Bulletin 700-PS Solid-State Timing Relay

Product Overview


Click to enlarge - 700PS-235-1


Bulletin 700-PS — Solid State Timing Relay


Standards Compliance


Certifications


Product Selection

Bulletin 700-PS

Click to enlarge - 700PS-235-1 Operating Mode Timing Range⋆ [s] Timing Relay with Self-Contained Potentiometer Unit Timing Relay for Use with External Potentiometer Unit
Cat. No. Cat. No.
On-Delay 0.1…2 700-PSAA1 700-PSRAA1
0.4…8 700-PSBA1 700-PSRBA1
1.5…30 700-PSCA1 700-PSRCA1
6…120 700-PSDA1 700-PSRDA1
Off-Delay 0.1…2 700-PSPA1 700-PSRPA1
0.4…8 700-PSRA1 700-PSRRA1
Cat. No. 700-PSPA1 1.5…30 700-PSTA1 700-PSRTA1
6…120 700-PSUA1 700-PSRUA1
  
⋆ The maximum range may be 50% greater and the minimum range may be 50% less than the values specified.
‡ All Cat. Nos. are factory stocked

Accessories

Accessories

Click to enlarge - 700PS-235-3 Description Cat. No.
Adapter Plate — For mounting Bulletin 700-PS timers directly on a panel or on Bulletin 700-MP universal mounting strips. 700-N25
Adapter for Bulletin 700-R, -RM Relays
Allows you to mount the Bulletin 700-PS timer on a 1…4 pole Bulletin 700-R or -RM relay.
700-N26
  Timing Range⋆  Resistance[mW]  
Cat. No. 700-N25 0.1…2
(0.4…8)
0.75 ‡  700-N35
Click to enlarge - 700PS-235-4 0.1…2
(0.4…8)
0.75 ‡  700-N35
1.5…30 2.0 ‡  700-N36
Cat. No. 700-N26 6…120 3.5 ‡  700-N37
  
‡ This Cat. No. includes only the potentiometer. Order Cat. No. 800T-N37 for the potentiometer operator and housing.

Specifications

Bulletin 700-PS

Supply Voltage 110…120V AC, 50/60 Hz
Power Requirement 4 VA, 2.5 W
Output Contact Ratings NEMA B600 and P300. See pub. 700-SG003_-EN-P.
Operating Temperature Range –20…+60 °C ambient (–4…+140 °F)
Reset Time 20 ms
Repeat Accuracy, Constant Voltage and Temperature ±2% of setting or ±0.004 s, whichever is greater
Standards NEMA B600, NEMA P300
Certifications UL Listed, Class I, Division 2, Groups A, B, C, and D, CSA Certified
  

Operation

The timer must be energized continuously (L1-L2). ON-Delay: When the initiating contact closes, timing begins. At time-out, the output contact closes. OFF-Delay: When the initiating contact closes, the output contact closes instantly. When the initiating contact re-opens, timing begins. At time-out, the output contact re-opens.

Typical Wiring Diagram§ 

Click to enlarge - 700PS-236-1


Attention — To avoid damage to timer, do not switch any load in addition to timing relay at terminals S1–S2. Do not apply an external voltage to terminals S1–S2.

§ External Potentiometer units have R1, R2 terminals for connecting the potentiometer.


Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Bulletin 700-PS

Click to enlarge - 700PS-237-1
Bulletin 700-PS Timer Mounted on the Adapter PlateCat. No. 700-N25Approximate Shipping Wt. 0.45 kg (1 lb)


Click to enlarge - 700PS-237-2
Bulletin 700-PS Timer Mounted on a 4-PoleBulletin 700-P or -PK, or 2-Pole Bulletin 700-PH RelayApproximate Shipping Wt. 1.02 kg (2.3 lb)


Click to enlarge - 700PS-237-3
Bulletin 700-PS Timer Mounted on a 4-PoleBulletin 700-R or -RM RelayApproximate Shipping Wt. 1.25 kg (2.8 lb)