Contact Ratings
The timing unit is provided with a contact block having one normally open and one normally closed contact. Circuits wired to a contact block must be of the same polarity. Contacts are silver of the quick make and break type. Contacts have a control circuit rating listed below.
Those relays provided with auxiliary contacts have a similar contact block mounted on the solenoid frame and operated directly by the solenoid. The auxiliary contact block used on the AC relays is the same as the contact block on the timing unit and has the same rating. On the DC relays, the auxiliary contacts are rated 5A, 115V; 1A, 230V.
Typical Wiring Diagrams
Auxiliary Contacts
ON-DELAY
|
|
OFF-DELAY
|
|
| Bulletin 849 and 849A (AC Only) Contact Ratings | |||||||
| NEMA A600 Maximum AC Contact Rating Per Pole | DC | ||||||
| Max. AC Voltage 60 or 50 Hz |
A | Continuous Carrying Current |
VA | Voltage Range |
Ampere Rating |
||
| Make | Break | Make | Break | ||||
| 120 | 60 | 6.00 | 10 | 7200 | 720 | 115…125 | 0.4 |
| 240 | 30 | 3.00 | 10 | 7200 | 720 | ||
| 480 | 15 | 1.50 | 10 | 7200 | 720 | 230…250 | 0.2 |
| 600 | 12 | 1.20 | 10 | 7200 | 720 | ||
Contact Designations
Refer to diagrams in Product Selection tables.
- N.O.T.C.— Normally Open Timed Closed
- N.C.T.O.— Normally Closed Timed Open
- N.C.T.C.— Normally Closed Timed Closed
- N.O.T.O.— Normally Open Timed Open