Bulletin 700S-P and 700S-PK Heavy-Duty Safety Control Relay
| Product Overview |
|
Bulletin 700S-P and 700S-PK — Heavy-Duty Safety Control Relays
Features
- Mechanically linked contacts meet IEC 947-5-1-L
- 2…12 poles all mechanically linked
- Red cover for easy identification of safety circuits
- Tamper resistant cover helps prevent changes which could jeopardize safety
- IEC mechanically linked contacts symbol displayed on front
- Visual indication of contact state
- Ideal for use in safety circuits
Certifications
- cULus Listed (File No. E14840, Guide NKCR/NKCR7)
CE Certified
ABS Certified
Standards Compliance
- UL 508
- CSA C22.2 No. 14
Product Selection
| Build a Catalog Number |
Bulletin 700S-P (10 A) Safety Control Relays — AC and DC Coil Voltages
ÄAC Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No.
Example: Cat. No. 700S-P310 becomes Cat. No. 700S-P310A1 for a 120V AC coil.
| [V] | 24 | 115-120 | 230-240 | 460-480 |
| 60 Hz | A24 | A1 | A2 | A4 |
| ⋆ For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor. | ||||
IEC 947-5-1 Annex L has 2 requirements for a relay to meet for mechanically linked contacts:
1.) If a N.O. contact welds, all the N.C. contacts will remain open and meet a 2500V impulse test.
2.) If a N.C. contact welds, all the N.O. contacts will remain open and meet a 2500V impulse test.
Bul. Nos. 700S-P and 700S-DCP relays meet these requirements including the 2500V impulse test.
The relays shown on this page are shipped from the factory with the Bul. 700-CPS safety cartridge installed and cannot be converted to N.O. or N.C. in the Field.
Bulletin 700S-PK (20 A) Safety Control Relays
| Contacts | Coil Voltage | Cat. No. | |
| N.O. | N.C. | ||
| 7 | 1 | 110V AC | 700S-PK710A1 |
| 6 | 2 | 110V AC | 700S-PK620A1 |
| 5 | 3 | 110V AC | 700S-PK530A1 |
| 4 | 4 | 110V AC | 700S-PK440A1 |
| 3 | 5 | 110V AC | 700S-PK350A1 |
| 10 | 2 | 110V AC | 700S-PK1020A1 |
| 3 | 1 | 110V AC | 700S-PK310A1 |
| 7 | 1 | 24V DC | 700S-DCPK710Z24 |
| 6 | 2 | 24V DC | 700S-DCPK620Z24 |
| 5 | 3 | 24V DC | 700S-DCPK530Z24 |
| 4 | 4 | 24V DC | 700S-DCPK440Z24 |
| 3 | 5 | 24V DC | 700S-DCPK350Z24 |
| 10 | 2 | 24V DC | 700S-DCPK1020Z24 |
| 3 | 1 | 24V DC | 700S-DCPK310Z24 |
Specifications
| Type | 700S-P | ||||||
| Electrical | |||||||
| Contact Rating Continuous | 10 A @ 600V AC 5 A @ 600V DC |
||||||
| Ratings Make/ Break |
AC | NEMA A600 | |||||
| DC | NEMA P600 | ||||||
| Minimum Contact Switching Ratings | 10V, 50 mA | ||||||
| DC Switching | Contacts in Series |
Volts DC | |||||
| 24V | 64V | 125V | 250V | 500V | 600V | ||
| 1 | 5 A | 2.2 A | 1.1 A | 0.55 A | 0.24 A | 0.2 A | |
| 2 | 10 A | 10 A | 5 A | 2 A | 0.7 A | 0.5 A | |
| 3 | — | — | 7 A | 3 A | 1.5 A | 1.0 A | |
| 4 | — | — | 10 A | 5 A | 2.5 A | 1.5 A | |
| Contact Electrical Life—Resistive Loads | 1.5 million operations at 10A break at 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC |
||||||
| Coil Voltage Range⋆ | AC | 85…110% | |||||
| DC | 80…110% | ||||||
| Battery Charging |
85…115% | ||||||
| Coil Consumption | 50 Hz | 60 Hz | |||||
| AC | Inrush | 132 VA | 138 VA | ||||
| Sealed | 19.3 VA | 19 VA | |||||
| DC | Inrush | 12.7 W | |||||
| Sealed | 12.7 W | ||||||
| Mechanical | |||||||
| Mechanically Linked Contacts | All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles | ||||||
| Operating Time | Pickup | AC 10…20 ms DC 30…50 ms |
|||||
| Dropout | AC 10…20 ms DC 20…33 ms |
||||||
| Mechanical Life | 10 million operations | ||||||
| Construction | |||||||
| Contact Arrangement | 2 to 12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum) |
||||||
| Contact Material/Design | Silver Nickel/Bifurcated | ||||||
| Mounting | Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended | ||||||
| Environmental | |||||||
| Operating Temperature§ | -20…+65 °C (-4…+149 °F) | ||||||
| Storage Temperature | -40…+65 °C (-40…+149 °F) | ||||||
| Wire Terminations | |||||||
| Wire size per UL/CSA | #18 AWG…(2) #12 AWG | ||||||
| Tightening Torque | 8…12 lbin (0.9…1.4 Nm) | ||||||
| ⋆ Coil voltage required for proper operation (percent of rated coil voltage). | |||||||
| § Temperature inside the panel. | |||||||
| Type | 700S-PK | ||||||
| Electrical | |||||||
| Contact Rating Continuous | 20 A @ 600V AC 10 A @ 600V DC |
||||||
| Ratings Make/ Break |
AC | NEMA A600 | |||||
| DC | NEMA P600 | ||||||
| Additional Contact Ratings for AC Single-Phase Loss | 3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 HP @ 120V AC - N.O./N.C. 20 A resistive heating to 600V AC 20 A Tungsten lighting load to 480V AC |
||||||
| DC Current Ratings Make/Break | Cartridge Cat. No. 700-CMS | ||||||
| DC Switching | Contacts in Series |
Volts DC | |||||
| 24V | 64V | 125V | 250V | 500V | 600V | ||
| 1 | 10 A | 5 A | 2.2 A | 0.55 A | 0.24 A | 0.2 A | |
| 2 | 20 A | 10 A | 5 A | 2 A | 0.7 A | 0.5 A | |
| 3 | — | 15 A | 7 A | 3 A | 1.5 A | 1.0 A | |
| 4 | — | 20 A | 10 A | 5 A | 2.5 A | 1.5 A | |
| Coil Voltage Range⋆ | AC | 85…110% | |||||
| DC | 80…110% | ||||||
| Battery Charging |
85…115% | ||||||
| Coil Consumption | 50 Hz | 60 Hz | |||||
| AC | Inrush | 132 VA | 138 VA | ||||
| Sealed | 19.3 VA | 19 VA | |||||
| DC | Inrush | 12.7 W | |||||
| Sealed | 12.7 W | ||||||
| Mechanical | |||||||
| Mechanically Linked Contacts | All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles | ||||||
| Operating Time | Pickup | AC 10…20 ms DC 30…50 ms |
|||||
| Dropout | AC 10…20 ms DC 20…33 ms |
||||||
| Construction | |||||||
| Contact Arrangement | 2 to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum) |
||||||
| Contact Material/Design | Silver Cadmium Oxide | ||||||
| Mechanical (Mechanically-Linked Contacts) | All contacts, are mechnically linked per IEC 947-5-1 Annex L for 2 to 12 poles | ||||||
| Mounting | Panel mount or strip mount recommended | ||||||
| Environmental | |||||||
| Operating§ Temperature | -20…+65 °C (-4…+149 °F) | ||||||
| Storage | -40…+65 °C (-40…+149 °F) | ||||||
| CSA certified, CSA file #LR1234, UL listed, UL file #E14840, Guide NKCR, CE certified IEC 947-5-1, IEC 336-1 CENELEC, BS 4794, VDE 0660, Listed: U.S. Coast Guard and American Bureau of Shipping, UL 508, CSA22.2 | |||||||
| Wire Terminations | |||||||
| Wire size per UL/CSA | #18 AWG…(2) #12 AWG | ||||||
| Tightening Torque | 8…12 lbin (0.9…1.4 Nm) | ||||||
| ⋆ Coil voltage required for proper operation (percent of rated coil voltage). | |||||||
| § Temperature inside the panel. | |||||||
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
|
|
|
|
|