Bulletin 700-HX Multifunction Digital Timing Relay

Product Overview


Click to enlarge - TOC-4-7


Bulletin 700-HX


Standards Compliance and Certifications

See Specifications.

Product Selection

Build a Catalog Number


Model Operating Mode Timing Range Socket Type Contact Output No. of Pins Input Voltage Cat. No.
Click to enlarge - TOC-4-7 A mode: Signal On-Delay 1
A-1 mode: Signal On-Delay 2
A-2 mode: Power On-Delay 1
A-3 mode: Power On-Delay 2
B mode: Repeat Cycle 1
B-1 mode: Repeat Cycle 2
D mode: Signal OFF-delay
E mode: One Shot
F mode: Cumulative
Twin Timer
0.000…9.999 s
0.000…99.99 s
0.000…999.9 s
0.000…9999 s
0.000…99 min 59 s
0.000…999.9 min
0.000…9999 min
0.000…99 hr 59 min
0.000…999.9 hr
0.000…9999 hr
700-HN100
700-HN125
SPDT 8 100…240V AC 700-HX86SA17
Cat. No. 700-HX… 24V AC
12…24V DC
700-HX86SU24
  

General Timer Functions

Click to enlarge - 700HX-165-3

Accessories

  Description Pkg. Quantity Cat. No.
Click to enlarge - 700-HN100_GS Screw Terminal Tube Base Socket — Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with Bulletin 700-HX Timing Relays. Order ten or multiples of ten 10 700-HN100
Cat. No. 700-HN100
Click to enlarge - 700SA-32-3 Screw Terminal Tube Base Socket — Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with Bulletin 700-HX Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required. 10 700-HN125
Cat. No. 700-HN125
Click to enlarge - 700SA-32-4 DIN (#3) Symmetrical Rail
35 x 7.5 x 1 m
10 199-DR1
Cat. No. 199-DR1
Click to enlarge - 700-HN108a Specialty Socket
8-pin backwired socket with solder terminals. For use with 700-HX Timing Relays.
10 700-HN108
Cat. No. 700-HN108
Click to enlarge - 700SA-32-6 Retainer Clip for Cat. Nos. 700-HN100 Sockets with all
700-HX Timing Relays

Secures timer in socket.

Note: Not required for installation
10 700-HN131
Sample Retainer Clips
Click to enlarge - 700HR-144-1 Frame Adapter
For flush or door mounting of all Bulletin 700-HR and -HX timers.
1 700-HN130
Cat. No. 700-HN130
Click to enlarge - 700HR-144-3 Protective Cover
Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all Bulletin 700-HRs and -HX timing relays.
1 700-HN132
Cat. No. 700-HN132
  

Timing Relay, Socket, Retainer Clip Reference Chart
Timer Type Socket Cat. No. Retainer Clip Cat. No.
700-HX 700-HN100 700-HN131
700-HN108 Not Required¬ 
700-HN125 Not Required¬ 
  
¬ Design of socket holds the relay securely and does not require retainer clips.

Specifications

Electrical Ratings
Pilot Duty Rating NEMA B300
Rated supply voltage 100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.)
Operating voltage range 85…110% of rated supply voltage
Power consumption 100…240V AC 4.3VA
24V AC/12…24V DC 3.4VA/1.7 W
Inrush Current 100…240V AC 3 A
24V AC/12…24V DC 5 A
Click to enlarge - 700HA-69-1 120V AC 30 A
Make 240V AC 15 A
Click to enlarge - 700HA-69-2 120V AC 3 A
Break 240V AC 1.5 A
Hp at 120V AC 1/4 Hp
Hp at 240V AC 1/3 Hp
Mechanical
Mounting Method Flush mounting, surface mounting, DIN mounting
Display Seven-segment, negative transmissive LCD; Present value (red, 8 mm high characters); Set value (green, 4 mm high characters)
Digits Four digits
Timer Time ranges 0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min 00 s…99 min 59 s, 0.0…999.9 min, 0 hr 00 min…99 hr 59 min, 0.0 hr…999.9 hr, 0 hr…9999 hr
Timer modes Elapsed time (Up), remaining time (Down), selectable
Output modes A, A-1, A-2, A-3, B, B-1, D, E, F, Z, ton or toff
Inputs Input signals Start, reset
Input method No-voltage input via:NPN transistor or switching of contact
Start, reset, gate Minimum input signal width: 1 or 20 ms (selectable)
Power reset Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode)
Control output SPDT contact output: 5 A at 250V AC, resistive load (cosine=1)
Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value)
External Power Supply No
Key Protect Yes
Memory Backup EEP-ROM (overwritten 200 000 times min), which can store data for 20 years min.
Accuracy of Operating Time and Setting Error¬  Power-ON start: +-0.01% +-50 ms max.
* to be rated against set value
Signal start: +- 0.005% +-30 ms max.
* to be rated against set value
Signal start at transistor output model: +- 0.005% +-3 ms max.T 
If the set value is within the sensor waiting time
(250 ms max.)
  
¬ The values are based on the set value.
T The value is applied for a minimum pulse width of 1 ms.

Characteristics¬ 
Insulation Resistance 100 mW min. (at 500V DC)
Dielectric Strength 2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-current-carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Noise Immunity '+-1.5 kV (between power terminals) for 100 to 240 VAC, +-480V for 24VAC/12 to 24VDC, and +-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise)
Static Immunity ±8 kV (malfunction), ±15 kV (destruction)
Vibration Resistance Malfunction 10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min
Shock Resistance Malfunction 98 m/s2 (approx. 10 G) each in three directions
Life Expectancy Mechanical 10 million operations min. (under no load at 18 000 operation/hr)
Electrical 100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level2) 8 kV air discharge (level3)
Immunity RF-interference: EN61000-4-3: 10 V/m
Enclosure Ratings Panel surface:IP66 and NEMA Type 4X (indoors)T 
Weight Approx. 100 g
Certifications CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked
Standards EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508
  
¬ 700-HX User Manual, pub. number 700-UM002_-EN-D, available at Literature Library.
T An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.

Timing Charts

Click to enlarge - 700HX-169-1


Output mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Click to enlarge - 700HX-169-2 Click to enlarge - 700HX-169-3
Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Click to enlarge - 700HX-169-4 Click to enlarge - 700HX-169-5
Output mode A-2: Power ON Delay 1 (Timer resets when power comes ON)
Click to enlarge - 700HX-169-6 Click to enlarge - 700HX-169-7
Output mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)
Click to enlarge - 700HX-169-8 Click to enlarge - 700HX-169-9
  
¬ Gate not included on any mode of this relay.

Output mode B: Repeat Cycle (Timer resets when power comes ON.)
Click to enlarge - 700HX-170-1 Click to enlarge - 700HX-170-2
Click to enlarge - 700HX-170-3 Click to enlarge - 700HX-170-4
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Click to enlarge - 700HX-170-5 Click to enlarge - 700HX-170-6
Click to enlarge - 700HX-170-7 Click to enlarge - 700HX-170-8
  
¬ Gate not included on any mode of this relay.

Output mode D: Signal OFF-delay (Timer resets when power comes ON.)
Click to enlarge - 700HX-171-1 Click to enlarge - 700HX-171-2
Output mode E: Interval (Timer resets when power comes ON.)
Click to enlarge - 700HX-171-3 Click to enlarge - 700HX-171-4
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Click to enlarge - 700HX-171-5 Click to enlarge - 700HX-171-6
  
¬ Gate not included on any mode of this relay.

Z Mode

Output quantity can be adjusted by changing the cycle time set in the adjustment level to 1 and by changing the ON duty (%) set value. The set value shows the ON duty (%) and can be set to a value between 0 and 100 (%). When the cycle time is 0, the output will always be OFF. When the cycle time is not 0 and when ON duty has been set to 0 (%), the output will always be OFF. When ON duty has been set to 100 (%), the output will always be ON.

Z mode: ON/OFF-duty Adjustable Repeat Cycle
Click to enlarge - 700HX-172-1 Click to enlarge - 700HX-172-2
Output mode T OFF: Twin Timer OFF start
Click to enlarge - 700HX-172-3 Click to enlarge - 700HX-172-4
Output mode T ON: Twin Timer ON start
Click to enlarge - 700HX-172-5 Click to enlarge - 700HX-172-6
  
¬ Gate not included on any mode of this Relay.

Approximate Dimensions

Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - 700HX-173-1
Cat. No. 700-HX…Panel Cutout


Click to enlarge - 700HA-72-2
Cat. No. 199-DR1 DIN Mounting Rail Series BCat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes


Terminal Arrangement

Click to enlarge - 700HX-173-3
Cat. No. 700-HX…