Electrical Ratings
Pilot Duty Rating NEMA B300
Rated supply voltage 100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.)
Operating voltage range 85…110% of rated supply voltage
Power consumption 100…240V AC 4.3VA
24V AC/12…24V DC 3.4VA/1.7 W
Inrush Current 100…240V AC 3 A
24V AC/12…24V DC 5 A
Click to enlarge - 700HA-69-1 120V AC 30 A
Make 240V AC 15 A
Click to enlarge - 700HA-69-2 120V AC 3 A
Break 240V AC 1.5 A
Hp at 120V AC 1/4 Hp
Hp at 240V AC 1/3 Hp
Mechanical
Mounting Method Flush mounting, surface mounting, DIN mounting
Display Seven-segment, negative transmissive LCD; Present value (red, 8 mm high characters); Set value (green, 4 mm high characters)
Digits Four digits
Timer Time ranges 0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min 00 s…99 min 59 s, 0.0…999.9 min, 0 hr 00 min…99 hr 59 min, 0.0 hr…999.9 hr, 0 hr…9999 hr
Timer modes Elapsed time (Up), remaining time (Down), selectable
Output modes A, A-1, A-2, A-3, B, B-1, D, E, F, Z, ton or toff
Inputs Input signals Start, reset
Input method No-voltage input via:NPN transistor or switching of contact
Start, reset, gate Minimum input signal width: 1 or 20 ms (selectable)
Power reset Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode)
Control output SPDT contact output: 5 A at 250V AC, resistive load (cosine=1)
Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value)
External Power Supply No
Key Protect Yes
Memory Backup EEP-ROM (overwritten 200 000 times min), which can store data for 20 years min.
Accuracy of Operating Time and Setting Error¬  Power-ON start: +-0.01% +-50 ms max.
* to be rated against set value
Signal start: +- 0.005% +-30 ms max.
* to be rated against set value
Signal start at transistor output model: +- 0.005% +-3 ms max.T 
If the set value is within the sensor waiting time
(250 ms max.)
  
¬ The values are based on the set value.
T The value is applied for a minimum pulse width of 1 ms.

Characteristics¬ 
Insulation Resistance 100 mW min. (at 500V DC)
Dielectric Strength 2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-current-carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Noise Immunity '+-1.5 kV (between power terminals) for 100 to 240 VAC, +-480V for 24VAC/12 to 24VDC, and +-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise)
Static Immunity ±8 kV (malfunction), ±15 kV (destruction)
Vibration Resistance Malfunction 10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min
Shock Resistance Malfunction 98 m/s2 (approx. 10 G) each in three directions
Life Expectancy Mechanical 10 million operations min. (under no load at 18 000 operation/hr)
Electrical 100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level2) 8 kV air discharge (level3)
Immunity RF-interference: EN61000-4-3: 10 V/m
Enclosure Ratings Panel surface:IP66 and NEMA Type 4X (indoors)T 
Weight Approx. 100 g
Certifications CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked
Standards EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508
  
¬ 700-HX User Manual, pub. number 700-UM002_-EN-D, available at Literature Library.
T An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.

Timing Charts

Click to enlarge - 700HX-169-1


Output mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Click to enlarge - 700HX-169-2 Click to enlarge - 700HX-169-3
Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Click to enlarge - 700HX-169-4 Click to enlarge - 700HX-169-5
Output mode A-2: Power ON Delay 1 (Timer resets when power comes ON)
Click to enlarge - 700HX-169-6 Click to enlarge - 700HX-169-7
Output mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)
Click to enlarge - 700HX-169-8 Click to enlarge - 700HX-169-9
  
¬ Gate not included on any mode of this relay.

Output mode B: Repeat Cycle (Timer resets when power comes ON.)
Click to enlarge - 700HX-170-1 Click to enlarge - 700HX-170-2
Click to enlarge - 700HX-170-3 Click to enlarge - 700HX-170-4
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Click to enlarge - 700HX-170-5 Click to enlarge - 700HX-170-6
Click to enlarge - 700HX-170-7 Click to enlarge - 700HX-170-8
  
¬ Gate not included on any mode of this relay.

Output mode D: Signal OFF-delay (Timer resets when power comes ON.)
Click to enlarge - 700HX-171-1 Click to enlarge - 700HX-171-2
Output mode E: Interval (Timer resets when power comes ON.)
Click to enlarge - 700HX-171-3 Click to enlarge - 700HX-171-4
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Click to enlarge - 700HX-171-5 Click to enlarge - 700HX-171-6
  
¬ Gate not included on any mode of this relay.

Z Mode

Output quantity can be adjusted by changing the cycle time set in the adjustment level to 1 and by changing the ON duty (%) set value. The set value shows the ON duty (%) and can be set to a value between 0 and 100 (%). When the cycle time is 0, the output will always be OFF. When the cycle time is not 0 and when ON duty has been set to 0 (%), the output will always be OFF. When ON duty has been set to 100 (%), the output will always be ON.

Z mode: ON/OFF-duty Adjustable Repeat Cycle
Click to enlarge - 700HX-172-1 Click to enlarge - 700HX-172-2
Output mode T OFF: Twin Timer OFF start
Click to enlarge - 700HX-172-3 Click to enlarge - 700HX-172-4
Output mode T ON: Twin Timer ON start
Click to enlarge - 700HX-172-5 Click to enlarge - 700HX-172-6
  
¬ Gate not included on any mode of this Relay.