Specifications

  Cat. No. 700-HT… Cat. No. 700-HTF…
Electrical Ratings
Pilot Duty RatingT  NEMA B300
Rated Thermal Current (Ith) 10 A
Rated Insulation Voltage (Ui) 250V IEC, 300V UL/CSA
Contacts Inductive Make Break HP Make Break HP
  Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2   Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2  
120V AC 30 A 3 A 1/2 N.O. 1/3 N.C 30 A 3 A 1/3
240V AC 15 A 1.5 A 1/2 N.O. 1/3 N.C 15 A 1.5 A 1/2
Resistive 28V DC 10 A 10 A 10 A 10 A
Permissible Coil Voltage Variation 85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
80…110% of Nominal Voltage at DC
Power Consumption ±10% AC 24V AC 2 VA
120V AC 4 VA
240V AC 4 VA
DC 1.3 W
Design Specification/Test Requirements
Dielectric Withstand Voltage Pole-to-Pole, same circuit (VRMS) 1000V AC
Pole-to-Pole, different circuits (VRMS) 2000V AC
Contact-to-Coil (VRMS) 2000V AC
Electrical Life Operations 100,000 minimum
Switching Frequency Operations 1800/hr
Coil Voltages See product selection
Mechanical
Degree of Protection Open Type (Guarded Terminal Sockets)
Mechanical Life Operations 10 x 106
Switching Frequency Operations 18,000/hr
Timing Duty Cycle Continuous
Repeat Accuracy
(constant voltage and temperature)
±2% (Time Delay: 0.1…2 s)
±1% (Time Delay: >2 s)
Repeat Accuracy
(variable voltage and temperature)
±10%
Fixed Time Setting Accuracy ±5% (Time Delay: 0.1…2 s)
±1% (Time Delay: >2 s)
Scale Tolerance High End of Range +5%
Low End of Range -50%
Reset Time ON Delay 100 ms
OFF Delay 40 ms
Environmental
Temperature Operating –28…+65 °C (50 °C max., 240V AC coil)
(–18…+149 °F) (122 °F max., 240V AC coil)
Storage –55…+85 °C
(–67…+185 °F)
Altitude 2000 m (6560 ft)
Construction
Insulating Material Molded High Dielectric Material
Enclosure Impact Resistant Dust Cover
Contact Material Silver Cadmium Oxide
Terminal Markings on Socket In accordance with EN50 005
Sockets 8- or 11-Pin Socket
(On = 8, Off = 11)
700-HN100, -HN125
700-HN101, -HN126
Certifications CSA Certified, File 223833, UL Recognized, File E3125 Guide NLDX 2,UL Listed,whe used with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets, File No. E3125 Guide NLDX, CE Marked
Standards EN 61812-1, EN 60947-1,-5-1, CSA 22.2 No. 14, UL 508
  
¬ See Performance Data.
T NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P.

Trigger Signal Cat. Nos. 700-HT / -HS

Contact closure provides signal to timer. A low energy signal is generated by the 700-HT / -HS timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Timing Diagrams

Click to enlarge - 700HTondelay
ON Delay


Click to enlarge - 700HToffdelay
OFF Delay