Bulletin 700-HS Timing Relay

Product Overview


Click to enlarge - 700-HS


Click to enlarge - 700-HSF


Bulletin 700-HS


Standards Compliance and Certifications

See Specifications.

Product Selection

Build a Catalog Number


Single Range Timing Relay with Blade Style Quick Connect/Solder Terminations

  Operating Mode Wiring Diagrams
U.S./Canada International
Click to enlarge - 700-HS On-Delay Click to enlarge - 700HS-151-4_b Click to enlarge - 700HS-151-5
Socket 700-HN154 or
700-HN153
700-HN153
Off-Delay Click to enlarge - 700HS-151-6_b Click to enlarge - 700HS-151-7
Bulletin 700-HS
DPDT 2-Pole
2 Form C Contacts
Socket 700-HN154 or
700-HN153
700-HN153
  

700 HS    2    2    A    A1
      a    b    c    d    e

a
Timer Type
Code Description
HS Square Base Adjustable Timing Relay

b
Mode Type
Code Mode
1 On-Delay
2 Off-Delay

c
Number of Poles
Code Description
2 2PDT

d
Timing Range
Code Adjustable Time — Type HS
A 0.1…10 s
B 1.0…100 s
C 0.1…10 min
D 1.0…100 min
E 0.1…10 hr

e
Coil Voltage
Code Volts
U12 12V AC/DC, 50/60 Hz
U24 24V AC/DC, 50/60 Hz
U120 120V AC/DC, 50/60 Hz

Fixed Timing Relays

  Description
Click to enlarge - 700-HSF Bulletin 700-HSF fixed timing relays feature a plug-in square base with blade style terminations. Construction is the same as the Bulletin 700-HS timing relay except that the adjustment knob has been removed to help prevent unwanted tampering. The timing and output specifications are identical to those of the Bulletin 700-HS timing relay. Setting will be ±5% of the time ordered.
Socket: Cat. No. 700-HN153 or 700-HN154
Bulletin 700-HSF
DPDT 2 Pole
2 Form C Contacts
  

700 HSF    2    2    025    S    U24
      a    b    c    d    e    f

a
Timer Type
Code Description
HSF Square Base Fixed Timing Relay

b
Mode Type
Code Mode
1 On-Delay
2 Off-Delay

c
Number of Poles
Code Description
2 2PDT

d
Timing Value ¬ 
Code Value
001…999 The three digit code represents a numeric value with one decimal place.
For example: code 001 is 0.1, code 025 is 2.5, and code 999 is 99.9
The acceptable range for each time unit is listed below:
Seconds - 001…999
Minutes - 001…999
Hours - 001…100

e
Timing Units ¬ 
Code Units
S Seconds
M Minutes
H Hours

f
Coil Voltage
Code Volts
U12 12V AC/DC, 50/60 Hz
U24 24V AC/DC, 50/60 Hz
U120 120V AC/DC, 50/60 Hz

¬ Use both the Timing Value and Timing Units tables to properly select the desired fixed time relay.
For example: 700-HSF22025SU24 selects a timer value of 2.5 seconds and 700-HSF22025MU24 selects a timer value of 2.5 minutes.


Accessories

  Description Pkg. Qty. Cat. No.
Click to enlarge - 700_HN153 Screw Terminal Socket — Panel or DIN Rail Mounting. Guarded Terminal Construction
11-blade socket for use with Bulletin 700-HB relays. This socket has coil and contact separation as well as the ability to use optional plug-in modules ( 700-A__ accessories, LED, surge suppression, timing modules).
10 700-HN153
Cat. No. 700-HN153
Click to enlarge - 700HB-76-6 Screw Terminal Base Socket — Panel or DIN Rail Mounting. Open Style Construction
11-blade for use with Bulletin 700-HB relays.
10 700-HN154
Cat. No. 700-HN154
Click to enlarge - 700SA-32-4 DIN (#3) Symmetrical Rail
35 x 7.5 x 1 m
10 199-DR1
Cat. No. 199-DR1
Click to enlarge - 700SA-32-6 Retainer Clip for Cat. Nos. 700-HN153 and -HN154 Sockets with Bulletin 700-HS Timing Relays¬ 
Secures relay in socket. Order must be for 10 clips or multiples of 10.
10 700-HN160
Sample Retainer Clips
Click to enlarge - 700SA-32-5   
Pre-Printed Identification Tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.  
10 700-N40
Blank Identification Tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N41
  

¬ Bulletin 700-HS Timing Relay, Socket, and Retainer Clip Reference Chart


Relay Type Socket Retainer Clip
700-HS 700-HN153 700-HN160
700-HN154
  

Specifications

  Cat. No. 700-HS… Cat. No. 700-HSF…
Electrical Ratings
Pilot Duty Rating T  NEMA B300
Rated Thermal Current (Ith) 12 A
Rated Insulation Voltage (Ui) 250V IEC,
300V UL/CSA
Contacts Inductive Make Break Hp Make Break Hp
  Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2   Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2  
120V AC 30 A 3 A 1/3 30 A 3 A 1/3
240V AC 15 A 1.5 A 1/2 15 A 1.5 A 1/2
Resistive 30V DC 12 A 12 A 12 A 12 A
Permissible Coil Voltage Variation 85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
80…110% of Nominal Voltage at DC
Power Consumption ±10% AC 24V AC 2 VA
120V AC 3 VA
240V AC
DC 1.3 W
Design Specification/Test Requirements
Dielectric Withstand
Voltage
Pole-to-Pole, same circuit (VRMS) 1000V AC
Pole-to-Pole, different circuits (VRMS) 2000V AC
Contact-to-Coil (VRMS) 2000V AC
Electrical Life Operations 100,000 minimum
Switching Frequency Operations 360/hr
Coil Voltages See product selection
Mechanical
Degree of Protection Open Type (Guarded Terminal Sockets)
Mechanical Life Operations 10 x 106
Switching Frequency Operations 18,000/hr
Timing Duty Cycle Continuous
Repeat Accuracy
(constant voltage and temperature)
±2% (Time Delay: 0.1…2 s)
±1% (Time Delay: >2 s)
Repeat Accuracy
(variable voltage and temperature)
±15%
Fixed Time Setting Accuracy ±2% (Time Delay: 0.1…2 s)
±1% (Time Delay: >2 s)
Scale
Tolerance
High End of Range +5%
Low End of Range –50%
Reset Time ON Delay 100 ms
OFF Delay 40 ms
Environmental
Temperature Operating –28…+65 °C
(–18…+149 °F)
Storage –55…+85 °C
(–67…+185 °F)
Altitude 2000 m (6560 ft)
Construction
Insulating Material Molded High Dielectric Material
Enclosure Impact Resistant Dust Cover
Contact Material Silver Nickel
Terminal Markings on Socket In accordance with EN 50 005
Sockets 8- or 11-Blade
(On = 8, Off = 11)
700-HN153 -HN154
Certifications CSA Certified, File 233833, UL Recognized, File E3125 Guide NLDX 2, cUus Listed when used with 700-HN153 and 700-HN154 sockets (File E3125, Guide NLDX/NLDX7), CE Marked

Standards EN 61812, EN 60947-5-1, CSA 22.2, UL 508
  
¬ See Performance Data.
T NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P.

Trigger Signal Cat. Nos. 700-HT / -HS

Contact closure provides signal to timer. A low energy signal is generated by the 700-HT / -HS timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Timing Diagrams

Click to enlarge - 700HSondelay
ON Delay


Click to enlarge - 700HSoffdelay
OFF Delay

Approximate Dimensions

Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - 700HSaproxdim
Bulletin 700-HS Timing RelayBulletin 700-HSF without knobs)


Click to enlarge - 700HA-72-2
Cat. No. 199-DR1 DIN Mounting Rail Series BCat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes


Cat. No. A B C D Approx.
Shipping Wt.
199-DR1 35
(1-3/8)
27
(1-1/16)
7.5
(19/64)
1.02
(1/64)
1.85 kg
(4.07 lbs.) (10/pkg)
199-DR4 35
(1-3/8)
27
(1-1/16)
15
(19/32)
2.3
(3/32)
3.68 kg
(8 lbs.) (5/pkg)
  

Click to enlarge - 700HB-80-2a
Cat. No. 700-HN153
Wire Size: 2 x 2.5 mm2
Single Wire – Up to #12 AWG
Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG)
(Either Solid or Stranded)
Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)


Click to enlarge - 700HB-80-2b
Cat. No. 700-HN154
Wire Size: 2 x 2.5 mm2
Single Wire – Up to #12 AWG
Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG)
(Either Solid or Stranded)
Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)