Bulletin 700-HTA Alternating Relay

Product Overview


Click to enlarge - 700-HTA1A1_L  

Bulletin 700-HTA Alternating Relay


Standards Compliance and Certifications

See Specifications.

Product Selection

Build a Catalog Number


Alternating Relays with Pin-Style Terminations

Bulletin 700-HTA Alternating Relay Wiring Diagrams
U.S./Canada International
SPDT Form C Contact SPDT Click to enlarge - 700-HTA1_wirediag Click to enlarge - 700-HTA1_wirediag_international
DPDT 2 Form C Contact DPDT Click to enlarge - 700-HTA2_wirediag Click to enlarge - 700-HTA2_wirediag_international
Cross-Wired DPDT 2 Form C Contacts Cross-Wired Click to enlarge - 700-HTA3_wirediag Click to enlarge - 700-HTA3_wirediag_international
  

700 HTA    2    A12    7
      a    b    c    d

a
Relay Type
Code Description
HTA Tube Base Alternating Relay

b
Model Type
Code Model
1 SPDT
2 DPDT
3 Cross-Wired

c
Coil Voltage
Code Description
A12 12V AC 50/60 Hz
A24 24V AC 50/60 Hz
A1 120V AC 50/60 Hz
A2 240V AC 50/60 Hz

d
Option
Code Description
blank Without switch
7 With switch

Accessories

  Description Pkg. Qty. Cat. No.
Click to enlarge - 700-HN100_GS Screw Terminal Tube Base Socket — Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with Bulletin 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten. 10 700-HN100
Cat. No. 700-HN100
Click to enlarge - 700SA-32-3 Screw Terminal Tube Base Socket — Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with Bulletin 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten. No retainer clip required. 10 700-HN125
Cat. No. 700-HN125
Click to enlarge - 700HA-66-3 Screw Terminal Tube Base Sockets — Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays. 10 700-HN101
Cat. No. 700-HN101
Click to enlarge - 700HT-158-1 Screw Terminal Tube Base Sockets — Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required. 10 700-HN126
Cat. No. 700-HN126
Click to enlarge - 700SA-32-4 DIN (#3) symmetrical rail
35 x 7.5 x 1 m
10 199-DR1
Cat. No. 199-DR1
Click to enlarge - 700SA-32-6 Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with Bullletin 700-HT Timing Relays, and Bulletin 700-HTA Alternating Relays¬ 
Secures relay in socket. Order must be for 10 clips or multiples of 10.
10 700-HN110
Sample Retainer Clips
Click to enlarge - 700SA-32-5 Pre-Printed Identification Tags — contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N40
Blank Identification Tags — contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays. 10 700-N41
  
¬ Bulletin 700-HT Timing Relay, Socket, and Retainer Clip Reference Chart.

Relay Type Socket Cat. No. Retainer Clip Cat. No.
700-HTA1
700-HTA3
700-HN100 700-HN110
700-HN125 Not RequiredT 
700-HTA2 700-HN101 700-HN110
700-HN126 Not RequiredT 
  
T Design of these sockets holds the relays securely and does not require retainer clips.

Specifications

  Cat. No. 700-HTA…
Electrical Ratings
Pilot Duty RatingT  NEMA B300 AC 15
Rated Thermal Current (Ith) 10 A
Rated Insulation Voltage (Ui) 250V IEC, 300V UL/CSA
Contacts Inductive Make Break HP
  Click to enlarge - 700HA-69-1 Click to enlarge - 700HA-69-2  
120V AC 30 A 3 A 1/3
240V AC 15 A 1.5 A 1/2
Resistive 30V DC 10 A 10 A
Permissible Coil Voltage Variation 85…110% of Nominal Voltage at 50 Hz
85…110% of Nominal Voltage at 60 Hz
Power Consumption ±10% AC 24V AC 2 VA
120V AC 4 VA
240V AC 4 VA
Design Specification/Test Requirements
Dielectric Withstand Voltage Pole-to-Pole, same circuit (VRMS) 1000V AC
Pole-to-Pole, different circuits (VRMS) 2000V AC
Contact-to-Coil (VRMS) 2000V AC
Electrical Life Operations 100,000 minimum
Switching Frequency Operations 1800/hr
Coil Voltages See product selection
Mechanical
Degree of Protection Open Type (Guarded Terminal Sockets)
Mechanical Life Operations 10 x 106
Switching Frequency Operations 18,000/hr
Start-up Time (max. time from power application until unit is timing) 0.05 sec
Max. Function Time (max. time power can drop out and unit continues timing) 0.01 sec
Min. Cycle Time 100 ms on release of the control switch
Environmental
Temperature Operating –28…+65 °C (50 °C max., 240V AC coil)
(–18…+149 °F) (122 °F max., 240V AC coil)
Storage –55…+85 °C
(–67…+185 °F)
Altitude 2000 m (6560 ft)
Construction
Insulating Material Molded High Dielectric Material
Enclosure Impact Resistant Dust Cover
Contact Material Silver Tin Oxide
Terminal Markings on Socket In accordance with EN50 005
Sockets 8- or 11-Pin Socket
700-HN100, -HN125
700-HN101, -HN126
Certifications CSA Certified, File 223833, UL Recognized (File E3125 Guide NLDX2/NLDX8), cULus Listed with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets (File No. E3125 Guide NLDX/NLDX7), CE-Marked (per EU Low Voltage Directive)
Standards EN 61812-1, EN/IEC 60947-1, -5-1, CSA 22.2 No. 14, UL 508
  
¬ Performance Data — See Performance Data, this catalog.
T NEMA Rating Chart is in publication 700-SG003_-EN-P.

Trigger Signal Cat. Nos. 700-HTA

Contact closure provides signal to timer. A low energy signal is generated by the 700-HTA alternating relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Example: Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Load Diagrams

Click to enlarge - 700-hTA_LoadDiag#1


Click to enlarge - 700-hTA_LoadDiag#2

Approximate Dimensions

Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

Click to enlarge - 700HTAapproxdim


Click to enlarge - 700HA-73-1
Cat. No. 700-HN100
Panel Mounting
Double Wire — 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG)(Either Solid or Stranded)Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)


Click to enlarge - 700HA-73-2
Cat. No. 700-HN125
Wire Size: 2 x 2.5 mm2Single Wire — Up to #12 AWGDouble Wire — 2 x 2.5 mm2 (#2 – 14 AWG… #2 – 20 AWG)(Either Solid or Stranded)Strip Length: 9 mm (3/8 in) — Torque: 0.8 N•m (7 lb•in)


Click to enlarge - 700HA-73-3
Cat. No. 700-HN101
Panel Mounting
Double Wire – 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG)(Either Solid or Stranded)Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)


Click to enlarge - 700HA-73-4
Cat. No. 700-HN126
Wire Size: 2 x 2.5 mm2Single Wire — Up to 12 AWGDouble Wire — 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG)(Either Solid or Stranded)Strip Length: 9 mm (3/8 in) — Torque: 0.8 N•m (7 lb•in)