Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > General Purpose Electronic Timers and Counters > Bulletin 700-HS Timing Relay
Bulletin 700-HS Timing Relay
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
| Cat. No. 700-HS… | Cat. No. 700-HSF… | |||||||
| Electrical Ratings | ||||||||
| Pilot Duty Rating T | NEMA B300 | |||||||
| Rated Thermal Current (Ith) | 12 A | |||||||
| Rated Insulation Voltage (Ui) | 250V IEC, 300V UL/CSA |
|||||||
| Contacts | Inductive | Make | Break | Hp | Make | Break | Hp | |
|
|
|
|
|
|||||
| 120V AC | 30 A | 3 A | 1/3 | 30 A | 3 A | 1/3 | ||
| 240V AC | 15 A | 1.5 A | 1/2 | 15 A | 1.5 A | 1/2 | ||
| Resistive 30V DC | 12 A | 12 A | — | 12 A | 12 A | — | ||
| Permissible Coil Voltage Variation | 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC |
|||||||
| Power Consumption ±10% | AC | 24V AC | 2 VA | |||||
| 120V AC | 3 VA | |||||||
| 240V AC | — | |||||||
| DC | 1.3 W | |||||||
| Design Specification/Test Requirements | ||||||||
| Dielectric Withstand Voltage |
Pole-to-Pole, same circuit (VRMS) | 1000V AC | ||||||
| Pole-to-Pole, different circuits (VRMS) | 2000V AC | |||||||
| Contact-to-Coil (VRMS) | 2000V AC | |||||||
| Electrical Life Operations | 100,000 minimum | |||||||
| Switching Frequency Operations | 360/hr | |||||||
| Coil Voltages | See product selection | |||||||
| Mechanical | ||||||||
| Degree of Protection | Open Type (Guarded Terminal Sockets) | |||||||
| Mechanical Life Operations | 10 x 106 | |||||||
| Switching Frequency Operations | 18,000/hr | |||||||
| Timing | Duty Cycle | Continuous | ||||||
| Repeat Accuracy (constant voltage and temperature) |
±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s) |
|||||||
| Repeat Accuracy (variable voltage and temperature) |
±15% | |||||||
| Fixed Time Setting Accuracy | — | ±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s) |
||||||
| Scale Tolerance |
High End of Range | +5% | — | |||||
| Low End of Range | 50% | — | ||||||
| Reset Time | ON Delay | 100 ms | ||||||
| OFF Delay | 40 ms | |||||||
| Environmental | ||||||||
| Temperature | Operating | 28…+65 °C (18…+149 °F) |
||||||
| Storage | 55…+85 °C (67…+185 °F) |
|||||||
| Altitude | 2000 m (6560 ft) | |||||||
| Construction | ||||||||
| Insulating Material | Molded High Dielectric Material | |||||||
| Enclosure | Impact Resistant Dust Cover | |||||||
| Contact Material | Silver Nickel | |||||||
| Terminal Markings on Socket | In accordance with EN 50 005 | |||||||
| Sockets | 8- or 11-Blade (On = 8, Off = 11) 700-HN153 -HN154 |
|||||||
| Certifications | CSA Certified, File 233833, UL Recognized, File E3125 Guide NLDX 2, cUus Listed when used with 700-HN153 and 700-HN154 sockets (File E3125, Guide NLDX/NLDX7), CE Marked |
|||||||
| Standards | EN 61812, EN 60947-5-1, CSA 22.2, UL 508 | |||||||
| ¬ See Performance Data. | ||||||||
| T NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. | ||||||||
Trigger Signal Cat. Nos. 700-HT / -HS
Contact closure provides signal to timer. A low energy signal is generated by the 700-HT / -HS timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.
Timing Diagrams
|
|