU24 selects a timer value of 2.5 seconds and 700-HSF22025MU24 selects a timer value of 2.5 minutes.
Accessories
¬ Bulletin 700-HS Timing Relay, Socket, and Retainer Clip Reference Chart
| Relay Type | Socket | Retainer Clip |
| 700-HS | 700-HN153 | 700-HN160 |
| 700-HN154 | ||
Specifications
| Cat. No. 700-HS… | Cat. No. 700-HSF… | |||||||
| Electrical Ratings | ||||||||
| Pilot Duty Rating T | NEMA B300 | |||||||
| Rated Thermal Current (Ith) | 12 A | |||||||
| Rated Insulation Voltage (Ui) | 250V IEC, 300V UL/CSA |
|||||||
| Contacts | Inductive | Make | Break | Hp | Make | Break | Hp | |
|
|
|
|
|
|||||
| 120V AC | 30 A | 3 A | 1/3 | 30 A | 3 A | 1/3 | ||
| 240V AC | 15 A | 1.5 A | 1/2 | 15 A | 1.5 A | 1/2 | ||
| Resistive 30V DC | 12 A | 12 A | — | 12 A | 12 A | — | ||
| Permissible Coil Voltage Variation | 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC |
|||||||
| Power Consumption ±10% | AC | 24V AC | 2 VA | |||||
| 120V AC | 3 VA | |||||||
| 240V AC | — | |||||||
| DC | 1.3 W | |||||||
| Design Specification/Test Requirements | ||||||||
| Dielectric Withstand Voltage |
Pole-to-Pole, same circuit (VRMS) | 1000V AC | ||||||
| Pole-to-Pole, different circuits (VRMS) | 2000V AC | |||||||
| Contact-to-Coil (VRMS) | 2000V AC | |||||||
| Electrical Life Operations | 100,000 minimum | |||||||
| Switching Frequency Operations | 360/hr | |||||||
| Coil Voltages | See product selection | |||||||
| Mechanical | ||||||||
| Degree of Protection | Open Type (Guarded Terminal Sockets) | |||||||
| Mechanical Life Operations | 10 x 106 | |||||||
| Switching Frequency Operations | 18,000/hr | |||||||
| Timing | Duty Cycle | Continuous | ||||||
| Repeat Accuracy (constant voltage and temperature) |
±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s) |
|||||||
| Repeat Accuracy (variable voltage and temperature) |
±15% | |||||||
| Fixed Time Setting Accuracy | — | ±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s) |
||||||
| Scale Tolerance |
High End of Range | +5% | — | |||||
| Low End of Range | 50% | — | ||||||
| Reset Time | ON Delay | 100 ms | ||||||
| OFF Delay | 40 ms | |||||||
| Environmental | ||||||||
| Temperature | Operating | 28…+65 °C (18…+149 °F) |
||||||
| Storage | 55…+85 °C (67…+185 °F) |
|||||||
| Altitude | 2000 m (6560 ft) | |||||||
| Construction | ||||||||
| Insulating Material | Molded High Dielectric Material | |||||||
| Enclosure | Impact Resistant Dust Cover | |||||||
| Contact Material | Silver Nickel | |||||||
| Terminal Markings on Socket | In accordance with EN 50 005 | |||||||
| Sockets | 8- or 11-Blade (On = 8, Off = 11) 700-HN153 -HN154 |
|||||||
| Certifications | CSA Certified, File 233833, UL Recognized, File E3125 Guide NLDX 2, cUus Listed when used with 700-HN153 and 700-HN154 sockets (File E3125, Guide NLDX/NLDX7), CE Marked |
|||||||
| Standards | EN 61812, EN 60947-5-1, CSA 22.2, UL 508 | |||||||
| ¬ See Performance Data. | ||||||||
| T NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. | ||||||||
Trigger Signal Cat. Nos. 700-HT / -HS
Contact closure provides signal to timer. A low energy signal is generated by the 700-HT / -HS timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.
Timing Diagrams
|
|
Approximate Dimensions
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
|
|
| Cat. No. | A | B | C | D | Approx. Shipping Wt. |
| 199-DR1 | 35 (1-3/8) |
27 (1-1/16) |
7.5 (19/64) |
1.02 (1/64) |
1.85 kg (4.07 lbs.) (10/pkg) |
| 199-DR4 | 35 (1-3/8) |
27 (1-1/16) |
15 (19/32) |
2.3 (3/32) |
3.68 kg (8 lbs.) (5/pkg) |
|
|