NEMA Heavy-Duty Industrial Relays

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > NEMA Heavy-Duty Industrial Relays > Bulletin 700S-P and 700S-PK Heavy-Duty Safety Control Relay

Bulletin 700S-P and 700S-PK Heavy-Duty Safety Control Relay

Introduction Certifications Product Selection Specifications Approximate Dimensions
Specifications

Type 700S-P
Electrical
Contact Rating Continuous 10 A @ 600V AC
5 A @ 600V DC
Ratings
Make/
Break
AC NEMA A600
DC NEMA P600
Minimum Contact Switching Ratings 10V, 50 mA
DC Switching Contacts
in Series
Volts DC
24V 64V 125V 250V 500V 600V
1 5 A 2.2 A 1.1 A 0.55 A 0.24 A 0.2 A
2 10 A 10 A 5 A 2 A 0.7 A 0.5 A
3 7 A 3 A 1.5 A 1.0 A
4 10 A 5 A 2.5 A 1.5 A
Contact Electrical Life—Resistive Loads 1.5 million operations at 10A break at 120V AC
14 million operations at 1A break at 120V AC
6 million operations at 1A break at 24V DC
Coil Voltage Range⋆  AC 85…110%
DC 80…110%
Battery
Charging
85…115%
Coil Consumption 50 Hz 60 Hz
AC Inrush 132 VA 138 VA
Sealed 19.3 VA 19 VA
DC Inrush 12.7 W
Sealed 12.7 W
Mechanical
Mechanically Linked Contacts All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles
Operating Time Pickup AC – 10…20 ms
DC – 30…50 ms
Dropout AC – 10…20 ms
DC – 20…33 ms
Mechanical Life 10 million operations
Construction
Contact Arrangement 2 to 12 Poles, Double Break Contacts
N.O. or N.C. (8 N.C. Maximum)
Contact Material/Design Silver Nickel/Bifurcated
Mounting Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended
Environmental
Operating Temperature§  -20…+65 °C (-4…+149 °F)
Storage Temperature -40…+65 °C (-40…+149 °F)
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m)
  
⋆ Coil voltage required for proper operation (percent of rated coil voltage).
§ Temperature inside the panel.

Type 700S-PK
Electrical
Contact Rating Continuous 20 A @ 600V AC
10 A @ 600V DC
Ratings
Make/
Break
AC NEMA A600
DC NEMA P600
Additional Contact Ratings for AC Single-Phase Loss 3 Hp @ 240V AC - N.O.
2 Hp @ 240V AC - N.O./N.C.
1 HP @ 120V AC - N.O./N.C.
20 A resistive heating to 600V AC
20 A Tungsten lighting load to 480V AC
DC Current Ratings Make/Break Cartridge Cat. No. 700-CMS
DC Switching Contacts
in Series
Volts DC
24V 64V 125V 250V 500V 600V
1 10 A 5 A 2.2 A 0.55 A 0.24 A 0.2 A
2 20 A 10 A 5 A 2 A 0.7 A 0.5 A
3 15 A 7 A 3 A 1.5 A 1.0 A
4 20 A 10 A 5 A 2.5 A 1.5 A
Coil Voltage Range⋆  AC 85…110%
DC 80…110%
Battery
Charging
85…115%
Coil Consumption 50 Hz 60 Hz
AC Inrush 132 VA 138 VA
Sealed 19.3 VA 19 VA
DC Inrush 12.7 W
Sealed 12.7 W
Mechanical
Mechanically Linked Contacts All contacts are mechanically linked per IEC 947-5-1 annex L for 2 to 12 poles
Operating Time Pickup AC – 10…20 ms
DC – 30…50 ms
Dropout AC – 10…20 ms
DC – 20…33 ms
Construction
Contact Arrangement 2 to 12 Poles, Convertible to
N.O. or N.C. (8 N.C. Maximum)
Contact Material/Design Silver Cadmium Oxide
Mechanical (Mechanically-Linked Contacts) All contacts, are mechnically linked per IEC 947-5-1 Annex L for 2 to 12 poles
Mounting Panel mount or strip mount recommended
Environmental
Operating§  Temperature -20…+65 °C (-4…+149 °F)
Storage -40…+65 °C (-40…+149 °F)
  CSA certified, CSA file #LR1234, UL listed, UL file #E14840, Guide NKCR, CE certified IEC 947-5-1, IEC 336-1 CENELEC, BS 4794, VDE 0660, Listed: U.S. Coast Guard and American Bureau of Shipping, UL 508, CSA22.2
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m)
  
⋆ Coil voltage required for proper operation (percent of rated coil voltage).
§ Temperature inside the panel.