NEMA Heavy-Duty Industrial Relays

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > NEMA Heavy-Duty Industrial Relays > Bulletin 700-RTC Solid-State Timing Relay

Bulletin 700-RTC Solid-State Timing Relay

Introduction Standards Compliance and Certifications Product Selection Accessories Specifications Approximate Dimensions
Specifications

Voltage and Power Requirements

AC Voltage
+10% –15% 50/60 Hz
Total Power Required Initiate Terminal Power Maximum Allowable Leakage
Current
Coil Code
24V AC 8 VA 4 VA 10 mA U24
110/120V AC 9 VA 4 VA 2.4 mA U1
  

DC Voltage
+10% –20%
Total Power Required Initiate Terminal Power Maximum Allowable Leakage
Current
Coil Code
24V DC 10 W 5 W 10 mA U24
120V DC 11 W 5 W 2.4 mA U1
  

Type 700-RTC
Contact Rating
(See pub. 700-SG003*)
NEMA B600 600V AC, 5 A
NEMA P300 300V DC, 5 A
Contact Arrangement 1…4 poles. Max. of 2 timed and 2 instantaneous.
Available in any combination of N.O. and N.C. contacts
Contact Material W (tungsten in a controlled gas atmosphere)
Operating Mode Convertible to ON-Delay or OFF-Delay
Timing Range 0.05…64 min.
Reset Time 25 ms
Repeat Accuracy ±1% (or ±50 ms) at constant voltage and temperature
Mounting Panel or strip mount
Surge Suppression Not required. Timers have internal suppression
Certifications UL Listed, File E10314, Guide NOIV, CSA Certified, File LR11924
Suitable for use in Class I, Division 2, Groups A, B, C, and D
Maximum Allowable Leakage Current 24V AC/DC 10 mA
110/120V AC,
120V DC
2.4 mA
Ambient Temperature⋆   
Operating: –20…+60 °C (–4…+140 °F)
Storage: –20…+60 °C (–4…+140 °F)
  
⋆ Continuous duty units placed close to each other (3 in a row) have a temperature range of –20…+45 °C (–4…+113 °F) or should have air circulated around the units. Approximate space of 3/4 in (mm) on all sides is needed.

Typical Wiring Diagram

Click to enlarge - 700RTC-242-1