Bulletin 700-P, 700-PH, and 700-PK Heavy-Duty Relay
| Product Overview |
|
Bulletin 700-P and 700-PK Direct Drive™ Convertible Contact Cartridge Relays
- NEMA and IEC ratings
- 600V maximum AC/DC
- Accessories for field installation: Adder Decks, time delay, latching, surge suppressors, mounting strip
- Contact Ratings: (10 A) 700-CP1, (20 A) 700-CPM, (35 A) 700-CPH, (Low Power) 700-CPR
- For machine tool and other heavy-duty applications
- Can accommodate ring tongue terminals
- Integral DIN Rail adapter on AC relays
- Finger-safe protection standard
Description
The Bulletin 700-P family of relays has four types of contact cartridges to meet your specific switching requirements. Different cartridges can be combined into one relay to yield a custom-tailored application solution. Time delay, latching attachments, overlapping, and logic reed contacts are available.
Bulletin 700-P relays use standard (10 A) contact cartridges with a double-break and bifurcated design. Bifurcation provides excellent contact reliability and low-contact bounce, while the double-break contact design reduces the possibility of contacts welding and enhances the relays ability to break DC circuits. These relays are supplied with a max. of 12 contacts (max. 8 N.C.).
Bulletin 700-PK master control relays contain (20 A) master contact cartridges with large single-contact pads on each side of the spanner for twice the current rating to control heavy loads and for master control of a system. The Bulletin 700-PK relay also has the same doublebreak design as the 700-P relay. These relays are supplied with a max. of 12 contacts (max. 8 N.C.). Time delay and latching attachments are available.
Bulletin 700-P and -PK relays combine the advantages of convertible contacts with Direct Drive, a construction designed to maintain non-overlap operation between N.O. and N.C. contacts (within published ratings).
Bulletin 700-PH relays contain (35 A) tandem contact cartridges. A jumper kit (Cat No. 700-CPH) allows two (20 A) master contact cartrridges to be connected in parallel. A maximum of six poles are supplied, up to four of which can be normally closed. Time delay and latch attachments are available.
Standards
- UL 508
- CSA C22.2, No. 14
- EN/IEC 60947-1, -5-1
Certifications
- cULus Listed (File No. E14840, Guide NKCR/NKCR7)
- ABS Certified
Product Selection
| Build a Catalog Number |
Electrically Held Relays
Bulletin 700-P Standard Contact Cartridge¬ T
AC-Operated Relays
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-P200Ä becomes Cat. No. 700-P200A48. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1z | B11ª | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1z | B11ª | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| z Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| ª Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
DC-Operated Relays
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-P200Ä becomes Cat. No. 700DC-P200Z48. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
| ¬ Normally closed contacts: The normally open contacts can easily be changed to normally closed in the field. Relays can be supplied with N.C. contacts. | ||||||||||||
| T Overlap contacts: To order a relay containing one pair: Use Cat. No. 700-PZ110. To order a relay containing two pairs: Use Cat. No. 700-PZ2220. N.O. contact closes before N.C. contact opens. AC Ratings: NEMA A600, DC Ratings: P161. | ||||||||||||
| Location of contacts in 2-pole relays. | ||||||||||||
| § Location of contacts in 6-pole relays: 4-pole relay plus the two contacts indicated. | ||||||||||||
| § Location of contacts in 10-pole relays: 8-pole relay plus the two contacts indicated. | ||||||||||||
| Ø For Type 4/4X Enclosure replace 1 with 4, for Type 7 & 9 Enclosure replace 1 with 7 (Example, 700-P401 becomes 700-P404). | ||||||||||||
Electrically Held Relays
Bulletin 700-PK Master Contact Cartridges¬ T
AC-Operated Relays
| Contacts | Contact Arrangement and Markings |
Type 1Ø General Purpose |
||
| N.O. | N.C. | Cat. No. | ||
|
2 | — |
|
700-PK201Ä |
| 4 | — | 700-PK401Ä | ||
| 6 | — |
|
700-PK601Ä | |
| 8 | — | 700-PK801Ä | ||
| 10 | — |
|
700-PK1001Ä | |
| 12 | — | 700-PK1201Ä | ||
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No.700-PK200Ä becomes Cat. No.700-PK200A48 for 48V 60 Hz. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1z | B11ª | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1z | B11ª | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| z Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| ª Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
DC-Operated Relays
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PK200Ä becomes Cat. No. 700DC-PK200Z12 for 12V DC. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
| ¬ Normally closed contacts: The normally open contacts can easily be changed to normally closed in the field. Relays can be supplied with N.C. contacts. | ||||||||||||
| T Overlap contacts: To order a relay containing one pair: Use Cat. No. 700-PZ110. To order a relay containing two pairs: Use Cat. No. 700-PZ2220. N.O. contact closes before N.C. contact opens. AC Ratings: NEMA A600, DC Ratings: P161. | ||||||||||||
| Location of contacts in 2-pole relays. | ||||||||||||
| § Location of contacts in 6-pole relays: 4-pole relay plus the two contacts indicated. | ||||||||||||
| § Location of contacts in 10-pole relays: 8-pole relay plus two contacts indicated | ||||||||||||
| Ø For Type 4/4X Enclosure replace 1 with 4, for Type 7 & 9 Enclosure replace 1 with 7 (Example, 700-PK401Ä becomes 700-PK404). | ||||||||||||
Electrically Held Relays — Typical Wiring Diagrams
|
|
Electrically Held Relays
Bulletin 700-PH 35A Tandem Contact Cartridges¬
AC-Operated Relays
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PH100Ä becomes Cat. No. 700-PH100A48. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1z | B11ª | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1z | B11ª | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| z Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| ª Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
DC-Operated Relays
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PH200Ä becomes Cat. No. 700DC-PH200Z12. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
| ¬ Normally closed contacts: The normally open contacts can easily be changed to normally closed in the field. Relays can be supplied with N.C. contacts. | ||||||||||||
| T Location of contacts in 1-pole relays. | ||||||||||||
| Location of contacts in 3-pole relays: 2-pole relay plus the contact indicated. | ||||||||||||
| § Location of contacts in 5-pole relays: 4-pole relay plus the contact indicated. | ||||||||||||
|
Time Delay Relays — Open Type With Pneumatic Time-Delay Attachment
- Factory-Assembled Bulletin 700-PT and PKT Timing Relays
- Timing Range — 0.1…60 s
- 0, 2, or 4 instantaneous contacts
- Two timed contacts — both ON Delay or both OFF Delay
- Convertible from ON Delay to OFF Delay and vice versa
- Standard contact cartridges rated NEMA A600 (AC) and P600 (DC)
- Master contact cartridges rated 2X NEMA A600 (AC) and 2X P600 (DC)
- Timing Range — 0.1…60 s
Bulletin 700-P Standard Contact Cartridge¬ T
Bulletin 700-PK Master Contact Cartridges¬
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PKT200Ä becomes Cat. No. 700-PKT200A48 for 48V 60 Hz. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1z | B11ª | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1z | B11ª | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| z Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| ª Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PKT200Ä becomes Cat. No. 700DC-PKT200Z12 for 12V DC. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
| ¬ Normally closed contacts: The normally open contacts can easily be changed to normally closed in the field. Relays can be supplied with N.C. contacts. | ||||||||||||
| T Overlap contacts: N.O. contact closes before N.C. contact opens. To order a relay containing one pair: Use Cat. No. 700-PTZ110. To order a relay containing two pairs: Use Cat. No. 700-PTZ2220. AC Ratings: NEMA A600, DC Ratings: P161. | ||||||||||||
| Location of contacts in 2-pole relays. | ||||||||||||
| § Timer has 1 N.O. and 1 N.C. convertible cartridge in addition to the instantaneous cartridges on the relay. Timer is supplied as On-Delay. Convertible to Off-Delay in the field. | ||||||||||||
| Ø The timer has 1 N.O. and 1 N.C convertible master cartridge in addition to the instantaneous master cartridges on the relay. Timer is supplied as On-Delay. It is convertible to Off-Delay in the field. | ||||||||||||
|
Mechanical Latching Relays
- Factory-Assembled Bulletin 700-PL Latching Relays
- Converts all poles to latching
- AC latch coil — max. six poles latching
- DC latch coil — max. five poles latching
- Latching relays have two coils — latch coil is the relay coil, reset coil is on the latch attachment
- Latch/reset coils can have two AC coils, two DC coils, or one AC and one DC coil (e.g., latch with AC power, unlatch with DC battery)
Bulletin 700-P Standard Contact Cartridge¬ T
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PL200Ä becomes Cat. No. 700-PL200A48. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
Relays with latch attachments: if the latch attachment coil is to be a different voltage other than the relay coil, add a second coil code suffix. Example: Cat. No. 700-PL400A1A24. Only one suffix is required if both coils are the same voltage.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1z | B11ª | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1z | B11ª | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| z Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| ª Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PL200Ä becomes Cat. No. 700DC-PL200Z12. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
| ATTENTION An open or failed unlatch control circuit will fail to unlatch the relay. For this reason, a mechanical latch unit should not be used where protection is needed against automatic restart after a power failure or where reliability to a control function is critical to safety. | ||||||||||||
| ¬ Normally closed contacts: The normally open contacts can easily be changed to normally closed in the field. Relays can be supplied with N.C. contacts. | ||||||||||||
| T Overlap contacts: To order a relay containing one pair: Use Cat. No. 700-PTZ110. To order a relay containing two pairs: Use Cat. No. 700-PTZ2220. N.O. contact closes before N.C. contact opens. AC Ratings: NEMA A600, DC Ratings: P161. | ||||||||||||
| Location of contacts in 2-pole relays. | ||||||||||||
| § Location of contacts in 4-pole relays: 2-pole relay plus the 2 contacts indicated. | ||||||||||||
Accessories
| International Symbol for Mechanically Linked Contacts |
|
Adder Decks
Contact Cartridges (Convertible from N.O. to N.C. and N.C. to N.O.)
Bulletin 700-PS and -PSR Solid-State Timers¬
Remote Potentiometers for Cat. No. 700-PSR…
| Timing Range [s] | Resistance [mW] | Cat. No. |
| 0.1…2 | 0.75 | 700-N35 |
| 0.4…8 | 0.75 | 700-N35 |
| 1.5…30 | 2.0 | 700-N36 |
| 6…120 | 3.5 | 700-N37 |
Pneumatic Time-Delay Unit 1 N.O. and 1 N.C. Convertible Contact Cartridge¬
Mechanical Latch Units
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PLLÄ becomes Cat. No. 700-PLLA1. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| Hz | 24 | 48 | 110 | 110-115 | 115-120 | 120 | 127 | 200-208 | 220-230 | 230-240 | 277 | 347 | 380 | 415 | 440-480 | 460-480 | 500 | 575-600 |
| 50 | B24 | B48 | A1¬ | B11T | — | — | B27 | — | B22 | B2 | — | — | B3 | B41 | B44 | — | B50 | — |
| 60 | A24 | A48 | — | — | A1¬ | B11T | — | A20 | A22 | A2 | A27 | A35 | — | — | — | A4 | — | A6 |
| ¬ Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. | ||||||||||||||||||
| T Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz. | ||||||||||||||||||
ÄDC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PLLÄ becomes Cat. No. 700DC-PLLZ12. For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| 6 | 12 | 18 | 24 | 32 | 48 | 64 | 72 | 90 | 115-125 | 230-250 | 500-550 | 575-600 |
| Z06 | Z12 | Z18 | Z24 | Z32 | Z48 | Z64 | Z72 | Z90 | Z1 | Z2 | Z5 | Z6 |
IP 2x Finger-Safe Cover Accessories
Specifications
| Type | 700-P, PL, PT | 700-PK, PKL, PKT | 700-PH | |||||||||||||||||
| Electrical | ||||||||||||||||||||
| Contact Rating Continuous | 10 A @ 600V AC 5 A @ 600V DC |
20 A @ 600V AC 10 A @ 600V DC |
35 A @ 600V AC 20 A @ 600V DC |
|||||||||||||||||
| Ratings Make/Break |
AC | NEMA A600 | 2 x NEMA A600 | 2 x NEMA A600 | ||||||||||||||||
| DC | NEMA P600 | 2 x NEMA P600 | 2 x NEMA P600 | |||||||||||||||||
| Additional Contact Ratings for AC single-phase loads | — | 3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 Hp @ 120V AC - N.O./N.C. 20 A Resistive Heating to 600V AC 20 A Tungsten Lighting Load to 480V AC |
5 Hp @ 240V AC - N.O. 3 Hp @ 240V AC - N.O./N.C. 2 Hp @ 120V AC - N.O./N.C. 35 A General Use At 0.75 PF to 600V AC 35 A Tungsten Lighting Load to 480V AC |
|||||||||||||||||
| DC Current Ratings Make/Break |
Cartridge Cat. No. 700-CP1 | Cartridge Cat. No. 700-CPM | Cartridge Cat. No. 700-CPH | |||||||||||||||||
| DC Switching | Contacts in Series | Volts DC | ||||||||||||||||||
| 24 | 64 | 125 | 250 | 500 | 600 | 24 | 64 | 125 | 250 | 500 | 600 | 24 | 64 | 125 | 250 | 500 | 600 | |||
| 480W | 480W | 275W | 138W | 135W | 120W | |||||||||||||||
| 1 | 5 A | 2.2 A | 1.1 A | .55 A | .24 A | .2 A | 10 A | 5 A | 2.2 A | .55 A | .24 A | .2 A | 10 A | 5 A | 2.2 A | .55 A | .24 A | .2 A | ||
| 2 | 10 A | 10 A | 5 A | 2 A | .7 A | .5 A | 20 A | 10 A | 5 A | 2 A | .7 A | .5 A | 20 A | 10 A | 5 A | 2 A | .7 A | .5 A | ||
| 3 | — | — | 7 A | 3 A | 1.5 A | 1.0 A | — | 15 A | 7 A | 3 A | 1.5 A | 1.0 A | — | 15 A | 7 A | 3 A | 1.5 A | 1.0 A | ||
| 4 | — | — | 10 A | 5 A | 2.5 A | 1.5 A | — | 20 A | 10 A | 5 A | 2.5 A | 1.5 A | — | 20 A | 10 A | 5 A | 2.5 A | 1.5 A | ||
| Coil Voltage Range | AC | 85…110% | 85…110% | 85…110% | ||||||||||||||||
| DC | 80…110% | 80…110% | 80…110% | |||||||||||||||||
| Battery Charging | 85…115% | 85…115% | 85…115% | |||||||||||||||||
| Coil Consumption P-PH-PK |
50 Hz | 60 Hz | 50 Hz | 60 Hz | 50 Hz | 60 Hz | ||||||||||||||
| A C |
Inrush | 132VAT | 138VAT | 132VAT | 138VAT | 132VAT | 138VAT | |||||||||||||
| Sealed | 19.3VAT | 19VAT | 19.3 VAT | 19VAT | 19.3VAT | 19VAT | ||||||||||||||
| D C |
Inrush | 12.7VAT | 12.7VAT | 12.7VAT | ||||||||||||||||
| Sealed | 12.7VAT | 12.7VAT | 12.7VAT | |||||||||||||||||
| PLL - PKLL AC Latch Unit |
Inrush | 15VAT | 15.6VAT | 5VAT | 15.6VAT | 15VAT | 15.6VAT | |||||||||||||
| Sealed | 5.4VAT | 5.5VAT | 5.4VAT | 5.5VAT | 5.4VAT | 5.5VAT | ||||||||||||||
| PLL - PKLL DC Latch Unit |
Unlatch | 35VAT | 35VAT | — | ||||||||||||||||
| Intermittent | 35 WT | 35 WT | — | |||||||||||||||||
| Reset Time | PT PKT | 75 ms | 75 ms | — | ||||||||||||||||
| Minimum Pulse | PLLPKLL | 75 ms | 75 ms | — | ||||||||||||||||
| Mechanical | ||||||||||||||||||||
| Operating Time | Pickup | AC 10…20 ms DC 30…50 ms |
AC 10…20 ms DC 30…50 ms |
AC 10…20 ms DC 30…50 ms |
||||||||||||||||
| Dropout | AC 10…20 ms DC 20…33 ms |
AC 10…20 ms DC 20…33 ms |
AC 10…20 ms DC 20…33 ms |
|||||||||||||||||
| Mechanical Life | 10 million operations | |||||||||||||||||||
| Construction | ||||||||||||||||||||
| Contact Arrangement | Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum) | Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum) | Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum) | |||||||||||||||||
| Contact Material | Nickel Silver | Silver Cadmium Oxide | Silver Cadmium Oxide | |||||||||||||||||
| Mounting | Panel or Strip Mount Horizontal Mounting Recommended |
Panel or Strip Mount Horizontal Mounting Recommended |
Panel or Strip Mount Horizontal Mounting Recommended |
|||||||||||||||||
| Environmental | ||||||||||||||||||||
| Temperature | Operating¬ | 20…+65 °C (4…149 °F) | 20…+65 °C (4…149 °F) | 20…+65 °C (4…149 °F) | ||||||||||||||||
| Storage | 40…+65 °C (40…149 °F) | 40…+65 °C (40…149 °F) | 40…+65 °C (40…149 °F) | |||||||||||||||||
| Certifications | CSA Certified, CSA File #LR1234, UL Listed, UL File #E14840, Guide NKCR, CE Certified, ABS | |||||||||||||||||||
| Standards | UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1 | |||||||||||||||||||
| Wire Terminations | ||||||||||||||||||||
| Wire size per UL/CSA | #18 AWG…(2) #12 AWG | |||||||||||||||||||
| Tightening Torque | 8…12 lb-in. (0.9…1.4 Nm) | |||||||||||||||||||
| ¬ Temperature inside the panel. | ||||||||||||||||||||
| T Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||||||||||||||||||
Operating Coils
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-P, -PH and -PK Relays
|
|
|
|
|
|
|
|
|